ECB violations
175-02-175-20 88 Avenue, Queens • Block 09833 • Lot 0004
45 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 13, 2025 | 39147776R | ACTIVE | CLASS - 2 | CLASS 2 ITEM: PROVIDE BOTTOM SWING DOOR TO SELF CLOSE. | $625 | $0 | Jun 16, 2025 |
| Nov 9, 2022 | 39073622P | ACTIVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). IN CAR PHONE NOT WORKING. BRAKE MAINTENANCE TAG EXPIRED ... | $1,250 | $0 | Nov 15, 2022 |
| Nov 9, 2022 | 39073654J | RESOLVE | CLASS - 2 | COMBUSTIBLE STORAGE IN BOILER ROOM, IMPROPER FLUE PIPE SUPPORT. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFI... | $625 | $0 | Nov 15, 2022 |
| Nov 9, 2022 | 39073653H | ACTIVE | CLASS - 2 | FOUND HB SMITH BOILER MODEL #28HE-10, SERIAL #28HE-10-142395 UNREGISTERED. REGISTER THE BOILER AND SUBMIT A CERTIFICA... | $625 | $0 | Nov 15, 2022 |
| Nov 9, 2022 | 39073655L | ACTIVE | CLASS - 2 | FOUND AO SMITH BOILER MODEL # HW-670 300 SERIAL # 2035120687564 UNREGISTERED., MAINTAIN BOILER; REGISTER THE BOILER A... | $625 | $0 | Nov 15, 2022 |
| Apr 26, 2022 | 39061024R | RESOLVE | CLASS - 2 | I OBSERVED IN CELLAR/BASEMENT EXCESSIVE COMBUSTIBLE STORAGE IN THE BOILER ROOM( RM 141), NO STORAGE SHALL BE KEPT IN ... | $625 | $0 | May 11, 2022 |
| Apr 26, 2022 | 39061022N | RESOLVE | CLASS - 2 | AT FIRST FL, SMOKE DOOR NEAR SOCIAL SERVICE OFFICE, AT 2ND FL, SMOKE DOOR NEAR 243 RM, AT ATTIC LEVEL, EXIT DOOR & RO... | $625 | $0 | May 11, 2022 |
| Apr 26, 2022 | 39061023P | RESOLVE | CLASS - 2 | AT OUTDOOR PLAYGROUND, ON THE FACADES, THREE UNSUPPORTED WINDOW A/C UNITS, REPAIR AND/OR REPLACE | $625 | $0 | May 11, 2022 |
| Oct 18, 2021 | 39049492X | RESOLVE | CLASS - 2 | NEED CORRECT SUPPORT FOR FLUEPIPE AND NOT HANG FROM HEADER TERMINATION OF COMBUSTION AIR NOT 30" HIGH CORRECT VIOLATI... | $625 | $0 | Nov 12, 2021 |
| Oct 18, 2021 | 39049493H | ACTIVE | CLASS - 2 | CLEAN BASE OF CHIMNEY REMOVE STORAGE IN BOILER ROOM CLEAN BASE OF CHIMNEY UNREGISTERED BOILER CORRECT VIOLATION & SEN... | $625 | $0 | Nov 12, 2021 |
| Feb 19, 2020 | 39017915M | RESOLVE | CLASS - 2 | WATER LEAKS FROM ROOF, CAUSING WATER DAMAGE IN STAIRCASE A AND OTHER AREAS IN THE BUILDING. PARTS OF WALL HAVE FALLEN... | $625 | $0 | Feb 21, 2020 |
| Feb 19, 2020 | 35473150N | ACTIVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT IN USE. I OBSERVED IN THE BASEMENT,IN ROOM 103/GAS ROOM TEMPORARY R... | $800 | $0 | May 12, 2020 |
| Feb 19, 2020 | 39017916Y | RESOLVE | CLASS - 2 | BOILER ROOM FIRES STOP MISSING BY MAIN DOOR AROUND PIPES AND MISSING SHEETROCK SECTION OF WALL BY THE MAIN DOOR., PRO... | $1,250 | $0 | Feb 21, 2020 |
| Sep 12, 2019 | 38271314Y | ACTIVE | CLASS - 1 | (97X17/11L10)(97X17)UPON INSPECTION DEVICE WAS FOUND OUT OF SERVICE.RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDO... | $1,250 | $0 | Dec 31, 2019 |
