ECB violations
134-01 Baisley Boulevard South, Queens • Block 12130 • Lot 0014
36 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 1, 2026 | 39182814M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED MISSING DOOR FOR ELEVATOR ROOM. REPLACED WITH PLYWOOD... | $0 | $0 | Jun 9, 2026 |
| Apr 1, 2026 | 39182815Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SPRINKLER CAPS PAINTED THROUGHOUT THE BUILDING. POTENTIAL FIRE... | $625 | $625 | Jun 9, 2026 |
| Apr 1, 2026 | 39182813K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS THROUGHOUT THE BUILDING(UNPERMITTED... | $2,500 | $2,500 | Jun 9, 2026 |
| Oct 30, 2024 | 39128940X | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS. OBSERVED BUILDING MATERIALS AND BOXES AT BASE OF ... | $1,250 | $1,250 | Mar 9, 2026 |
| Oct 30, 2024 | 39128938R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $2,500 | $2,500 | Mar 9, 2026 |
| Oct 30, 2024 | 39128936N | RESOLVE | CLASS - 2 | OBSERVED DEFECTIVE PUMP( WATER LEAK AND SCALING ON PUMP) LOCATED GAS METER ROOM, ALSO ACTIVE WATER LEAK IN THE BOILER... | $312 | $0 | Jun 16, 2025 |
| Oct 30, 2024 | 39128951L | RESOLVE | CLASS - 2 | I OBSERVED ON THE ROOF AREAS THE UNPERMITTED SUE OF BX CABLING OUTDOORS, LFMC IN LENGTHS GREATER THAN 6 FT, AND FLEXI... | $400 | $0 | Jun 16, 2025 |
| Oct 30, 2024 | 39128935L | RESOLVE | CLASS - 2 | OBSERVED NO VENTILATION IN THE BOILER ROOM HOUSING 3 GAS FIRED WATER HEATERS( 1 NOT WORKING) LOCATED IN THE BASEMENT/... | $0 | $0 | Jun 16, 2025 |
| Oct 30, 2024 | 39128950J | RESOLVE | CLASS - 2 | I OBSERVED IN THE BASEMENT BOILER ROOM THE FAILURE TO PROVIDE A REMOTE SHUT-DOWN FOR THE GAS FIRED WATER HEATERS AS R... | $0 | $0 | Jun 16, 2025 |
| Oct 30, 2024 | 39128954R | RESOLVE | CLASS - 2 | I OBSERVED IN THE MECHANICAL ROOMS LOCATED IN THE BASEMENT AREA THE FAILURE TO INSTALL GFCI OUTLETS FOR THE PROTECTIO... | $1,200 | $0 | Jan 7, 2025 |
| Oct 30, 2024 | 39128934J | RESOLVE | CLASS - 2 | OBSERVED PAINTED SPRINKLER HEADS ON THE 1 FLOOR ALSO OBSERVED PAINTED SPRINKLER CAPS THROUGHOUT BUILDING. AS PER 102.... | $0 | $0 | Jun 16, 2025 |
| Oct 30, 2024 | 39128949M | RESOLVE | CLASS - 1 | I OBSERVED ON ALL FLOORS THE FAILURE TO PROVIDE TAMPER-RESISTANT OUTLETS IN THE HALLWAYS ACCESSIBLE TO CHILDREN AS PE... | $2,500 | $0 | Jun 24, 2025 |
| Oct 30, 2024 | 39128952N | RESOLVE | CLASS - 1 | I OBSERVED THE USE OF THE DISCONNECT SUPPLYING POWER TO THE MITSUBISHI UNITS ON THE FAR SIDE OF THE 5TH FLOOR ROOF BE... | $400 | $0 | Jun 24, 2025 |
| Oct 30, 2024 | 39128955Z | RESOLVE | CLASS - 1 | I OBSERVED IN THE ELECTRICAL CLOSETS ON ALL FLOORS THE FAILURE TO PROPERLY TERMINATE THE BX CABLING IN THE ELECTRICAL... | $4,800 | $0 | Nov 14, 2025 |
| Oct 30, 2024 | 39128956K | RESOLVE | CLASS - 1 | I OBSERVED WORK PERFORMED BY UNKNOWN PERSONS TO INSTALL BRANCH CIRCUIT WIRING, RACEWAYS, WIRING, EQUIPMENT DISCONNECT... | $1,200 | $0 | Nov 14, 2025 |
| Oct 30, 2024 | 39128957M | RESOLVE | CLASS - 1 | I OBSERVED ON ALL THE ROOF AREAS THE INSTALLATION OF BRANCH CIRCUIT WIRING TO SUPPLY POWER FOR NEW ELECTRIC HEATING U... | $400 | $0 | Nov 14, 2025 |
| Oct 30, 2024 | 39128953P | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT WATER METER ROOM THE FAILURE TO INSTALL THE ELECTRICAL GROUND CONDUCTOR FOR THE ELECTRICAL... | $4,800 | $0 | Jun 24, 2025 |
| Oct 30, 2024 | 39128939Z | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS ON ROOF LEVEL AND ELECTRICAL ROOMS THROUGHOUT BUILDING. I... | $0 | $0 | Jun 16, 2025 |
