ECB violations
175-02 Jamaica Avenue, Queens • Block 10215 • Lot 0001
41 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| May 28, 2026 | 35731759M | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED: EXTERIOR EXIT DOORS ARE NOT SELF-CLOSING PROPERLY ON THE ROOF STAIRCASE "C" AND CA... | $625 | $0 | Jun 18, 2026 |
| May 28, 2026 | 35731756R | ACTIVE | CLASS - 2 | RE-ISSUE #35725483J. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: FPSC INTERIOR DOORS DO NOT SELF-CL... | $3,125 | $0 | Jun 18, 2026 |
| May 28, 2026 | 35731757Z | ACTIVE | CLASS - 2 | RE-ISSUE #35725482H. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ON STAIRCASE "C" BETWEEN PENTHOUSE... | $3,125 | $0 | Jun 18, 2026 |
| May 28, 2026 | 35731758K | ACTIVE | CLASS - 2 | RE-ISSUE #35725481X. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: PENTHOUSE 1 HAS (3)SNOW BLOWERS BE... | $3,125 | $0 | Jun 18, 2026 |
| Dec 5, 2025 | 39169428H | ACTIVE | CLASS - 2 | INCAR EMERGENCY OUTSIDE COMM INOPERATIVE , REPAIR | $625 | $0 | Dec 23, 2025 |
| Sep 23, 2025 | 35725483J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED INTERIOR FPSC DOORS NOT WORKING PROPERLY AT PENTHOUSE #1... | $1,250 | $0 | Oct 20, 2025 |
| Sep 23, 2025 | 35725482H | ACTIVE | CLASS - 2 | REISSUE #35692269K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED CRUMBLING AND MISSING PLASTER OR CEI... | $1,250 | $0 | Oct 20, 2025 |
| Sep 23, 2025 | 35725481X | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT PENTHOUSE #1, UNLAWFUL STORAGE OF (3)GAS POWERED SNOW... | $2,500 | $0 | Oct 21, 2025 |
| Oct 21, 2024 | 35692269K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED STAIR "C"HAS SPALLING AND CRACKING/MISSING PLASTER ON CE... | $625 | $0 | Dec 3, 2024 |
| Oct 21, 2024 | 35692267R | RESOLVE | CLASS - 2 | REISSUE #35663562R. EXIT DOOR NOT SELF-CLOSING. NOTED EXTERIOR DOORS AT CAFETERIA EXITS ARE CORRODED AT THE BOTTOM AN... | $1,562 | $0 | Dec 3, 2024 |
| Oct 21, 2024 | 35692268Z | RESOLVE | CLASS - 2 | REISSUE #35663561P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED STAIR A EXTERIOR GLASS PANEL CRACKED... | $1,562 | $0 | Dec 3, 2024 |
| Jul 7, 2023 | 35663562R | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED: AT EXIT #2, ONE DOOR AND CAFETERIA MAIN ENTRY/EXIT ONE DOOR DO NOT CLOSE PROPERLY.... | $625 | $0 | Sep 26, 2023 |
| Jul 7, 2023 | 35663561P | RESOLVE | CLASS - 2 | REISSUE #35654911L FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT STAIRWAY BOTH SIDE, FROM 2ND FLOO... | $1,562 | $0 | Sep 26, 2023 |
| May 26, 2022 | 35654911L | RESOLVE | CLASS - 2 | REISSUE#35577112Z FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT STWY-A BETWEEN 4TH FLR & 3R... | $1,562 | $0 | Sep 13, 2022 |
| May 26, 2022 | 35654912N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED:OBSERVED AT(CELLAR LEVEL)ELECTRICAL METER ROOM/RM#C13 HAS... | $625 | $0 | Sep 13, 2022 |
| Jun 17, 2021 | 39043001P | RESOLVE | CLASS - 2 | GAS CONNECTION IS MISSING A SHUTOFF VALVE AND HARD PIPE TO GAS PRESSURE GAUGE AT TOP OF BURNER/WHISKER SWITCH IS DEFE... | $625 | $0 | Jun 17, 2021 |
| Jun 17, 2021 | 39043002R | RESOLVE | CLASS - 2 | GAS CONNECTION IS MISSING A SHUTOFF VALVE AND HARD PIPE TO GAS PRESSURE GAUGE AT TOP OF BURNER/WHISKER SWITCH DEFECTI... | $625 | $0 | Jun 17, 2021 |
| May 27, 2021 | 35577113K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED AT 4TH FL ROOM 415;SPALLING PLASTER WITHIN THE CLO... | $625 | $0 | Sep 14, 2021 |
| May 27, 2021 | 35577111R | RESOLVE | CLASS - 2 | REISSUED#35495507Y FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NOTED: OBSERVED LOOSE FLASHING AT ROOF LEVEL,AT... | $1,562 | $0 | Sep 14, 2021 |
| May 27, 2021 | 35577114M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES: NOTED: OBSERVED LOOSE& DELAMINATING BRICKS AT EAST ELEVATION APPROX ... | $2,500 | $0 | Sep 14, 2021 |
