ECB violations
155 Avenue, Queens • Block 11445 • Lot 0001
50 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 16, 2026 | 35732215Z | ACTIVE | CLASS - 2 | REISSUED ECB #35717209R. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARG... | $3,125 | $0 | May 13, 2026 |
| May 1, 2023 | 35672984L | RESOLVE | CLASS - 2 | REISSUE#35654933M(4/19/2022)FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:ILLUMINATION FOR EXITS,EXIT DISCHAR... | $1,562 | $0 | Aug 1, 2023 |
| May 1, 2023 | 35672985N | RESOLVE | CLASS - 2 | REISSUE#35654931Z(4/19/22)FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER AT CAFETERIA KITCHEN NO FIRE SUPPRESS... | $1,562 | $0 | Aug 1, 2023 |
| Apr 19, 2022 | 35654931Z | RESOLVE | CLASS - 2 | REISSUE#35555755P.FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED THERE IS NO FIRE SUPRESSION SYSTEM IN T... | $1,562 | $0 | Jul 26, 2022 |
| Apr 19, 2022 | 35654933M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $625 | $0 | Jul 26, 2022 |
| Apr 19, 2022 | 35654932K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED OBSERVED ON THE THIRD FLOOR ROOM 320 THERE IS A LEAK COMI... | $625 | $0 | Jul 26, 2022 |
| Mar 18, 2021 | 35555755P | RESOLVE | CLASS - 2 | REISSUE35402508K FAILURE TO MAINTAIN BLDG IN CODECOMPLIANT MANNER:NOTED:NO FIRE SUPRESSION SYSTEM@CAFETERIA'S 10BURNE... | $1,562 | $0 | Jun 15, 2021 |
| Apr 22, 2020 | 35491067L | RESOLVE | CLASS - 2 | REISSUE#35402508K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN KITCHEN NEXT TO CAFETERIA,A COMMERCI... | $1,562 | $0 | Aug 18, 2020 |
| Apr 29, 2019 | 39002433H | RESOLVE | CLASS - 2 | GLASS MISSING IN REAR OF BOILER TO SIGHT FIRE BOLTS MISSING ON BOILER DOORS GAS WTR HTR HAS DRAFT INDUCER AT TNK CHIM... | $0 | $0 | May 9, 2019 |
| Apr 29, 2019 | 39002434J | RESOLVE | CLASS - 2 | WATER-AROUND-BOILER-MISSING BOLTS ON BOILER DOORS-GLASS MISSING IN REAR BOILER DOOR TO SIGHT FIRE | $0 | $0 | May 9, 2019 |
| Apr 8, 2019 | 35402509M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NO FIRE STOPPING PERBC 712.3;27-345.NOTED:AT ELECTRICAL ROOM HOLES ... | $0 | $0 | Jul 9, 2019 |
| Apr 8, 2019 | 35402507Z | RESOLVE | CLASS - 2 | REISSUE #35316707M.FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER .NOTED:AT GROUND WATER PENETRATION CAUSING T... | $0 | $0 | Jul 9, 2019 |
| Apr 8, 2019 | 35402511L | RESOLVE | CLASS - 2 | BC28-301.1.UNLAWFUL PLACEMENT OF FURNISHINGS DECORATIONS OR OTHER OBJECT AT EXITS THAT OBSTRUCT ACCESS TO EGRESS FROM... | $0 | $0 | Jul 9, 2019 |
| Apr 8, 2019 | 35402508K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:AT CAFETERIA 10 BURNER GAS STORE HAVE NO FIRE SUPRESSION SYST... | $0 | $0 | Jul 9, 2019 |
| Feb 14, 2018 | 35316707M | RESOLVE | CLASS - 2 | RE-ISSUE #35235447K FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:@CELLAR LEVEL, THE ENTIRE CELLAR IS IN A ... | $0 | $0 | Apr 17, 2018 |
| Apr 13, 2017 | 35235447K | RESOLVE | CLASS - 2 | REISSUE #35178084M. FAILURE TO MAINTAIN BLDG. NOTED: ENTIRE CELLAR LEVEL IS IN A SERIOUS STATE OF GROUND WATER PENETR... | $0 | $0 | May 16, 2017 |
| Jul 26, 2016 | 35178084M | RESOLVE | CLASS - 2 | REISSUE #34241167K FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.GROUND WATER PENETRATING THROUGH CONCRETE SL... | $0 | $0 | Nov 15, 2016 |