| May 18, 2023 | 39086635R | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED. HAZARDOUS CONDITION CAR DOOR CAN BE OPENED OUTSIDE THE LANDI... | $1,280 | $0 | Jul 25, 2023 |
| Jul 10, 2018 | 32097353H | RESOLVE | CLASS - 2 | B254.15.32A.50A.50B.50C.50D.AT TIME OF INSPECTION THE FOLLOWING VIOLAITING CONDITIONS WERE OBSERVED:15-SEAL ALL HOLES... | $0 | $0 | Aug 28, 2018 |
| Nov 14, 2017 | 38258848M | RESOLVE | CLASS - 2 | 97X10. 97X10 DEVICE INOPERATIVE REPAIR. | $250 | $0 | Jan 2, 2018 |
| Jul 26, 2017 | 38256446K | RESOLVE | CLASS - 1 | 97X17. THE ELEVATOR OUT OF SERVICE. UPON INSP THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION... | $0 | $0 | Dec 12, 2017 |
| Mar 1, 2016 | 35171297Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING CODE COMPLIANT:LACK OF EMERGENCY LIGHTINGPER BC1006.1;27-542.NOTED:AT STAIR C2,C1,D4 AND... | $0 | $0 | Apr 19, 2016 |
| Mar 1, 2016 | 35171296M | RESOLVE | CLASS - 2 | WORK WITHOUT PERMIT.NOTED:INSTALLED 2 FLEX SIGNS-BUSINESS RELATED APPROXIMATELY 10'X20'.ONE ALONG 134 AVE AND ONE ALO... | $830 | $0 | Apr 19, 2016 |
| Jun 20, 2015 | 32075259Y | RESOLVE | CLASS - 2 | 254;4;15;32;50;50A; #4 MANUAL RESET LOW WATER CUT OFF MISSING #32 EXPOSED WIRING IN BOILER ROOM #50 REPLACE CORREDED ... | $0 | $0 | Aug 4, 2015 |
| Mar 8, 2015 | 35117714Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN EXTERIOR WALL IN A CODE COMPLIANT MANNER. A SECTION OF BRICK PARAPET AT THE SOUTH EXTERIOR WALL(A... | $500 | $0 | Jun 9, 2015 |
| May 19, 2010 | 32068786K | RESOLVE | CLASS - 1 | 51,32A SEALING #2 & #3 HOT WATER HEATERS.PARTIAL STOP WORK ORDER. 32A CICULATOR PUMP NOT HARDWIRED IN 32A SWITCH'S TW... | $13,000 | $0 | Dec 21, 2010 |
| May 14, 2010 | 34853434N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: CRACKS/STEP CRACKS ABOVE 5TH FLR WINDOW AT EXP 3 REAR (NORTH ... | $2,500 | $0 | Jul 6, 2010 |
| Feb 18, 1998 | 34169527L | RESOLVE | Hazardous | PLUMBING WORK WITHOUT A PERMIT. NOTE: PLUMBING WORK PROPOSED ON APP. #400761975 BEING DONE WITHOUT A PERMIT. REMEDY: ... | $500 | $0 | Aug 25, 1998 |
| Feb 18, 1998 | 34169528N | RESOLVE | Hazardous | PLUMBING WORK WITHOUT A PERMIT. NOTE: PLUMBING WORK PROPOSED OR APP #400774952 BEING DONE WITHOUT A PERMIT. REMEDY: O... | $500 | $0 | Aug 25, 1998 |
| Feb 18, 1998 | 34169529P | RESOLVE | Hazardous | PLUMBING WORK WITHOUT A PERMIT. NOTE: PLUMBING WORK PROPOSED ON APP #400800905 BEING DONE WITHOUT A PERMIT. REMEDY: O... | $250 | $0 | Aug 25, 1998 |
| Jan 25, 1995 | 34109679X | RESOLVE | Non-Hazardous | OCCLUPANCY CONTARY TO C OF O. UPON INSPETION A DELI/GROCERY STORE IS LOCATED IN LOBBY OF HOTEL. C OF O DOES NOT STATE... | $800 | $0 | Mar 14, 1995 |
| Feb 24, 1992 | 34068728P | RESOLVE | Non-Hazardous | INSUFFICIENT NUMBER OF SIAMESE CONNECTIONS CELLAR SPRINKLERED WITH NO SIAMESE OUTSIDE. REMEDY: INSTALL SUFFICIENT NUM... | $400 | $0 | May 19, 1992 |
| Jan 18, 1991 | 34049779L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN RECORD OF DACT & FILTER CLEANING. REMEDY. MAINTAIN RECORD OF DUCT & FILTER CLEANING. MERGENCY LIG... | $110 | $0 | May 7, 1991 |
| Jul 3, 1990 | 32006422X | RESOLVE | Non-Hazardous | 31A WIRING EXPOSED. 32- INSTALL CHAINS ON RELIEF VALVES | $85 | $0 | Nov 13, 1990 |
| Jun 3, 1988 | 34004921Y | RESOLVE | Hazardous | PLACE OF ASSEMBLY CONTRARY TO APPROVED PLAN. BANDSTAND CHANGED TO DIFFENENT LOCATION. REMEDY: AMEND PA PLAN OR RETURN... | $200 | $0 | Oct 11, 1988 |