ECB violations
183-02-183-04 Jamaica Avenue, Queens • Block 10352 • Lot 0050
31 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 15, 2021 | 39042832L | RESOLVE | CLASS - 2 | FOUND AO SMITH DIRECT VENT WATER HEATER MODEL BTH-150 300 OPERATING WITH DEFECTS. NEUTRALIZING KIT MISSING FOR EXHAUS... | $625 | $625 | Aug 3, 2021 |
| Mar 24, 2021 | 39038246R | RESOLVE | CLASS - 1 | ELEVATOR IS OUT OF SERVICE. RESTORE TO SERVICE. CATI TAG EXPIRED. PROVIDE. CAT5 TAG EXPIRED. PROVIDE. | $1,250 | $1,250 | May 11, 2021 |
| Jan 4, 2021 | 39034228P | RESOLVE | CLASS - 2 | TWO AO SMITH BTH250 HOT WATER HEATERS CONNECTED TO TWO TJV120M STORAGE TANKS. INCORRECT VENTING MATERIAL, VENTING CAN... | $1,562 | $1,562 | Apr 6, 2021 |
| Aug 8, 2018 | 32097368K | RESOLVE | CLASS - 2 | 50A,50B,50C,50D,50E,50F-TWO AOSMITH BTH 250, HOT WATER HEATERS CONNECTED TO TWO AOSMITH TJY120M STORAGE TANKS HAVE FO... | $655 | $0 | Mar 19, 2019 |
| Apr 27, 2018 | 35337183N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/ VIOLATION #35322250M ISSUED ON 03/09/18 AND TO ... | $625 | $0 | Jul 31, 2018 |
| Mar 29, 2018 | 35326376X | RESOLVE | CLASS - 2 | FAILURE TO MAINTIAN BLDG IN CODE COMPLIANT MANNER. OBSERVED AT TOP OF STAIRWELL INSPECTOR'S TEST STATION INCORRECTLY ... | $310 | $0 | Jun 19, 2018 |
| Mar 9, 2018 | 35322250M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: AT THE INTERSECTION CORNER OF JAMAICA AVENUE FDNY CONNE... | $1,000 | $0 | Apr 24, 2018 |
| Jan 21, 2018 | 35311554H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT THE INTERSECTION CORNER OF JAMAICA AVENUE FDNY CONNE... | $0 | $0 | May 1, 2018 |
| Jan 18, 2018 | 35297844H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED AT THE TOP OF THE STAIRWELLS THE INSPECTORS TENT STATI... | $0 | $0 | May 1, 2018 |
| Dec 8, 2017 | 35297090K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: AT THE INTERSECTION CORNER OF JAMAICA AVE FDNY CONNECTION N... | $0 | $0 | Apr 24, 2018 |
| Nov 1, 2017 | 35294571H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. NOTED: AT THE INTER SECTION CORNER OF JAMAICA AVE FDNY CONNECTION ... | $500 | $0 | May 1, 2018 |
| Sep 19, 2017 | 38257666R | RESOLVE | CLASS - 1 | 5M7:14M7;11J11;MISSING PART OF DOOR RESTRICTOR ON ONE OPENING,MUST PROVIDE.CAR MIRRORS MISSING-MUST PROVIDE;CAR TRAVE... | $1,000 | $0 | Mar 6, 2018 |
| Sep 2, 2017 | 35290636L | RESOLVE | CLASS - 1 | WORK NO PERMIT OBSERVED @ STAIRS ALL FLOORS, REPLACED SPRINKLER HEADS & FDNY BALL CHECK VALVE W/OUT AN ACTIVE APPROVE... | $1,630 | $0 | Feb 6, 2018 |
| Aug 23, 2017 | 35261707R | RESOLVE | CLASS - 2 | WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCS AND/OR APPROVED AMENDMENTS.PREMISES UNDER NB 420911160.EXP 3/16/1... | $500 | $0 | Jan 18, 2018 |
| Aug 23, 2017 | 35261708Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER.PREMISES UNDER NB420911160.NOTE AT TIME OF INSPECION FOUND 1)MULT... | $500 | $0 | Jan 18, 2018 |
| Aug 4, 2017 | 35287230Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:OBSERVED AT THE INTERSECTION CORNER OF JAMAICA AVE-FDNY CONNECT... | $1,000 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272428H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN LAUNDRY ROOM SPRINKLER HEAD(FIRE)INSTALLED LESS THAN 4... | $1,250 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272086R | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED IN SIDE COURTYARD: THE INSTALLATION OF A BACKYARD POWER GENERATOR. RECORDS IND... | $1,600 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272429J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED AT TOP OF STAIRS IN STAIRWELL NO PRESSURE GAUGE INSTALLED... | $1,250 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272430R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN SPRINKLER CONTROL ROOM IN SUB-CELLAR. NO SPACE SPRINKL... | $1,250 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272431Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN SUB-CELLAR GAS METER ROOM NO VENTILATION AS REQUIRED B... | $500 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272432K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: LACK OF A SYSTEM OFAUTOMATIC SPRINKLERS WHERE REQUIRED PER BC 903.... | $1,000 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272433M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN SUBCELLAR FIRE SPRINKLER HEADCS INSTALLED TO HIGH IN C... | $1,000 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272434Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. FAILURE TO COMPLY W/THE LAW FOR DRAINAGE SYSTEM PER PC 702.1;27-91... | $500 | $0 | Jan 18, 2018 |
| Jul 13, 2017 | 35272085P | RESOLVE | CLASS - 1 | SEC. 110.2(B) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL. OBSERVED IN ELECTRICAL VAULT ROOM: TH... | $1,600 | $0 | Jan 18, 2018 |
| Jan 30, 2017 | 35226453M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 1/30/17SPRINKLER HEAD TO CLOSE TO THE SOFFIT IN THE LA... | $530 | $0 | Mar 21, 2017 |
| Jan 30, 2017 | 35226452K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. OBSERVED ON 3/21/17IN FIRE PUMP ROOM THERE IS NO EXTRA SPRINKLER H... | $530 | $0 | Mar 21, 2017 |
| Sep 2, 2015 | 35145283Y | RESOLVE | CLASS - 2 | AIR POLLUTION NOTE AT TIME OF INSPECTION ACTIVE CONSTRUCTION SITE OF A4 STORY BUILDING.EXERIOR WORK IN PROGRESS.SANDI... | $4,000 | $0 | Oct 20, 2015 |
| Jul 14, 2015 | 35130670M | RESOLVE | CLASS - 1 | 3307.3,3307.6.2,3301.2 OVERHEAD PROTECTION FOR WALKWAY AND SIDEWALK.NOED:AT TIME OF INSPECTION OF 4 STORY NEW BUILDIN... | $1,630 | $0 | Sep 1, 2015 |
| Jul 14, 2015 | 35130669P | RESOLVE | CLASS - 2 | 3308.1.1 VERTICAL SAFETY NETTING NOT PROVIDED.AT TIME OF INSPECTION OF4 STORY NEW BUILDING UNDER CONSTRUCTION TO HEIG... | $0 | $0 | Sep 1, 2015 |
| Feb 28, 2015 | 35120875R | RESOLVE | CLASS - 1 | SEC. 3304.7 SAFE MEANS OF INGRESS & EGRESS. AT TIME OF INSPECTION OBSERVED NB UNDER CONSTRUCTION FOUNDATION WORK IN P... | $1,630 | $0 | Apr 14, 2015 |