| May 27, 2021 | 35577112Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: NOTED: OBSERVED CRACKE GLASS WINDOW PANEL AT STAIR'A'BETWEEN 3RD &... | $625 | $0 | Sep 14, 2021 |
| Mar 24, 2021 | 39038179X | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY : INSTAL... | $1,250 | $0 | Apr 16, 2021 |
| Mar 24, 2021 | 39038180N | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS PER 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. REMEDY : INSTAL... | $1,250 | $0 | Apr 15, 2021 |
| May 13, 2020 | 35495507Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NOTED AT ROOF LEVEL METAL FLASHING IN SIDE THE PARAPET LOOSE AN... | $625 | $0 | Aug 25, 2020 |
| Jun 7, 2019 | 35414953R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. STAIRCASE UPPERLEVEL TO CHILL ROOM AREA HOLES MADE IN STAIRCAS... | $0 | $0 | Sep 10, 2019 |
| Oct 9, 2018 | 35361645Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: ROOM #415, LEAK IN THE CLOSET DUE TO ROOF LEAK. MOD BUI... | $0 | $0 | Dec 18, 2018 |
| Oct 9, 2018 | 35361644R | RESOLVE | CLASS - 2 | REISSUE #35335270M FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: ROOF EXIT, DOOR HAVE NO PUSH BAR AND... | $0 | $0 | Dec 18, 2018 |
| Dec 19, 2016 | 35222478K | RESOLVE | CLASS - 2 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O OR DOB RECORDS. NOTED: @ TIME OF INSP OBSERVED ROOM C-11, @ CELLAR L... | $0 | $0 | Feb 7, 2017 |
| Nov 9, 2016 | 35216472Z | RESOLVE | CLASS - 2 | REISSUE #35107194P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: WATER PENETRATION INTO FEMALE LOCKER ROO... | $0 | $0 | Feb 7, 2017 |
| Aug 1, 2014 | 35107194P | RESOLVE | CLASS - 2 | REISSUE 35027761M. WATER PENETRATION INTO FEMALE LOCKER ROOMS C28A, C28B. REMEDY: SEAL PENETRATIONS. | $0 | $0 | Oct 28, 2014 |
| Aug 1, 2014 | 35107195R | RESOLVE | CLASS - 2 | ILLEGAL HARDWARE NOTED @MOST CLASSROOM DOORS W/DOOR STOPS @BASE OF DOORS. REMEDY: REMOVE HARDWARE. | $0 | $0 | Oct 28, 2014 |
| Jul 11, 2013 | 35027761M | RESOLVE | CLASS - 2 | WATER PENETRATION AT CELLAR LEVEL FOUNDATION IN FEMALE CHANGING RM C28A,C28B. REMEDY: MAINTAIN WATER PROOFING. | $0 | $0 | Sep 17, 2013 |
| Jul 11, 2013 | 35027762Y | RESOLVE | CLASS - 2 | EXCESSIVE STORAGE OF COMBUSTABLE MATERIALS COMPUTERS,TABLES,CHAIRS & OTHER EQUIPMENT STORED IN EMERGENCY GENERATOR RO... | $0 | $0 | Sep 17, 2013 |
| Dec 23, 2009 | 38208168N | RESOLVE | CLASS - 2 | 97B10 PERFORM ALL NECESSARY ALTERATIONS TO MAKE 5YRS BUFFER TEST POSSIBLE | $2,500 | $0 | Feb 16, 2010 |
| May 1, 2006 | 38158746N | RESOLVE | Non-Hazardous | 85U05/02L10/39O02/30B07/71B07. 02L10-EMERGENCY PHONE, 39O02-REMOVE BOXES NOT BELONGING THERE, 30B07-PIN FINALS, 71B07... | $0 | $0 | Jun 20, 2006 |
| May 1, 2006 | 38158747P | RESOLVE | Non-Hazardous | 85U05/71B07/66Q03. 71B07-UNDER THE CAR LIGHT GUARD, 66Q03-SUMP PUMP COVER. | $0 | $0 | Jun 20, 2006 |
| Jan 13, 1995 | 34119454Y | RESOLVE | Non-Hazardous | OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O #Q196844 FROM CATERING FACILITY ON LOT #1+9 TO LOT 1 ONLY.REMEDY;AMEND C... | $0 | $0 | Apr 10, 1996 |
| Jan 29, 1990 | 34033840P | RESOLVE | Non-Hazardous | EMERGENCY LIGHTING IS INADEQUATE. DOES NOT CONFORM OT APPROVED PLANS. | $0 | $0 | Jul 24, 1990 |
| Jan 29, 1990 | 34033839H | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE PANIC HARDWARE WHERE REQUIRED BY LAW. REQUIRED MEANS OF EGRESS IS OBSTRUCTED. EXIT DOOR SWINGS AGA... | $400 | $0 | Jul 24, 1990 |
| Nov 14, 1989 | 34033943H | RESOLVE | Non-Hazardous | CATERING ESTABLISHMENT AND BANQUET HALLS WITH DANCING WITH AN OCCUPANT LOAD OF 300 OR MORE PERSONS LCCTUAL OCCUPANT L... | $200 | $0 | Apr 10, 1990 |
| Nov 14, 1989 | 34033941Y | RESOLVE | Non-Hazardous | ASYSTEM OF AUTOMATIC SPRINKLERS SYSTEM NOT PROVIDED FOR THE CATERING ESTABLISHMNET WITH AN OCCUPANT LOAD OF 300 OR MO... | $200 | $0 | Apr 10, 1990 |