ECB violations
Womens Leadership School Queens, Queens • Block 09707 • Lot 0048
32 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 27, 2026 | 35732245J | ACTIVE | CLASS - 2 | REISSUE#35719690L DATE OF ISSUE:05.12.2025 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT THE TIME OF INSPE... | $3,125 | $0 | Jun 4, 2026 |
| Dec 17, 2025 | 39170686Z | ACTIVE | CLASS - 2 | OIL LEAKING IN MACHINE ROOM , REPAIR / INCAR 2ND FLOOR CALL BUTTON DOESN'T LIGHT UP , REPAIR | $625 | $0 | Dec 24, 2025 |
| May 12, 2025 | 35719690L | ACTIVE | CLASS - 2 | REISSUE#35677445P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT OIL VAULT ROOM WATER PENETRATION INT... | $3,125 | $0 | Jul 7, 2025 |
| May 12, 2025 | 35719691N | RESOLVE | CLASS - 2 | REISSUE#35677446R EMERGENCY SIGNS AT ELEVATOR CALL STATION S MISSING DEFECTIVE OR NON-COMPLIANT WITH SECTIONS REQUIRE... | $1,562 | $0 | Jul 7, 2025 |
| May 16, 2024 | 35677444N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OIL TANK ROOM VAULT OUTSIDE WATER ENTERING VAULT BX PIPE'S WAT... | $625 | $0 | Aug 20, 2024 |
| May 16, 2024 | 35677446R | RESOLVE | CLASS - 2 | REISSUE 35671748P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. EMERGENCY SIGNS AT ELEVATOR CALL STATION MI... | $1,562 | $0 | Aug 20, 2024 |
| May 16, 2024 | 35677445P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. LIGHTS NOT WORKING IN OIL VAULT 4 OF 6 BROKEN NOT WORKING AND ... | $625 | $0 | Aug 20, 2024 |
| Apr 24, 2023 | 35671748P | RESOLVE | CLASS - 2 | REISSUE:35473588H EMERGENCY SIGNS ELEVATOR PROMIT STATIONTS MISSING EMEGENCY SIGN AT BASEMENT.REM:COMPLY WITH CODE. | $1,562 | $0 | Aug 1, 2023 |
| Apr 5, 2022 | 35650766X | RESOLVE | CLASS - 2 | REISSUED#35555790K.EMERGENCY SIGNS.AT ELEVATOR CALL STATIONS MISSING,DEFECTIVE AS NON-COMPLIANT WITH SECTION REQUIREM... | $1,562 | $0 | Jul 19, 2022 |
| Apr 5, 2022 | 35650767H | RESOLVE | CLASS - 2 | REISSUED#35555792Y.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.AT TIME OF INSPECTION OBSERVED AT ROOF MECHA... | $1,562 | $0 | Jul 19, 2022 |
| Apr 1, 2022 | 39059327L | RESOLVE | CLASS - 1 | DEVICE WAS FOUND OUT OF SERVICE ON THE 2ND FLOOR NOT LEVEL. THIS IS THE ONLY ELEVATOR IN THE BUILDING. RESTORE TO SER... | $1,250 | $0 | Apr 19, 2022 |
| Mar 16, 2021 | 35555790K | RESOLVE | CLASS - 2 | REISSUED35473588H EMERGENCY SIGNS@ELEVATOR CALL STATIONS MISSING,DEFECTIVE OR NONCOMPLIANT W/SEC REQUIREMENTS.NOTED O... | $1,562 | $0 | Jun 15, 2021 |
| Mar 16, 2021 | 35555791M | RESOLVE | CLASS - 2 | REISSUED35473587X FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NO FIRE STOPPING PER BC712.3;27-345.NOTED OBSERVED... | $3,125 | $0 | Jun 15, 2021 |
| Mar 16, 2021 | 35555792Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER.NOTED OBSERVED:@ROOF'S MECHANICAL/GENERATOR&HOT WATER TANKRM,STRUCTU... | $625 | $0 | Jun 15, 2021 |
| Apr 23, 2020 | 35473587X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTE: AT BASEMENT LEVEL IN E... | $1,250 | $0 | Aug 18, 2020 |
| Apr 23, 2020 | 35473588H | RESOLVE | CLASS - 2 | EMERGENCY SIGNS AT ELEVATOR CALL STATIONS MISSING DEFECTIVE OR NON COMPLIANT W/SECTION REQUIREMENTS. NOTE: AT BASEMEN... | $625 | $0 | Aug 18, 2020 |
