| Apr 2, 2026 | 39183012P | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS AT COMPACTOR ROOM AND COMMON AREA A... | $25,000 | $25,000 | May 10, 2027 |
| Apr 2, 2026 | 39182944K | RESOLVE | CLASS - 1 | CLASS 1 CEASE USE ITEM: DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. RE... | $1,250 | $1,250 | Jun 9, 2026 |
| Apr 2, 2026 | 39182962Y | ACTIVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED THAT MAIN ELECTRICAL SERVICE WAS NOT GROUNDED TO MAIN WATER SERVICE PI... | $4,800 | $4,800 | Oct 13, 2026 |
| Apr 2, 2026 | 39182963X | ACTIVE | CLASS - 1 | FAILURE TO PROPERLY GROUP/LABEL DISCONNECTS. OBSERVED IN THE MAIN ELECTRICAL RM THAT SERVICE SWITCHES WAS NOT LABELED... | $1,000 | $1,000 | Oct 13, 2026 |
| Apr 2, 2026 | 39183006Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED SPRINKLER HEADS OBSTRUCTED IN COMMON AREA AND DIRECTO... | $6,250 | $6,250 | May 10, 2027 |
| Apr 2, 2026 | 39183005R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED SPRINKLER CAPS PAINTED THROUGHOUT BUILDING. PREVIOUS ... | $10,000 | $10,000 | May 10, 2027 |
| Apr 2, 2026 | 39182943Z | RESOLVE | CLASS - 2 | CLASS 2: BOTH TOP AND BOTTOM FINAL TERMINAL STOPPING DEVICES ARE NOT PROPERLY SECURED/PINNED, PROPERLY SECURE BOTH SW... | $0 | $0 | Jun 9, 2026 |
| Mar 26, 2025 | 39142946H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 C... | $2,500 | $2,500 | Sep 15, 2026 |
| Mar 26, 2025 | 39142945X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $0 | Jan 20, 2026 |
| Mar 11, 2024 | 39108354P | RESOLVE | CLASS - 2 | OBSERVED PAINTED SPRINKLER CAPS ON FLOORS 5-2. AS PER 102.3 OF THE PLUMBING CODE MAINTENANCE. INSTALLATIONS, BOTH EXI... | $655 | $0 | Sep 10, 2024 |
| Feb 26, 2024 | 39106915R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CATEGORY 1 TAG ON THE CO0NTROLLER EXPIRED (09/2021), PROVIDE A... | $0 | $0 | May 7, 2024 |
| Feb 26, 2024 | 39106914P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. CATEGORY 1 TAG ON THE CO0NTROLLER EXPIRED (09/2021), PROVIDE A... | $0 | $0 | May 7, 2024 |
| Oct 18, 2022 | 39072237Y | RESOLVE | CLASS - 1 | I OBSERVED IN DOB RECORDS NO PERMIT FOR THE INSTALLATION OF THE LIGHTING ALONG THE SIDEWALK SHED. THE INSTALLATION IS... | $400 | $0 | Mar 2, 2023 |
| Oct 18, 2022 | 39072238X | RESOLVE | CLASS - 1 | I OBSERVED ALONG THE SIDEWALK SHED THE FAILURE TO PROPERLY SUPPORT THE CONDUIT RACEWAY AND THE TEMPORARY LIGHTING AS ... | $1,600 | $0 | Mar 14, 2023 |
| Jun 15, 2022 | 39064177L | RESOLVE | CLASS - 2 | EXP#3 (REAR PARKING) RE-POINTING THAT WAS DONE A YEAR AGO, CRACKS OPENING UP IN A FEW AREAS. AT EXP#1 (FRONT ENTRANCE... | $1,280 | -$1,280 | Aug 2, 2022 |
| Oct 5, 2021 | 39048745K | RESOLVE | CLASS - 2 | FOUND AO SMITH BTH 250 WATER HEATER NOT REGISTERED, MAINTAIN BOILER; REGISTER WATER HEATER AND SUBMIT A CERTIFICATE O... | $0 | $0 | Nov 23, 2021 |
| Jan 4, 2021 | 39034267H | RESOLVE | CLASS - 2 | AO SMITH MODEL BTH-250 300 SERIAL # 1843112334700 CONDENSING HOT WATER HEATER HAS INCORRECT VENTING MATERIAL., MAINTA... | $625 | $0 | Apr 6, 2021 |
