ECB violations
Epic High School South, Queens • Block 11714 • Lot 0100
59 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 21, 2026 | 35732377L | ACTIVE | CLASS - 2 | REISSUED ECB#35717208P FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED AT 2ND FLOOR GYM RUNNING AND STEP ... | $3,125 | $0 | May 14, 2026 |
| Apr 21, 2026 | 35732383H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED CRACKED GLASS PANEL ON EXIT DOOR#3.REM:REPAIR AND/OR REPL... | $1,250 | $0 | May 14, 2026 |
| Apr 21, 2026 | 35732382X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8;27-371.N... | $1,250 | $0 | May 14, 2026 |
| Apr 21, 2026 | 35732381Y | ACTIVE | CLASS - 2 | REISSUED ECB#35717204H ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIIFCATE OF OCCUPANCY AS PER 28-118.3.1;2... | $3,125 | $0 | May 14, 2026 |
| Apr 21, 2026 | 35732380M | ACTIVE | CLASS - 2 | REISSUE ECB#35717205J FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.NOTED SMOKE DOORS NOT CLOSING PROPERLY AT... | $3,125 | $0 | May 14, 2026 |
| Apr 21, 2026 | 35732379P | ACTIVE | CLASS - 2 | REISSUED ECB#35717206L EXIT DOOR NOT SELF CLOSING.NOTED EXIT DOOR#3 NOT CLOSING PROPERLY.REM:REPAIR/REPLACE DOOR. | $1,562 | $0 | May 14, 2026 |
| Apr 21, 2026 | 35732378N | ACTIVE | CLASS - 2 | REISSUED ECB#35717207N FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES A... | $3,125 | $0 | May 14, 2026 |
| Apr 11, 2025 | 35717205J | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 4 FLOOR CORRIDOR 442, CORRIDOR 449, 3FL. CORRIDOR 312... | $1,250 | $0 | May 16, 2025 |
| Apr 11, 2025 | 35717206L | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED AT 4 FLOOR SMOKE STAIR D, 2FL.(5) STAIR B AND E, DOORS ARE NOT CLOSING PROPERLY, 1F... | $625 | $0 | May 16, 2025 |
| Apr 11, 2025 | 35717204H | ACTIVE | CLASS - 2 | REISSUE #35678861Z. ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-1... | $3,125 | $0 | May 16, 2025 |
| Apr 11, 2025 | 35717207N | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | May 16, 2025 |
| Apr 11, 2025 | 35717208P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 2 FLOOR ALL 4 GYM WALLS 6 RUNNING AND STEP CRACKS. RE... | $1,250 | $0 | May 16, 2025 |
| Apr 23, 2024 | 35678861Z | ACTIVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS 28-118.3.1-28-118.3.2.TCO 400950501T030... | $1,250 | $0 | Jul 3, 2024 |
| Nov 17, 2021 | 39051296L | RESOLVE | CLASS - 2 | VALVE LEAKING OFF HEADER,CEILING INSULATION FALLING ON BURNER,DRAFT INDUCER NOT WORKING | $625 | $0 | Dec 14, 2021 |
| Nov 17, 2021 | 39051295J | RESOLVE | CLASS - 2 | BOLTS & DOGS MISSING ON FRONT & REAR DOORS OF BOILER | $625 | $0 | Dec 14, 2021 |
| Sep 10, 2021 | 35591195Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN/DISPLAY ONSITE DOCUMENTS BY CHAPTER 33 AT TIME OF INSPECTION OF AN ACTIVE SITE I OBSERVED 2 WORKE... | $0 | $0 | Dec 7, 2021 |
| Apr 24, 2020 | 35491072X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: NOTED: OBSERVED FIRE PROOF SELF CLOSING @2ND FLOOR MISSING EXIT 3,... | $625 | $0 | Aug 18, 2020 |
| Apr 24, 2020 | 35491071Y | RESOLVE | CLASS - 2 | RE-ISSUE #35423364N- FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER: NOTED: OBSERVED @"MOD SCHOOL" DO NOT CLOSE PR... | $1,562 | $0 | Aug 18, 2020 |