| Sep 11, 2018 | 32097014N | RESOLVE | CLASS - 2 | 15,32A,50A-50E. 50A-SIGHT GLASS IN REAR OF BOILER MISSING; 50B-CLEAN BASE OF CHIMNEY; 50C-WATER LEAK ON WATER PIPES; ... | $0 | $0 | Nov 27, 2018 |
| Mar 8, 2017 | 35229174N | RESOLVE | CLASS - 2 | REISSUE: 35177288J. AT GAS METER ROOM, WALL CRACKED. RMDY: COMPLY WITH SUMMONS. | $0 | $0 | May 3, 2017 |
| Apr 11, 2016 | 35177288J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN IN CODE COMPLIANT MANNER. REISSUE VIO# 34958185M. NOTE: @ TIME OF INSP CONDITION REMAIN THE SAME ... | $0 | $0 | Jul 19, 2016 |
| Apr 11, 2016 | 35177289L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES REISSUE VIO# 34891570P. NOTE: @ TIME OF INSP CONCLITION REMAIN THE ... | $0 | $0 | Jul 19, 2016 |
| Feb 3, 2015 | 35112044X | RESOLVE | CLASS - 2 | REISSUE 35085203N.EXTERIOR BRICK CHIMNEY HAS APP 5'VERTICAL CRACK WESTSIDE.REM:MAINTAIN BLDG. | $0 | $0 | Mar 31, 2015 |
| Feb 3, 2015 | 35112045H | RESOLVE | CLASS - 2 | REISSUE 34958185M.CMU WALL IS GAS METER ROOM HAS CRACKS.REM:MAINTAIN BLDG. | $0 | $0 | Mar 31, 2015 |
| Mar 3, 2014 | 35085203N | RESOLVE | CLASS - 2 | RE-ISSUE # 35027944P. EXTERIOR BRICK CHIMNEY HAS VERTICAL CRACK 5'LONG AT WEST SIDE. REMEDY: REPAIR CHIMNEY. | $0 | $0 | Jun 3, 2014 |
| Jul 26, 2013 | 35027944P | RESOLVE | CLASS - 2 | REISSUE 34958184K. EXTERIOR BRICK CHIMNEY HAS VERTICAL CRACK 5' LONG (WEST SIDE). REMEDY: REPAIR CHIMNEY. | $0 | $0 | Sep 17, 2013 |
| Jul 17, 2012 | 34958185M | RESOLVE | CLASS - 2 | THE CONCRETE BLOCK WALL IS CRACKED LOCATED IN THE GAS METER ROOM AT THE CELLAR ROOM. REMEDY: REPAIR &/OR REPLACE BLOC... | $0 | $0 | Sep 18, 2012 |
| Jul 17, 2012 | 34958184K | RESOLVE | CLASS - 2 | REISSUE: 34891570P BRICK CHIMNEY IS VERTICALLY CRACKED APPROX 5'FEET LONG AT THE ROOF LEVEL. REMEDY: REPAIR &/OR REPL... | $0 | $0 | Sep 18, 2012 |
| Apr 8, 2011 | 34891570P | RESOLVE | CLASS - 2 | EXTERIOR BRICK CHIMNEY IS VERTICALLY CRACKED APPROX 5' FEET LONG AT THE ROOF LEVEL. REMEDY: REPLACE/REPLACE CRACKED B... | $0 | $0 | May 17, 2011 |
| Feb 24, 2009 | 34761651L | RESOLVE | CLASS - 2 | SMOKE DETECTORS IS NOT FULLY ATTACHED TO THE CEILING LOCATED AT THE MECHANICAL RM AT ROOF LVL REM: FULLY ATTACH SMOKE... | $0 | $0 | May 12, 2009 |
| Mar 26, 2004 | 34419940Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN NOTED:2ND FL STAIRCASE A 6FT HORIZONTAL STRUCTURA L CRACK ON BOTTOM OF STAIRS.REMEDY: MAKE ALL NE... | $0 | $0 | Jun 22, 2004 |
| Mar 28, 2003 | 34383119J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. NOTED: AT GYMNASIUM IN MALE BATHROOM DUE TO SUSTAINED WATER DAMAGE CEILING IS CRACKED, PEELING A... | $0 | $0 | Jun 24, 2003 |
| Mar 28, 2003 | 34383118H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN. NOTED: AT STAIRCASE "A" CEILING AT ROOF PLASTER PEELING DUE TO WATER DAMAGE ALSO IN STAIRCASE "A... | $0 | $0 | Jun 24, 2003 |
| Nov 24, 1998 | 34191671R | RESOLVE | Non-Hazardous | ALTERED BLDG OCCUPIED W/O A VALID C OF O. C OF O 400680802 TEMP EXP 10/2/98. REMEDY: OBTAIN VALID C OF O. | $0 | $0 | Sep 21, 1999 |