| Apr 28, 2015 | 35127980K | RESOLVE | CLASS - 3 | REISSUE #35093983N.FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:GROUND WATER PENETRATION THROUGHOUT AREAS ... | $0 | $0 | Jun 16, 2015 |
| May 1, 2014 | 35093984P | RESOLVE | CLASS - 2 | EXIT PASSAGEWAY OBSTRUCTED AT BULKHEAD STAIR A & B WITH BUFFER MACHINES,BUCKETS, ALSO 2ND FLOOR FRONT OF ROOM 208,211... | $0 | $0 | Jun 17, 2014 |
| May 1, 2014 | 35093983N | RESOLVE | CLASS - 2 | RE-ISSUE # 35027734R. GROUND WATER PENETRATING THROUGHOUT CONCRETE SLAB IN BASEMENT. REMEDY: SEAL PENETRATION. | $0 | $0 | Jun 17, 2014 |
| Jul 9, 2013 | 35027733P | RESOLVE | CLASS - 2 | REISSUE 34981684M DAMAGED PLASTER WALLS IN CORRIDORS ADJACENT TO ROOMS209,213,215,309,313,& 315. REMEDY: REPAIR ALL D... | $0 | $0 | Sep 17, 2013 |
| Jul 9, 2013 | 35027734R | RESOLVE | CLASS - 2 | REISSUE 34981683K GROUND WATER PENETRATING THROUGH CONCRETE SLAB AT MANY LOCATIONS THROUGHOUT CELLAR. REMEDY: MAKE NE... | $0 | $0 | Sep 17, 2013 |
| May 22, 2012 | 34981685Y | RESOLVE | CLASS - 2 | WATER PENETRATING THROUGH ROOF & CAUSING DAMAGE TO WALL IN CORRIDOR ADJACENT TO ROOMS 309 & 315.REM:REPAIR ROOF. | $0 | $0 | Aug 14, 2012 |
| May 22, 2012 | 34981682Z | RESOLVE | CLASS - 2 | EXIT LIGHTING IN T1,T2,T3,& T4.NOT WORKING.REM:REPAIR OR REPLACE EXIT LIGHTS. | $0 | $0 | Aug 14, 2012 |
| May 22, 2012 | 34981684M | RESOLVE | CLASS - 2 | WALLS IN CORRIDOR OUTSIDE OF ROOMS 109,209,309 & 315 HAVE DAMAGED PLASTER & ARE DAMP FROM WATER PENETRATING FROM ROOF... | $0 | $0 | Aug 14, 2012 |
| May 22, 2012 | 34981687H | RESOLVE | CLASS - 2 | 27-369)@ 2 FLR CORRIDOR STORAGE OF TV,CARTS,ART WORK,DESKS,& OTHER SCHOOL SUPPLIES & EQUIPMENT NEAR STAIR DOORS @ BOT... | $0 | $0 | Aug 14, 2012 |
| May 22, 2012 | 34981686X | RESOLVE | CLASS - 2 | PLEXI VISION PANELS INSTALLED ON DOORS @ VARIOUS LOCATIONS THROUGHOUT BLDG.REM:PROVIDE REQUIRED GLASS PANELS. | $0 | $0 | Aug 14, 2012 |
| May 22, 2012 | 34981683K | RESOLVE | CLASS - 2 | REISSUE#34918155P GROUND WATER PENETRATING THROUGH CONCRETE SLAB @ MANY LOCATIONS THROUGHOUT CELLAR LEVEL.REM:MAKE AL... | $0 | $0 | Aug 14, 2012 |
| Jun 30, 2011 | 34918155P | RESOLVE | CLASS - 2 | REISSUE 34241167K,34282729Y,34420989N,34770578Z,34839540X. NOTED: WATER PENETRATING INTO BASEMENT FLOOR ENTERING MULT... | $0 | $0 | Sep 13, 2011 |
| Apr 15, 2010 | 34839540X | RESOLVE | CLASS - 2 | REISSUE # 34241167K, 34282729Y, 34420989N, 34770578Z, NOTED AT TIME OFINSPECTION MULTIPLE LOCATIONS GROUND WATER PENE... | $0 | $0 | Jul 20, 2010 |
| Apr 15, 2010 | 34839541H | RESOLVE | CLASS - 3 | TRANSPORTABLE T-2 FLOORING SAGGING IN FRONT OF DOOR - T-2 REMEDY: REPAIR T-2 FLOOR | $0 | $0 | Jul 20, 2010 |
| Mar 23, 2009 | 34770577R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN NOTE:DEFECTIVE & ROTTED THROUGH DOOR FRAMES & DOORS NOT OPENING & CLOSING PROPERLY LOCATIONS 1.OI... | $0 | $0 | Jul 7, 2009 |
| Mar 23, 2009 | 34770578Z | RESOLVE | CLASS - 3 | REISSUE 334420989N FAILURE TO MAINTAIN NOTE CHRONIC GROUND WATER PENETRATION AT CELLAR SLAB FLS THRU-OUT AND BOILER R... | $0 | $0 | Jul 7, 2009 |
| Mar 23, 2009 | 34770575N | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN NOTE:WOOD SEATING AREA OF PLAYGROUND BENCHES IS ROTTED THROUGH & SPLITTING & CRUMBLING LOCATION B... | $0 | $0 | Jul 7, 2009 |
