Skip to content

ECB violations

134-01 Baisley Boulevard South, Queens • Block 12130 • Lot 0014

36 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 1, 2026 39182814M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED MISSING DOOR FOR ELEVATOR ROOM. REPLACED WITH PLYWOOD... $0 $0 Jun 9, 2026
Apr 1, 2026 39182815Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. SPRINKLER CAPS PAINTED THROUGHOUT THE BUILDING. POTENTIAL FIRE... $625 $625 Jun 9, 2026
Apr 1, 2026 39182813K ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED HOLE PENETRATIONS THROUGHOUT THE BUILDING(UNPERMITTED... $2,500 $2,500 Jun 9, 2026
Oct 30, 2024 39128940X RESOLVE CLASS - 1 FAILURE TO MAINTAIN ADEQUATE HOUSEKEEPING PER SECTION REQUIREMENTS. OBSERVED BUILDING MATERIALS AND BOXES AT BASE OF ... $1,250 $1,250 Mar 9, 2026
Oct 30, 2024 39128938R RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $2,500 $2,500 Mar 9, 2026
Oct 30, 2024 39128936N RESOLVE CLASS - 2 OBSERVED DEFECTIVE PUMP( WATER LEAK AND SCALING ON PUMP) LOCATED GAS METER ROOM, ALSO ACTIVE WATER LEAK IN THE BOILER... $312 $0 Jun 16, 2025
Oct 30, 2024 39128951L RESOLVE CLASS - 2 I OBSERVED ON THE ROOF AREAS THE UNPERMITTED SUE OF BX CABLING OUTDOORS, LFMC IN LENGTHS GREATER THAN 6 FT, AND FLEXI... $400 $0 Jun 16, 2025
Oct 30, 2024 39128935L RESOLVE CLASS - 2 OBSERVED NO VENTILATION IN THE BOILER ROOM HOUSING 3 GAS FIRED WATER HEATERS( 1 NOT WORKING) LOCATED IN THE BASEMENT/... $0 $0 Jun 16, 2025
Oct 30, 2024 39128950J RESOLVE CLASS - 2 I OBSERVED IN THE BASEMENT BOILER ROOM THE FAILURE TO PROVIDE A REMOTE SHUT-DOWN FOR THE GAS FIRED WATER HEATERS AS R... $0 $0 Jun 16, 2025
Oct 30, 2024 39128954R RESOLVE CLASS - 2 I OBSERVED IN THE MECHANICAL ROOMS LOCATED IN THE BASEMENT AREA THE FAILURE TO INSTALL GFCI OUTLETS FOR THE PROTECTIO... $1,200 $0 Jan 7, 2025
Oct 30, 2024 39128934J RESOLVE CLASS - 2 OBSERVED PAINTED SPRINKLER HEADS ON THE 1 FLOOR ALSO OBSERVED PAINTED SPRINKLER CAPS THROUGHOUT BUILDING. AS PER 102.... $0 $0 Jun 16, 2025
Oct 30, 2024 39128949M RESOLVE CLASS - 1 I OBSERVED ON ALL FLOORS THE FAILURE TO PROVIDE TAMPER-RESISTANT OUTLETS IN THE HALLWAYS ACCESSIBLE TO CHILDREN AS PE... $2,500 $0 Jun 24, 2025
Oct 30, 2024 39128952N RESOLVE CLASS - 1 I OBSERVED THE USE OF THE DISCONNECT SUPPLYING POWER TO THE MITSUBISHI UNITS ON THE FAR SIDE OF THE 5TH FLOOR ROOF BE... $400 $0 Jun 24, 2025
Oct 30, 2024 39128955Z RESOLVE CLASS - 1 I OBSERVED IN THE ELECTRICAL CLOSETS ON ALL FLOORS THE FAILURE TO PROPERLY TERMINATE THE BX CABLING IN THE ELECTRICAL... $4,800 $0 Nov 14, 2025
Oct 30, 2024 39128956K RESOLVE CLASS - 1 I OBSERVED WORK PERFORMED BY UNKNOWN PERSONS TO INSTALL BRANCH CIRCUIT WIRING, RACEWAYS, WIRING, EQUIPMENT DISCONNECT... $1,200 $0 Nov 14, 2025
Oct 30, 2024 39128957M RESOLVE CLASS - 1 I OBSERVED ON ALL THE ROOF AREAS THE INSTALLATION OF BRANCH CIRCUIT WIRING TO SUPPLY POWER FOR NEW ELECTRIC HEATING U... $400 $0 Nov 14, 2025
Oct 30, 2024 39128953P RESOLVE CLASS - 1 I OBSERVED IN THE BASEMENT WATER METER ROOM THE FAILURE TO INSTALL THE ELECTRICAL GROUND CONDUCTOR FOR THE ELECTRICAL... $4,800 $0 Jun 24, 2025
Oct 30, 2024 39128939Z RESOLVE CLASS - 2 EXIT DOOR NOT SELF-CLOSING. OBSERVED NON SELF CLOSING DOORS ON ROOF LEVEL AND ELECTRICAL ROOMS THROUGHOUT BUILDING. I... $0 $0 Jun 16, 2025