| May 1, 2019 | 39002513H | RESOLVE | CLASS - 1 | B 154 NO CLEAN OUT ON CHIMNEY BASE, WRONG WATER PIPE SUPPORT, WRONG AND NOT ENOUGH FLUE SUPPORT CORRECT ALL VIOLATING... | $0 | $0 | May 2, 2019 |
| May 1, 2019 | 39002510M | ACTIVE | CLASS - 1 | B 154 FOUND HB SMITH OIL FIRED BOILER, WITH RECURRING CONDITION VIOLATION # 32098180N NOT REGISTERED, REGISTER THE BO... | $0 | $0 | May 2, 2019 |
| Feb 6, 2019 | 32098180N | RESOLVE | CLASS - 2 | B254,50A-50D. 50A-DISCHARGE PIPE ON RELIEF VALVE CANNOT HAVE THREADS 50B-MISSING INSULATION ON PIPES; 50C-MISSING VEN... | $0 | $0 | Jun 25, 2019 |
| Feb 6, 2019 | 32098181P | RESOLVE | CLASS - 2 | B254,50A-50C. 50A-SOOT ON BOILER AND FLOOR; 50B-NO INSULAITON ON PIPE50C-NEED CORRECT SUPPORT FOR FLUE PIPE. | $0 | $0 | Jun 25, 2019 |
| Aug 15, 2018 | 32097373P | ACTIVE | CLASS - 2 | HB SMITH 28HE-10 BOILER: 50A MISSING GUARDS ON GAUGE GLASS 50B-BODY DRAIN PLUGGED ON RELIEF VALVE; 50C-FUMERS AT BURN... | $0 | $0 | Oct 23, 2018 |
| Aug 15, 2018 | 32097372N | RESOLVE | CLASS - 2 | B254,15,33A,39,50A,50B. HB SMITH 28A- 6 BOILER: 50A-IMPROPER SUPPORT FOR FLUE PIPE; 50B- NO CLEAN OUT AT CHIMNEY BASE... | $0 | $0 | Oct 23, 2018 |
| Mar 21, 2018 | 32093366Z | RESOLVE | CLASS - 2 | 15,32A,50A,50B. B354-50A-WRONG MATERIAL ON FLUE SUPPORT; B-NO CLEAN OUT ON CHIMNEY BASE. CORRECT ALL VIOLATING CONDIT... | $0 | $0 | May 29, 2018 |
| Mar 21, 2018 | 32093365R | ACTIVE | CLASS - 2 | 36,15,50A,50B. B254-36 FOUND HB SMITH BOILER NOT REGISTERED. 50A-NO STORAGE IN BOILER ROOM; B-BURNER HAS FUMES ON STA... | $0 | $0 | May 29, 2018 |
| Oct 4, 2017 | 35279860Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35272435X ISSUED ON 07/13/17 & TO FILE A C... | $4,000 | $0 | Nov 21, 2017 |
| Sep 19, 2017 | 38257667Z | RESOLVE | CLASS - 2 | 97X10)DEVICE INOPERATIVE, RETURN TO SERVICE. | $0 | $0 | Nov 28, 2017 |
| Jul 13, 2017 | 35272093P | ACTIVE | CLASS - 2 | FAILURE TO INSTALL GROUND-FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. OBSERVED IN LAUNDRY ROOM: RECEPTAC... | $0 | $0 | Oct 17, 2017 |
| Jul 13, 2017 | 35272435X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN CELLAR GAS METER ROOM W/ NO PERMANENT VENTILATION. APP... | $0 | $0 | Sep 5, 2017 |
| Jul 13, 2017 | 35272092N | ACTIVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN BASEMENT OF ANNEX BUILDING: MAIN GROUNDING CONDUCTOR CLAMP FOR BUIL... | $0 | $0 | Oct 17, 2017 |
| Jan 17, 2017 | 35225867H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. OBSERVED ON 01/17/ 17 STORAGE IN GAS METER ROOM. NO STORAGE SHALL ... | $0 | $0 | Mar 21, 2017 |
| Dec 28, 2016 | 38251430N | RESOLVE | CLASS - 1 | 97X07 ONLY ELEVATOR IN BLDG OUT OF SERVICE. THE DEVICE IS 0/0/0 CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. RE... | $0 | $0 | Mar 21, 2017 |
| Dec 16, 2016 | 38251380Y | RESOLVE | CLASS - 1 | 97X17 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. () EQUIPMENT - ELEVATOR AS PER BC 3001.2 AND 27-987. DOB REC... | $0 | $0 | Jan 24, 2017 |
