ECB violations
113-18 Rockaway Boulevard, Queens • Block 11705 • Lot 0036
24 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jul 7, 2026 | 39194984N | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE REAR/ PARKING LOT A/C SPILT UNIT COMPRESSOR INSTALLED WITH ALUMINUM... | $2,500 | $0 | Sep 15, 2026 |
| Jul 7, 2026 | 39195018Y | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED WOOD PANELS AS WALLS, WHICH ARE NOT FIRE RATED INSIDE... | $2,500 | $2,500 | Sep 15, 2026 |
| Jul 7, 2026 | 39195017M | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. EXIT DOOR HAS ILLEGAL HARDWARE, PREVENT PERSONAL FROM OPENING ... | $2,500 | $2,500 | Sep 15, 2026 |
| Jul 7, 2026 | 39195016K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED CONVEYOR BELT OBSTRUCTING STAIRCASE LEADING FROM BASE... | $2,500 | $2,500 | Sep 15, 2026 |
| Jul 7, 2026 | 39195004N | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ATOI OBSERVED THROUGH OUT BUILDING OBSTRUCTED SPRINKLER HEADS ... | $2,500 | $2,500 | Sep 15, 2026 |
| Jul 7, 2026 | 39195019X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED STORAGE IN SPRINKLER ROOM. COMBUSTIBLE ITEMS (TV, COM... | $1,250 | $1,250 | Sep 15, 2026 |
| Jul 7, 2026 | 39194985P | ACTIVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR. OBSERVED IN THE MAIN ELECTRICAL RM NO ELECTRODE GROUND ROD NOT INST... | $4,800 | $4,800 | Sep 15, 2026 |
| Mar 18, 2024 | 39109055J | RESOLVE | CLASS - 2 | EMERGENCY EXIT DOOR DOES NOT SELF-CLOSE LOCATED AT GROUND FLOOR, EXPOSURE #2., REPAIR/REPLACE DOOR | $0 | $0 | May 28, 2024 |
| Mar 18, 2024 | 39109056L | RESOLVE | CLASS - 2 | HOLE PENETRATION THROUGH CMU BLOCK WALL WITH PIPES AND ELECTRICAL WIRES RUNNING THROUGH THEM, LOCATED AT BOILER MECHA... | $0 | $0 | May 28, 2024 |
| Nov 15, 2022 | 39073918Y | RESOLVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR, STAIR CASE B & CELLAR LEVEL THREE EXIT DOORS DO NOT CLOSE PROPERLY, ALSO, EMERGENCY EXIT CO... | $0 | $0 | Jan 3, 2023 |
| Nov 15, 2022 | 39073917M | RESOLVE | CLASS - 2 | OBSERVED: EXISTING EMERGENCY LIGHT AT 2ND FL NEAR 219 RM, FIRST FL NEAR 111 & 103 RM DO NOT WORK PROPERLY WHEN TESTED... | $0 | $0 | Jan 3, 2023 |
| Jul 8, 2022 | 39065481K | RESOLVE | CLASS - 1 | I OBSERVED IN THE 1ST FLOOR STORAGE ROOM, KITCHEN/ ENTRANCE EMERGENCY LIGHT, BASEMENT LAUNDRY ROOM DRYERS THE IMPROPE... | $800 | $0 | Oct 4, 2022 |
| Jul 8, 2022 | 39065484X | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT LAUNDRY ROOM THE IMPROPER FUSING OF THE GROUNDED CONDUCTOR (NEUTRAL)IN AN ELECTRICAL SYSTE... | $2,400 | $0 | Oct 4, 2022 |
| Jul 8, 2022 | 39065482M | RESOLVE | CLASS - 2 | I OBSERVED IN THE COMMON AREAS AND HALLWAYS RECEPTACLES NOT OF THE TAMPER-RESISTANT TYPE/OR MADE TAMPER PROOFED AS RE... | $0 | $0 | Aug 23, 2022 |
| Jul 8, 2022 | 39065483Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT LAUNDRY ROOM THE IMPROPER TERMINATION OF ELECTRICAL CONDUCTORS ON LOAD SIDE OF THE EQUIPME... | $1,200 | $0 | Oct 4, 2022 |
| Feb 13, 2020 | 39017508P | RESOLVE | CLASS - 2 | I OBSERVED EXPOSED ENERGIZED CONDUCTORS ON THE ROOF FEEDING PERIMETER EXTERIOR LIGHTS, AND A LACK OF MECHANICAL CONTI... | $0 | $0 | Mar 31, 2020 |
| Jul 30, 2019 | 39006678Y | RESOLVE | CLASS - 2 | CELLAR LEVEL FIRE STOP NOT DONE IN THE BOILER ROOM AND LAUNDRY, FIRE BLOCK FOAM USED DOES NOT HAVE A 2HR RATING. ALL ... | $0 | $0 | Sep 17, 2019 |
| Feb 7, 2019 | 35386384K | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,DEVICES,MATERIALS,APPARATUS,APPLIANCES,OR WIRING IN USE. OBSERVED I... | $0 | $0 | May 7, 2019 |
| Jul 16, 2018 | 35342330K | RESOLVE | CLASS - 1 | FGC411.1.RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT.OBSERVED ON07/16/2018 AT ABOVE ADDRESS RESIDENTIAL GAS FLE... | $2,500 | $0 | Jan 22, 2019 |
| Jul 16, 2018 | 35342331M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 07/16/2018 ABOVE ADDRESS NO VENTILATION IN GAS METE... | $0 | $0 | Sep 4, 2018 |
| Jul 16, 2018 | 35346379J | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/OUT A PERMIT OBSERVED INSTALLATION OF CONDUIT,JUNCTION BOXES,LIGHTS,ALONG THE PERIMETER OF BLDG & R... | $0 | $0 | Sep 25, 2018 |
| Jul 16, 2018 | 35346377X | RESOLVE | CLASS - 2 | PROHIBITED USE OF (EMT) ELECTRICAL METALLIC TUBING OBSERVED ALONG PARAPET WALL THE INSTALLATION OF EMT TO PROVIDE POW... | $0 | $0 | Sep 25, 2018 |
| Jul 16, 2018 | 35341611M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3;27-345. GAS METER ROOM IN CELLAR FIR... | $0 | $0 | Sep 18, 2018 |
| Jul 16, 2018 | 35346378H | RESOLVE | CLASS - 2 | FAILURE TO SECURE/SUPPORT RACEWAYS/CABLE ASSEMBLIES/ BOXES CABINETS/FITTINGS.OBSERVED ALONG ROOFTOP PARAPET WALL,EMT ... | $0 | $0 | Sep 25, 2018 |