ECB violations

North Conduit Avenue, Queens • Block 12137 • Lot 0020

42 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Jun 15, 2026 39192597Y ACTIVE CLASS - 1 ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN MAIN ELECTRICAL ONE NEW RISER LEAVING DISTRIBUTION GOING TO RM L39 FEED... $2,500 $2,500 Aug 25, 2026
Jun 15, 2026 39192598X ACTIVE CLASS - 2 UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... $800 $800 Aug 25, 2026
Jun 15, 2026 39192599H ACTIVE CLASS - 2 FAILURE TO PROPERLY SECURE/SUPPORT ELECTRICAL METALLIC TUBING. OBSERVED ON THE ROOF ALUMINUM PIPE WAS NOT SUPPORTED C... $500 $500 Aug 25, 2026
Jun 15, 2026 39192630R RESOLVE CLASS - 2 CLASS 2: 1) EMERGENCY PHONE INOPERATIVE AS PER ASME A17.1/CSA B44 2.27.1. REMEDY: RESTORE TWO-WAY EMERGENCY COMMUNICA... $0 $0 Aug 25, 2026
Jun 15, 2026 39192620N ACTIVE CLASS - 1 ATOI OBSERVED IN BASEMENT LACK OF SPRINKLER COVERAGE IN LAUNDRY ROOM, IMPROPER MATERIAL USED ON DRYER VENTS. PER PC 1... $2,500 $2,500 Aug 25, 2026
Jun 15, 2026 39192629J ACTIVE CLASS - 1 CLASS 1 RTS: FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-9... $1,250 $1,250 Aug 25, 2026
Jun 15, 2026 39192596M ACTIVE CLASS - 1 ELECTRICAL CLOSET NOT DEDICATED TO ELECTRICAL DISTRIBUTION EQUIPMENT ONLY. OBSERVED ON THE 1ST AND 2ND FL, BASEMENT A... $1,200 $1,200 Aug 25, 2026
Dec 16, 2025 39170601K ACTIVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER FOR SUMMONS 39151545L. OBSERVED GATES AT EMERGENCY EGRESS ARE P... $25,000 $25,000 Feb 24, 2026
Dec 16, 2025 39170602M ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH DEPARTMENT OF BUILDING FOR SUMMO... $6,250 $6,250 Feb 24, 2026
Dec 16, 2025 39170600Z ACTIVE CLASS - 2 FAILURE TO COMPLY WITH COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH DEPARTMENT OF BUILDING FOR SUMMO... $6,250 $6,250 Feb 24, 2026
Jun 20, 2025 39151546N ACTIVE CLASS - 1 UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED GAS POWERED SNOW BLOWER, ELECTRICAL SCOOTER, AND GASOL... $2,500 $0 Mar 17, 2026
Jun 20, 2025 39151544J RESOLVE CLASS - 1 FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED 6 FOOT METAL STANDING FANS IN PUBLIC HALLWAYS AND VENDING M... $1,250 $1,250 Mar 17, 2026
Jun 20, 2025 39151543H RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 ... $1,250 $1,250 Mar 17, 2026
Jun 20, 2025 39151545L RESOLVE CLASS - 1 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED GATES AT EMERGENCY EGRESS ARE PAD LOCKED AT CHAINED. ... $1,250 $0 Mar 17, 2026
Nov 3, 2023 39098753X RESOLVE CLASS - 1 THE ONLY ELEVATOR IN BUILDING (OR SECTION OF BUILDING) OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT... $1,250 $0 Jan 9, 2024
Oct 20, 2022 39072348R RESOLVE CLASS - 2 CAT ONE TAG EXPIRED ON 9/20. PROPERLY SECURED THE SAFETY EDGE STICK ON THE CAR DOOR SIDE. $0 $0 Dec 6, 2022
Aug 19, 2021 39046247Z RESOLVE CLASS - 1 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED (CU). OIL LEAK IN PIT DEVICE FAILED DRIFT TEST. IT MOVE 1" IN... $1,250 $0 Oct 5, 2021
Nov 22, 2019 35434244M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 11/12/19 AT ABOVE ADDRESS NO VENTILATION IN GAS MET... $0 $0 Feb 18, 2020
Sep 25, 2019 38271786M RESOLVE CLASS - 2 97-X-17 UPON INSPECTION DEVICE WAS FOUND TO BE OUT OF SERVICE. RESTORETO SERVICE IMMEDIATLEY & CONTACT NYCDOB FOR A C... $312 $0 Mar 3, 2020
Jun 5, 2018 35335438R RESOLVE CLASS - 3 FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED IN GAS METER ROOM IN CELLAR, NO VENTILATION INSTALLED... $0 $0 Jul 24, 2018