| Sep 27, 2010 | 38212997M | RESOLVE | CLASS - 2 | 100-M-07 PROVIDE FIRE EXTINGUISHER IN MOTOR RM.100-R-09 REMOVE OR CAP SPRINKLER ABOVE CONTROLLER BOARD.53-B-14 SHORTE... | $0 | $0 | Nov 16, 2010 |
| Apr 14, 2008 | 38183758P | RESOLVE | Non-Hazardous | 55Y13,40M07,86M05,51M07. 40-PROVIDE SIGNAGE ON DOOR. 51-PROVIDE ROPE GUARD. | $0 | $0 | Jun 3, 2008 |
| Feb 24, 2004 | 34431228M | RESOLVE | Non-Hazardous | WORK W/OUT A PERMIT.EXPIRED PERMIT.PERMIT #401138675 FOR HEAVY DUTY SIDEWALK SHED.REMEDY:RENEW PERMIT | $2,500 | $0 | Apr 13, 2004 |
| Feb 24, 2004 | 34431229Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL.NOTED:(1)CRACKED BRICK FACADE AT VARIOUS LOCATIONS ON NORTHERN OR FRONT ELEVAT... | $2,500 | $0 | Apr 13, 2004 |
| Jul 5, 2000 | 32019057J | RESOLVE | Hazardous | 41A,41C,49,48A.41A-FIRE CHAMBER DOOR CRACKED AND NO CLOSING FLAME COMING OUT.49-NO GAUGE ON HOT WATER AFTER MIXING VA... | $2,500 | $0 | Aug 22, 2000 |
| May 3, 1999 | 34191604R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL. DEFECT IS: PLASTER AND PAINT HAVE BEEN EXFOLIATED ON ALL HEIGHT FRONT AND... | $2,500 | $0 | Jun 22, 1999 |
| Apr 6, 1999 | 34191329L | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING WALL DEFECT IS LOOSE AND MISSING MORTAR JOINTS AT CORNICES A T 3RD STORY FRONT ... | $2,500 | $0 | Jun 1, 1999 |
| Jul 17, 1998 | 34180232L | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR BLDG WALL. DEFECT IS: PART OF EAST CORNEREXTERIOR WALL LOOSE SOME BRICKS & MORTAR. REMED... | $0 | $0 | Oct 20, 1998 |
| Jul 14, 1998 | 38075823Y | RESOLVE | Non-Hazardous | 16H,36O,50O,59Y,46O,57O,74M, 16- CEASE USE DUE TO WORN GIBBS ON LOBBY SHAFT DOOR . 74- NO METAL CONTAINER WITH COVER ... | $2,500 | $0 | Sep 1, 1998 |
| Jun 15, 1998 | 34179591P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECT IS: CRACKED AND MISSING BRICKS AT THE EAST CORNER NEXT TO THE PARKING LOT CORNER OF EXTERI... | $2,500 | $0 | Sep 29, 1998 |
| May 10, 1993 | 38032247P | RESOLVE | Non-Hazardous | 33I 35K 58O 59O 55X 53L 03O 39F 46L 15M 36W 26M 30O 03L 15P 33 REPAIR REPLACE GLASS DOOR LOCK & HANDLE RESECURE & REP... | $5,000 | $0 | Jun 22, 1993 |
| Nov 27, 1991 | 38016518H | RESOLVE | Non-Hazardous | 2X,7L,16H,18D,29O,30O,33I,55X,57O,58O,59O,73#,74#, 16 4TH FLOOR 18 MAIN FLOOR 33 SKYLIGHT GLASS 73 PERFORM 5 YR TEST ... | $1,000 | $0 | Feb 4, 1992 |
| Jan 30, 1991 | 38004348X | RESOLVE | Non-Hazardous | 2X,29O,300,331,55X,57O,58O,59O,#73, (33) SKYLIGHT GLASS. (73) CONDUCT A 5 YEAR TEST. | $150 | $0 | Jul 24, 1991 |
| Oct 28, 1988 | 34011919K | RESOLVE | Non-Hazardous | ALTERED BLDG. OCCUPIED WITHOUT A VALID CERT. OF OCCUPANCY . REMEDY: DISCONTINUE ILLEGAL USE UNTIL A CERT. OF OCCUPANC... | $0 | $0 | Dec 20, 1988 |
| Oct 28, 1988 | 34014492Y | ACTIVE | Hazardous | FAILURE TO PROVIDE REQUIRED MEANS OF EGRESS FROM EVERY FLOOR . REMEDY: EGRESS DOOR. | $400 | $0 | Dec 13, 1988 |