| May 22, 2019 | 35423364N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT 1ST FLOOR AT EXIT B, 3 DOORS DO NTO CLOSE PROPERLY D... | $0 | $0 | Aug 27, 2019 |
| May 22, 2019 | 35423365P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT ELECTRICAL ROOM, ILLEGAL STORAE OF SMART BOARDS, FLO... | $0 | $0 | Aug 27, 2019 |
| Oct 5, 2018 | 32097535Z | RESOLVE | CLASS - 2 | B254,61,24B,50A. FOUND FOLLOWING VIOLATING CONDITION FOR BOILER #61180-03 6A,24B. 50A-CONDENSATE THE TANK LEAKING. RM... | $0 | $0 | Jan 8, 2019 |
| Mar 24, 2017 | 35228969M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NO FIRE STOPPING PERBC 712.3; 27-345 NOTE: AT CELLAR ELECTRICAL ROO... | $0 | $0 | May 16, 2017 |
| May 8, 2015 | 35120229M | RESOLVE | CLASS - 2 | REISSUE 35093982L FAILURE TO MAINTAIN ADEQUATE FIRESTOPPING OBSERVED:FIRESTOPPING MISSING AROUND ENTRANCE AREA AT 2 F... | $0 | $0 | Jun 16, 2015 |
| Apr 30, 2014 | 35093982L | RESOLVE | CLASS - 2 | RE-ISSUE # 35023379N. MISSING FIRE STOPPING AT 2ND FLOOR AUDITORIUM FAN ROOM, BASEMENT SPRINKLER ROOM, PAINT ROOM. RE... | $0 | $0 | Jun 17, 2014 |
| Jun 24, 2013 | 35023377J | RESOLVE | CLASS - 2 | REISSUE 34958140Z. PLEXI-VISION PANELS INSTALLED ON DOOR AT VARIOUS LOCATIONS THROUGHOUT THE BLDG. REMEDY: PROVIDE RE... | $0 | $0 | Aug 20, 2013 |
| Jun 24, 2013 | 35023379N | RESOLVE | CLASS - 2 | FIRE STOPPING MISSING. 1- 4TH FLR FAN ROOM - WALLS. 2. BASEMENT PAINT ROOM - WALLS. 3- SPRINKLER ROOM - BASEMENT - WA... | $0 | $0 | Aug 20, 2013 |
| Jun 24, 2013 | 35023376H | RESOLVE | CLASS - 2 | REISSUE- 34958141K. CORRIDOR CEILINGS HAVE LOOSE AND MISSING CEILING TILES @ VARIOUS LOCATIONS ON FLRS 4,3,2,1. REMED... | $0 | $0 | Aug 20, 2013 |
| Jun 24, 2013 | 35023378L | RESOLVE | CLASS - 2 | REISSUE 34958139L. DOORS AT MANY LOCATIONS THROUGHOUT THE BLDG, DOORS ARE RACKED, MISSING CHECKS AND HAVE KICKED DOWN... | $0 | $0 | Aug 20, 2013 |
| May 2, 2012 | 34958139L | RESOLVE | CLASS - 2 | DOORS AT MANY LOCATIONS THROUGHOUT BLDG ARE RACKED, MISSING DOOR CHECKS AND HAVE KICK DOWN DOOR STOPS. REMEDY: REPAIR... | $0 | $0 | Jun 19, 2012 |
| May 2, 2012 | 34958141K | RESOLVE | CLASS - 2 | CORRIDOR CEILING HAVE LOOSE & MISSING CEILING TILES AT VARIOUS LOCATIONS. REMEDY: REPAIR/REPLACE CEILING. | $0 | $0 | Jun 19, 2012 |
| May 2, 2012 | 34958140Z | RESOLVE | CLASS - 2 | SEC. 27-371(B). PLEXI VISION PANELS INSTALLED ON DOOR AT VARIOUS LOCATIONS THROUGHOUT BLDG. REMEDY: PROVIDE REQUIRED ... | $0 | $0 | Jun 19, 2012 |
| Feb 9, 2010 | 34839527L | RESOLVE | CLASS - 1 | -HAZ- EXIT DOORS STUCK SHUT AT EXIT # 1 FL ALSO PANIC HARDWARE MISSINGROOM 146 ( CAFETERIA ) REMEDY: REPAIR FORTHWITH! | $0 | $0 | Jul 20, 2010 |
| Feb 9, 2010 | 34856071R | RESOLVE | CLASS - 2 | DEFECTIVE STAIRCASE DOORS THROUGHOUT BLDG TO MANY TO LIST DOORS NOT CLOSING PROPERLY,MISSING FIRE RATED WINDOWS. REME... | $0 | $0 | Sep 14, 2010 |
| Feb 9, 2010 | 34827945X | RESOLVE | CLASS - 2 | BUCKLING OF CONCRETE FLOOR BY EXIT PASSAGEWAY 1ST FLR EXIT 1 & BULKHEAD EXIT STAIRCASE#4.REM:REPAIR TRIP HAZARD | $0 | $0 | Apr 20, 2010 |