| Sep 19, 2019 | 38271777K | RESOLVE | CLASS - 1 | (CEASE USE-59X10)(1L10,2L10)1L10-EMERGENCY STOP SWITCH WORKS BUT NO BUZZER.2L10-ALARM BELL NOT WORKING NO BUZZER.59X1... | $1,250 | $0 | Jan 28, 2020 |
| Sep 19, 2019 | 38271776Z | RESOLVE | CLASS - 1 | (CEASE USE-5A10,59X10)(67X10)5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH SWITCHES,DISABLE.59X10-BRAKE ELECTRI... | $1,250 | $0 | Jan 28, 2020 |
| Dec 11, 2018 | 38266884J | RESOLVE | CLASS - 1 | CU5A10,59BB7. 5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH. THIS IS A SAFETY DEVICE TO ENSURE PASSENGERS SAFET... | $1,250 | $0 | Feb 19, 2019 |
| Dec 11, 2018 | 38266885L | RESOLVE | CLASS - 2 | 59BB7,59B7. 59BB07-BRAKE MAINTENANCE TAG EXPIRED; 59B7-BRAKE MONITOR INSUFFICIENT MISSING CONTACT. | $0 | $0 | Feb 19, 2019 |
| Jul 11, 2018 | 35342333X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 7-11-18 AT ABOVE ADDRESS. NO BALL DRIP FOUND ON THE FI... | $0 | $0 | Feb 5, 2019 |
| Jul 11, 2018 | 35341608L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER 712.3;27-345. NO FIRE STOP DONE IN HOT WATER ... | $0 | $0 | Sep 18, 2018 |
| Jun 12, 2018 | 35340375P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35311369X ISSUED ON 03-02-18 & TO FILE A C OF C PURSUAN... | $0 | $0 | Feb 19, 2019 |
| Mar 2, 2018 | 35311370N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: CELLAR LEVEL MAINTEN... | $0 | $0 | Apr 17, 2018 |
| Mar 2, 2018 | 35311369X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: @ CELLAR LEVEL WATER ENTERING FROM EXTERIOR OF BLDG INTO SP... | $1,000 | $0 | Apr 17, 2018 |
| Mar 2, 2018 | 35312067P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.OBSERVED ON 03/02/2018 AT ABOVE ADDRESS NO BALLDRIP(6D)FOUND ON... | $0 | $0 | Jul 10, 2018 |
| Mar 2, 2018 | 35321708K | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. OBSERVED THE FOLLOWING VIOLATING CONDITION IN THE ELECTRICAL ROOM LOCATE... | $3,000 | $0 | Apr 17, 2018 |
| Feb 18, 2018 | 35283815L | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35272359N ISSUED ON 07/13/17 & TO FILE A C OF C PURSUAN... | $6,000 | $0 | Apr 10, 2018 |
| Feb 6, 2018 | 38261255Y | RESOLVE | CLASS - 2 | 67X10,29Q03,59B01-67X10)REPAIR EMERGENCY PHONE. 29Q03)INSTALL DOOR OPERATOR GUARD. 59B01)PROPERTY ADJUST BRAKE MONITO... | $0 | $0 | Mar 27, 2018 |
| Jan 10, 2018 | 35282194N | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35272359N ISSUED ON 07/13/17 & TO FI... | $6,000 | $0 | Feb 27, 2018 |
| Nov 18, 2017 | 35279571M | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35272359N ISSUED 07/13/17 AND TO FILE... | $6,000 | $0 | Jan 2, 2018 |
| Oct 3, 2017 | 35279667R | RESOLVE | CLASS - 1 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35272359N ISSUED ON 07/13/17 & TO FILE A C... | $2,400 | $0 | Nov 21, 2017 |
| Sep 13, 2017 | 38257314N | RESOLVE | CLASS - 2 | 01X10 STOP WITCH WORKIN NO SOUND. 02X10- NO SOUND | $0 | $0 | Oct 31, 2017 |