| Mar 23, 2009 | 34770576P | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN NOTE:NO FRESH AIR INTAKE IN GAS METER RM REMEDY:PROVIDE FRESH AIR INTAKE | $0 | $0 | Jul 7, 2009 |
| Mar 23, 2009 | 34770249H | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN NOTE: VERTICAL CRACKS IN BRICKWORK. LOCATION: EXT WALL OF AUDITORIUM ON 153 AVE (WEST CORNER) @83... | $0 | $0 | Jul 7, 2009 |
| Apr 12, 2007 | 34569793R | RESOLVE | Non-Hazardous | REISSUE #34482007Z.FAILURE TO MAINTAIN-EXTERIOR.WATER PENATRATION THRUCONCRETE FL INTO BASEMENT THRU-OUT.REMEDY:MAKE ... | $0 | $0 | Jun 26, 2007 |
| May 12, 2005 | 34482007Z | RESOLVE | Non-Hazardous | REISSUE V#34420989N.WATER PENETRATION THROUGH CONCRETE FLOOR INTO BASEMENT THROUGHOUT.REMEDY:STOP WATER PENETRATION.M... | $0 | $0 | Aug 2, 2005 |
| Mar 22, 2004 | 34419926H | RESOLVE | Hazardous | FAILURE TO MAINTAIN NOTED:AT MAIN ENTRANCE LOBBY STAIRS.1 STEP BROKE N OFF APPROX 2'EXPOSING RE-BAR CAUSING HAZARDOUS... | $0 | $0 | Jun 22, 2004 |
| Dec 29, 2003 | 34420989N | ACTIVE | Hazardous | FAILURE TO MAINTAIN BUILDING, DEFECTOR IS: GROUND WATER IS SEEPING INTO ENTIRE BOILER ROOM. REMEDY: OBTAIN ALL PERMIT... | $0 | $0 | Mar 16, 2004 |
| Mar 14, 2003 | 34383281H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. (REISSUE) DEFECT IS GROUND WATER PENETRATION AT VARIOUS LOCATIONS THROUGHOUT BASEMENT. ... | $0 | $0 | Jun 24, 2003 |
| Jan 29, 2002 | 34308659K | RESOLVE | Hazardous | REISSUE FAILURE TO MAINTAIN BUILDING DEFECT IS: GROUND WATER PENETRATION AT VARIONS LOCATIONS THROUGHOUT BASEMENT. RE... | $0 | $0 | Apr 9, 2002 |
| Sep 20, 2001 | 34280286P | RESOLVE | Non-Hazardous | FAILURE TO PROVIDE EMERGENCY POWER TO EXIT LIGHTS IN THREE CLASS ROOM OF TRANSPORT UNITS.REMEDY:PROVIDE EMERGENCY POW... | $0 | $0 | Nov 27, 2001 |
| Mar 22, 2001 | 34282729Y | ACTIVE | Non-Hazardous | FAILURE TO MAINTAIN.UPON INSPECTION OF THE ABOVE ADDRESS.THERE IS WATER PENETRATION THROUGH OUT THE MASEMENT IN THE F... | $0 | $0 | Jul 3, 2001 |
| Mar 22, 2001 | 34282730L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN.UPON INSPECTION OF THE ABOVE ADDRESS.WATER PENETRATION IN CEILING AT THE FOLLOWING AREAS(1)ROOM 3... | $0 | $0 | Jul 3, 2001 |
| Mar 22, 2001 | 34282731N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN UPON INSPECTION OF THE ABOVE ADDRESS(1)EXIT 8 & 9 & 10 & 11 LEADING TO ROOF BULKHEAD HAS STRESS C... | $0 | $0 | Jul 3, 2001 |
| May 2, 2000 | 34241167K | ACTIVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG. DEFECT IS GROUND WATER PENETRATING THROUGHOUT BASEMENT FL. REMEDY:DO ALL REPAIRS. | $0 | $0 | Jul 25, 2000 |
| Jun 25, 1999 | 34212703M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING EXTERIOR. DEFECTS ARE: CHAIN LINK FENCE @ SW CORNER OF BLDG NEXT TO PLAYGROUND IS DEFECT... | $0 | $0 | Sep 21, 1999 |
| Jun 25, 1999 | 34212705X | RESOLVE | Non-Hazardous | WORK WITHOUT A PERMIT: MAINTAINING THE ERECTION OF A SIDEWALK SHED AT THE WESTERN AND EASTERN ELEVATIONS OF BUILDING ... | $0 | $0 | Sep 21, 1999 |
| Jun 25, 1999 | 34212704Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING INTERIOR. DEFECT IS: GROUND WATER IS SEEPING INTO ENTIRE BASEMENT. MAKE SHIFT DRAIN ARE ... | $0 | $0 | Sep 21, 1999 |