May 18, 2023 39086635R RESOLVE CLASS - 1 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED. HAZARDOUS CONDITION CAR DOOR CAN BE OPENED OUTSIDE THE LANDI... $1,280 $0 Jul 25, 2023
Jul 10, 2018 32097353H RESOLVE CLASS - 2 B254.15.32A.50A.50B.50C.50D.AT TIME OF INSPECTION THE FOLLOWING VIOLAITING CONDITIONS WERE OBSERVED:15-SEAL ALL HOLES... $0 $0 Aug 28, 2018
Nov 14, 2017 38258848M RESOLVE CLASS - 2 97X10. 97X10 DEVICE INOPERATIVE REPAIR. $250 $0 Jan 2, 2018
Jul 26, 2017 38256446K RESOLVE CLASS - 1 97X17. THE ELEVATOR OUT OF SERVICE. UPON INSP THE DEVICE IS FOUND TO BE OUT-OF-SERVICE CREATING A HAZARDOUS CONDITION... $0 $0 Dec 12, 2017
Mar 1, 2016 35171297Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING CODE COMPLIANT:LACK OF EMERGENCY LIGHTINGPER BC1006.1;27-542.NOTED:AT STAIR C2,C1,D4 AND... $0 $0 Apr 19, 2016
Mar 1, 2016 35171296M RESOLVE CLASS - 2 WORK WITHOUT PERMIT.NOTED:INSTALLED 2 FLEX SIGNS-BUSINESS RELATED APPROXIMATELY 10'X20'.ONE ALONG 134 AVE AND ONE ALO... $830 $0 Apr 19, 2016
Jun 20, 2015 32075259Y RESOLVE CLASS - 2 254;4;15;32;50;50A; #4 MANUAL RESET LOW WATER CUT OFF MISSING #32 EXPOSED WIRING IN BOILER ROOM #50 REPLACE CORREDED ... $0 $0 Aug 4, 2015
Mar 8, 2015 35117714Z RESOLVE CLASS - 1 FAILURE TO MAINTAIN EXTERIOR WALL IN A CODE COMPLIANT MANNER. A SECTION OF BRICK PARAPET AT THE SOUTH EXTERIOR WALL(A... $500 $0 Jun 9, 2015
May 19, 2010 32068786K RESOLVE CLASS - 1 51,32A SEALING #2 & #3 HOT WATER HEATERS.PARTIAL STOP WORK ORDER. 32A CICULATOR PUMP NOT HARDWIRED IN 32A SWITCH'S TW... $13,000 $0 Dec 21, 2010
May 14, 2010 34853434N RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCES. NOTED: CRACKS/STEP CRACKS ABOVE 5TH FLR WINDOW AT EXP 3 REAR (NORTH ... $2,500 $0 Jul 6, 2010
Feb 18, 1998 34169527L RESOLVE Hazardous PLUMBING WORK WITHOUT A PERMIT. NOTE: PLUMBING WORK PROPOSED ON APP. #400761975 BEING DONE WITHOUT A PERMIT. REMEDY: ... $500 $0 Aug 25, 1998
Feb 18, 1998 34169528N RESOLVE Hazardous PLUMBING WORK WITHOUT A PERMIT. NOTE: PLUMBING WORK PROPOSED OR APP #400774952 BEING DONE WITHOUT A PERMIT. REMEDY: O... $500 $0 Aug 25, 1998
Feb 18, 1998 34169529P RESOLVE Hazardous PLUMBING WORK WITHOUT A PERMIT. NOTE: PLUMBING WORK PROPOSED ON APP #400800905 BEING DONE WITHOUT A PERMIT. REMEDY: O... $250 $0 Aug 25, 1998
Jan 25, 1995 34109679X RESOLVE Non-Hazardous OCCLUPANCY CONTARY TO C OF O. UPON INSPETION A DELI/GROCERY STORE IS LOCATED IN LOBBY OF HOTEL. C OF O DOES NOT STATE... $800 $0 Mar 14, 1995
Feb 24, 1992 34068728P RESOLVE Non-Hazardous INSUFFICIENT NUMBER OF SIAMESE CONNECTIONS CELLAR SPRINKLERED WITH NO SIAMESE OUTSIDE. REMEDY: INSTALL SUFFICIENT NUM... $400 $0 May 19, 1992
Jan 18, 1991 34049779L RESOLVE Non-Hazardous FAILURE TO MAINTAIN RECORD OF DACT & FILTER CLEANING. REMEDY. MAINTAIN RECORD OF DUCT & FILTER CLEANING. MERGENCY LIG... $110 $0 May 7, 1991
Jul 3, 1990 32006422X RESOLVE Non-Hazardous 31A WIRING EXPOSED. 32- INSTALL CHAINS ON RELIEF VALVES $85 $0 Nov 13, 1990
Jun 3, 1988 34004921Y RESOLVE Hazardous PLACE OF ASSEMBLY CONTRARY TO APPROVED PLAN. BANDSTAND CHANGED TO DIFFENENT LOCATION. REMEDY: AMEND PA PLAN OR RETURN... $200 $0 Oct 11, 1988