| Aug 19, 2017 | 35277318J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/ VIOLATION #35272363X ISSUED ON 07/13/17 AND TO ... | $830 | $0 | Dec 26, 2017 |
| Jul 13, 2017 | 35272358L | RESOLVE | CLASS - 2 | FGC,404.12. MISC VIOLATIONS-OBSERVED IN GAS METER ROOM GAS HOUSE PIPING NOT PROPERLY CAPPED PFF AT METER LOCATION-AT ... | $800 | $0 | Aug 29, 2017 |
| Jul 13, 2017 | 35272362Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: FAILURE TO COMPLY W/LAW OF DRAINAGE SYSTEM PER PC 702.1;27-902. CO... | $500 | $0 | Nov 22, 2017 |
| Jul 13, 2017 | 35272361M | RESOLVE | CLASS - 1 | FGC 406.6.2.1.MISC-VIOLATION - GAS SUPPLIED WITHOUT DOB CERTIFICATE ORINSPECTION-RES.GAS STOVE IN USE.REM:HAVE GAS CE... | $1,600 | $0 | Aug 29, 2017 |
| Jul 13, 2017 | 35272359N | RESOLVE | CLASS - 1 | WORK,NO PERMIT IN CELLAR.MAINTENANCE ROOM INSTALL RESID-GAS STOVE WITHASSOC.GAS PIPING-NO RECORD OF DOB PERMIT FOR TH... | $1,600 | $0 | Aug 29, 2017 |
| Jul 13, 2017 | 35272360K | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEMS TESTED-OBSERVED IN CELLAR,INSTALLED RESIDE.GAS STOVE & GAS PIPING-IN ... | $0 | $0 | Aug 29, 2017 |
| Jul 13, 2017 | 35272363X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:FAILURE TO PAINTDEDICATED SPRINKLER MAIN LINE @ FRONT ENTRANCE-... | $250 | $0 | Aug 29, 2017 |
| Jan 23, 2017 | 35230307X | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONATINED IN SUMMONS/VIO# 35216888M ISSUED ON 10/25/16 & TO FILE A CERT OF CORRE... | $0 | $0 | Jun 6, 2017 |
| Jan 17, 2017 | 35225865Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. DOB RECORDS SHOW THE LAST BOILER INSPECTION WAS DONE ON 9/27/13 ... | $500 | $0 | Mar 28, 2017 |
| Jan 17, 2017 | 35225864M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 1/17/17SPRINKLER MAIN NOT PAINTED IN THE HALLWAY ON TH... | $0 | $0 | Mar 7, 2017 |
| Jan 17, 2017 | 35225866X | RESOLVE | CLASS - 1 | FGC 411.1. RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVEDON 1/17/17 IN CELLAR RESIDENTIAL GAS FLEX CONNE... | $1,600 | $0 | Mar 28, 2017 |
| Oct 25, 2016 | 35216888M | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. AT THE TIME OF MY INSPECTION,1PM ON 10/25/16 AT THEABOVE PLACE OF ACCURRENCE ADDRESS I OBSERVED IN... | $0 | $0 | Jan 10, 2017 |
| Oct 25, 2016 | 35216306N | RESOLVE | CLASS - 1 | SEC. 411.1 MISC VIOLATION: RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. AT THE TIME OF MY INSPECTION 1PM ON 10/... | $1,600 | $0 | Dec 13, 2016 |
| Oct 25, 2016 | 35216889Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT THE TIME OF MY INSPECTION,1PM ON 10/25/16 AT THE ABOVE PLACE OF... | $0 | $0 | Jan 10, 2017 |
| Oct 25, 2016 | 35216887K | RESOLVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC102... | $500 | $0 | Jan 10, 2017 |
| Oct 23, 2016 | 35213939J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. NO FIRE PROOFING/STOPPING PER BC 712.3;27-345. NOTED: MULTIPLE P... | $250 | $0 | Dec 13, 2016 |