| Feb 9, 2010 | 34827946H | RESOLVE | CLASS - 1 | HAZ TRANSPORTABLES WITH DETERIORATING FLRING SAGGING IN AREAS,ALSO BUCKLING OF ROOF UNITS BEING USED AS SHOP STORAGE.... | $0 | $0 | Apr 20, 2010 |
| Feb 9, 2010 | 34827944Y | RESOLVE | CLASS - 2 | REISUUE 34770709J/EXTERIOR WALL FRONT MAIN ENTRANCE AROUND DOE MEDALLION LOOSE/MISSING MORTAR JOINTS.REM:MAKE SAFE | $0 | $0 | Apr 20, 2010 |
| Feb 9, 2010 | 34856070P | RESOLVE | CLASS - 1 | EXIT DOOR STUCK SHUT AT EXIT #1,ALSO MISSING PANIC HARDWARE ROOM 146 (CAFETERIA) REMEDY: MAKE SAFE. | $0 | $0 | Sep 14, 2010 |
| Feb 9, 2010 | 34839528N | RESOLVE | CLASS - 2 | DEFECTIVE STAIRCASE DOORS THROUGHOUT BLDG DOORS NOT CLOSING PROPERLY.AND MULTIPLE DOORS MISSING FIRE RATED GLASS WIND... | $0 | $0 | Jul 20, 2010 |
| Apr 7, 2009 | 34770709J | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN NOTE:MORTAR MISSING FROM FRONT FACADE BRICK WORK LOCATION FRONT FACADE LEFT OF MAIN ENTRANCE AT 3... | $0 | $0 | Jul 7, 2009 |
| Apr 7, 2009 | 34770708H | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN DISPLACEMENT OF GLAZED AND NON GLAZED WALL BLOCK W/ SEPERATING CRACKS AND MORTAR MISSING LOCATION... | $0 | $0 | Jul 7, 2009 |
| Apr 7, 2009 | 34770707X | RESOLVE | CLASS - 3 | REISSUE #34711938N DEFECTIVE SMOKE DOORS AT STAIRWELLS NOT OPEN/CLOSE PROPERLY LOCATIONS EXIT C 3RD FL 2 DOORS EXIT C... | $0 | $0 | Jul 7, 2009 |
| Apr 7, 2009 | 34770710R | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN NOTE:INCOMPLETE ROOF REPAIRS 10 X 10 SECTION OF FLAT ROOF REPAIRED W/O REPLACING PROTECTIVE GRAVE... | $0 | $0 | Jul 7, 2009 |
| Nov 7, 2008 | 34711938N | RESOLVE | CLASS - 3 | DEFECTIVE DOORS 4 FL STAIRWAY C 4 DOORS, STAIR D 1 DOOR, STAIR 1 4 DOORS, 3 FLOOR STAIR C, ROOM 303, 2 FLOOR STAIR C.... | $0 | $0 | Dec 16, 2008 |
| Apr 3, 2007 | 34569769R | RESOLVE | Hazardous | FAILURE TO MAINTAIN INTERIOR-CELLAR ELECTRIC ROOM USED AS STORAGE PC MONITORS.CELLAR GAS METER ROOM USED AS STORAGE-W... | $0 | $0 | Jun 26, 2007 |
| Apr 3, 2007 | 34569770Y | RESOLVE | Hazardous | FAILURE TO MAINTAIN EXTERIOR ROOF ON MAIN BUILDING LEAKING WATER AT S EVERAL LOCATIONS.WATER PUDDLES ON IN THE 4TH FL... | $0 | $0 | Jun 26, 2007 |
| Apr 3, 2007 | 34569768P | RESOLVE | Hazardous | EXIT DOOR NOT SELF CLOSING.4TH FLOOR EXIT 2 -1 DOOR -CLOSE BROKEN.3RD FLOOR-EXIT 4-1 DOOR-CLOSE BROKEN. REMEDY: REPAI... | $0 | $0 | Jun 26, 2007 |
| May 1, 2006 | 38158745L | RESOLVE | Non-Hazardous | 24L10/10B07/16J01/02L10/38A06/38Q03. 16J01-ADJUST BSMT. DOORS FOR SELFCLOSING. 02L10-EMERGENCY PHONE. 38A06-EXPOSED 1... | $0 | $0 | Jun 20, 2006 |
| Dec 8, 2003 | 34422922H | RESOLVE | Hazardous | FAILURE TO MAINAIN BUILIDNG HAZARDOUS DEFECT THROUGH OUT SCHOOL HALLWAYS & CLASSROOMS CEILING TILE 12X12 FIBER TILE A... | $0 | $0 | Feb 3, 2004 |
| Dec 8, 2003 | 34422923J | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILIDING HAZARDOUS DEFECT:THROUGH OUT SCHOOL HOLES IN CEILING SOME AREAS HAVE ELECTRICAL WIRES B... | $0 | $0 | Feb 3, 2004 |
| Dec 8, 2003 | 34422924L | RESOLVE | Non-Hazardous | USE OF ILLEGAL HARDWARE IN PALCE OF ASSEMBLY THROUGHUT SCHOOL DOORS H AVE SLIDE BOLTS ON DOORS.REMEDY:REMOVE ILLEGAL(... | $0 | $0 | Feb 3, 2004 |