Nov 21, 2017 35297213L RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVED AT A RISER FOR THE AUTOMATIC FIRE SPRINKLER SYSTEM A BU... $500 $0 Feb 6, 2018
Nov 21, 2017 35297105Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: IN ROOMS L47 & L29,BO... $0 $0 Feb 6, 2018
Nov 21, 2017 35297220J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVED IN BOILER ROOM 2 EXHAUST FAN FOR THE BOILER ROOM BEING ... $0 $0 Feb 6, 2018
Nov 21, 2017 35297212J RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVED THE F.D.CONNECTION CHECK VALVE AT THE FRONT LEFT OF THE... $500 $0 Feb 6, 2018
Nov 21, 2017 35296974L RESOLVE CLASS - 2 FAILURE TO INSTALLED GROUND FAULT CIRCUIT INTERRUPTER(GFCI)PROTECTION AD REQUIRED. IBSERVED IN LAUNDRY ROOM. RECEPTAC... $1,200 $0 Apr 24, 2018
Nov 21, 2017 35297218K RESOLVE CLASS - 2 WORK W/O A PERMIT. OBSERVED IN CELLAR A 4'INCH F.D. CHECK VALUE INSTALLED & SEVERAL FEET OF SCHEDULE 10 LIGHT WALL PI... $400 $0 Feb 6, 2018
Nov 21, 2017 35297219M RESOLVE CLASS - 2 FAILURE TO HAVE OR ALTERED PLUMBING SYSTEM TESTED. OBSERVED IN CELLAR A 4'INCH F.D. CHECK VALVUE & SEVERAL FEET OF SC... $500 $0 Feb 6, 2018
Nov 21, 2017 35297104M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. NOTED: IN BOILER ROOM(RM 22),CONCRETE CEILING & WALLS CRACKED IN V... $0 $0 Feb 6, 2018
Nov 21, 2017 35297217Z RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. OBSERVED ON ROOF GAS SUPPLY PIPING TO HVAC SYSTEM INCORRECTLY SU... $0 $0 Feb 6, 2018
Nov 21, 2017 35297214N RESOLVE CLASS - 2 SEC. 903.6 FAILURE TO PAINT DEDICATED SPRINKLER PIPING/VALVE IN ACCORDANCE W/SECTION. OBSERVED IN SEVERAL LOCATION IN... $400 $0 Apr 24, 2018
Nov 21, 2017 35297216R RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT. OBSERVED AT THE ROOF THE WENT THROUGH ROOF(VTR)TERMINATING BELOW THE HE... $200 $0 Feb 6, 2018
Nov 21, 2017 35297215P RESOLVE CLASS - 2 SEC. 411.1 RESIDENTIAL GAS FLEX HOSE USED ON COMMERCIAL EQUIPMENT. OBSERVED IN KITCHEN RESIDENTIAL GAS FLEX HOSE USED... $800 $0 Feb 6, 2018
Jan 10, 2017 35225602M RESOLVE CLASS - 1 SEC. 411.1 MISC VIO: RESIDENTIAL GAS FLEX USED ON COMMECIAL EQUIPMENT.AT THE TIME OF MY INSPECTION ON 1-10-17 AT THE ... $1,600 $0 Mar 7, 2017
Jan 10, 2017 35225604X RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. AT THE TIME OF MYINSPECTION ON 1-10-17 AT THE ABOVE PLACE OF OCC... $500 $0 Mar 7, 2017
Jan 10, 2017 35225603Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BLDG IN A CODE COMPLIANT MANNER. AT THE TIME OF MYINSPECTION ON 1-10-17 AT THE ABOVE PLACE OF OCC... $500 $0 Mar 7, 2017
Jan 10, 2017 35225625P RESOLVE CLASS - 3 FAILURE TO MAINTAIN BLDG WALLS OR APPURTENANCE DEFECT NOTED: ELEVATOR SHAFT EXTERIOR BRICK WALL HAS APPROX 1 1/2"WIDE... $0 $0 Feb 28, 2017
Oct 15, 2003 38142376Z RESOLVE Non-Hazardous 17D06/ 17H11/ 10M07/ 06B11/ 47Y13/ 47O02/ 10=FRON DOOR. 06=REPLACE GATE SWITCH ROLLER. $0 $0 Dec 2, 2003
Aug 7, 2001 34298521L RESOLVE Non-Hazardous OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS. UPON INSPECTION OF... $400 $0 Jan 8, 2002
Apr 5, 2000 38096305R RESOLVE Non-Hazardous 16H12,25E11,43B01,57Y14,57Y02, (43)STOPPING HARD. $0 $0 May 23, 2000
Jul 22, 1999 38086648J RESOLVE Non-Hazardous 11Q,25O,30O,35O,36Q,43Y,57O,73U,74O. CLEAN TOP OF CAR, PERFORM THREE YEAR PRESSURE TEST, CLEAN ENTRANCE TO PUMO ROOM. $0 $0 Sep 7, 1999
Sep 8, 1998 38079086L RESOLVE Non-Hazardous 40Y14, 73O2, 35O2, 22D6 $0 $0 Oct 27, 1998
Mar 8, 1991 38008410X RESOLVE Non-Hazardous 50Y,73O,74O. (50) REMOVE OIL FROM DRIP PAN. (74) CLEAN TOP OF CAR. $1,000 $0 Apr 23, 1991