ECB violations
136-05 Cranston Street, Queens • Block 12137 • Lot 0001
12 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 1, 2025 | 39161998N | RESOLVE | CLASS - 2 | OBSERVED ON THE BASEMENT FLOOR, SPRINKLER HEADS OBSTRUCTED, AND INCORRECT SPRINKLER HEADS USED IN THE STAIRWELL THROU... | $3,125 | $3,125 | Dec 9, 2025 |
| Oct 1, 2025 | 39162006X | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. OBSERVED GAS METER ROOM DOOR NON SELF CLOSING. POTENTIAL FIR HAZARD. LOCATED ON GROUND FO... | $1,562 | $1,562 | Dec 9, 2025 |
| Oct 1, 2025 | 39162005Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED 3RD AND 2ND FLOOR MECHANICAL ROOMS OBSTRUCTED WITH BA... | $3,125 | $3,125 | Dec 9, 2025 |
| Oct 1, 2025 | 39162007H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... | $12,500 | $12,500 | Dec 9, 2025 |
| Jul 23, 2019 | 39006140M | RESOLVE | CLASS - 2 | ECCESSIVE STORAGE IN THE ELECTRICAL EQUIPMENT ROOM WITH CARD BOARD BOXES CLEANING EQUIPMENT AND PLASTIC BAGS OF MATER... | $250 | $0 | Nov 12, 2019 |
| Jul 23, 2019 | 39006145L | RESOLVE | CLASS - 2 | OBSERVED THE ELECTRICAL EQUIPMENT ROOM BEING USED AS A EMPLOYEE BREAKROOM, THERE IS A MICROWAVE, WATERCOOLER, TABLE W... | $0 | $0 | Nov 12, 2019 |
| Jul 23, 2019 | 39006138N | RESOLVE | CLASS - 2 | I OBSERVED NO ILLUMINATION ALONG THE COVERED PASSAGEWAY RAMP PROVIDING EGRESS FROM THE PROPERTY. ALSO NOTED DEFECTIVE... | $400 | $0 | Nov 12, 2019 |
| Jul 23, 2019 | 39006150X | RESOLVE | CLASS - 2 | OBSERVED IN COURTYARD THE INSTALLATION OF OUTDOOR BOXES FOR GFCI RECEPTACLES WITHOUT PROPER RACEWAYS INSTALLED AND EX... | $800 | $0 | Nov 12, 2019 |
| Jul 23, 2019 | 39006136J | RESOLVE | CLASS - 1 | NO REMOTE SHUTDOWN INSTALLED FOR GAS FIRED SYSTEMS OUTSIDE OF ALL MECHANICAL ROOMS. AS PER MC 1006.8.1 A REMOTE SHUTD... | $0 | $0 | Nov 12, 2019 |
| Jan 31, 2019 | 35372717M | ACTIVE | CLASS - 2 | FAIL TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER RE:INSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC... | $625 | $0 | Jun 18, 2019 |
| Jan 31, 2019 | 35372716K | RESOLVE | CLASS - 1 | FGC 411.1 RESIDENTIAL GAS FLEX USED ON COMMERCIAL EQUIPMENT. OBSERVED 1/31/19 AT ABOVE ADDRESS RESIDENTIAL GAS FLEX U... | $625 | $0 | Jun 18, 2019 |
| Sep 11, 2018 | 35348936M | RESOLVE | CLASS - 1 | BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY. NOTED: PREMISES IS A 3 STORY HOTEL. C OF O #420319337T003... | $6,250 | $0 | Oct 30, 2018 |