ECB violations
146-80 Guy R Brewer Boulevard, Queens • Block 13307 • Lot 0091
45 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jan 30, 2026 | 39175413X | ACTIVE | CLASS - 2 | OBSERVED A POWERFLAME BURNER MODEL WCR3-G-20 SERIAL # 082287282 INSTALLED WITHOUT A PERMIT. OBTAIN THE PROPER PERMIT ... | $1,250 | $0 | Feb 6, 2026 |
| Dec 9, 2022 | 39075415L | ACTIVE | CLASS - 3 | FOUND POWERFLAME GAS FIRED BURNER MODEL # WCR3-G-20, SERIAL # 082287282 BEING INSTALLED WITHOUT A PERMIT ON A WEIL MC... | $250 | $0 | Jan 11, 2023 |
| Nov 22, 2022 | 39074350P | ACTIVE | CLASS - 2 | OBSERVED ACTIVE WATER LEAK ON PUMP IN THE BOILER ROOM THAT IS LOCATED IN THE CELLAR. AS PER PC 102.3 MAINTENANCE. INS... | $625 | $0 | Dec 8, 2022 |
| Nov 21, 2022 | 39074205Z | ACTIVE | CLASS - 2 | CIRCULATOR LEAKING, NO FITTINGS/THREADS ON EXPANSION TANK RELIEF VALVE DISCHARGE PIPING TERMINATION, NO THREADS ON RE... | $625 | $0 | Dec 8, 2022 |
| Jan 26, 2022 | 35644907J | ACTIVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY W/COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP WAS MADE TO CORRECT OR CERTIFY ECB #'... | $2,500 | $0 | May 24, 2022 |
| Jan 11, 2022 | 39054079Z | ACTIVE | CLASS - 2 | I OBSERVED ACTIVE WATER LEAK AT THE EXPANSION TANK LOCATED IN THE BOILER ROOM AT CELLAR/BASEMENT LEVEL, BOILER #2 MIS... | $625 | $0 | Feb 11, 2022 |
| Dec 14, 2021 | 35634552K | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH COMMISSIONER'S ORDERS.RECORDS INDICATE NO APP MADE TO CORRECT OR CERTIFY ECB #35... | $0 | $0 | Mar 29, 2022 |
| Nov 4, 2021 | 35634288K | ACTIVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY W/AN ORDER OF THE COMMISSIONER.FAILURETO CORRECT & CERTIFY SUMMONS ECB#35423759H & EC... | $2,500 | $0 | Feb 1, 2022 |
| Sep 17, 2021 | 39047861N | ACTIVE | CLASS - 2 | AIR SEPERATOR LEAKING, NO FITTINGS/THREADS ON EXPANSION TANK RELIEF DISCHARGE PIPING TERMINATION. | $625 | $0 | Oct 15, 2021 |
| Aug 4, 2021 | 35583903X | ACTIVE | CLASS - 1 | AN UNLAWFUL ACT. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS #3534637... | $2,500 | $0 | Oct 26, 2021 |
| Jun 26, 2021 | 35583629M | ACTIVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. FAILURE TO CORRECT AND CERTIFY SUMMONS #35379762N... | $2,500 | $0 | Sep 14, 2021 |
| Jan 6, 2021 | 39034377Z | RESOLVE | CLASS - 2 | NO STORAGE IN BOILER ROOM, CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORRECTION | $625 | $0 | Jan 22, 2021 |
| Mar 4, 2020 | 39018872X | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Mar 16, 2020 |
| Feb 18, 2020 | 39017762K | ACTIVE | CLASS - 2 | BOILER RELIEF VALVE LEAKING, REMOVE THREADS ON DISCHARGE PIPING FOR RELIEF ON EXPANSION TANKS AND BACKFLOW PREVENTER,... | $625 | $0 | Feb 21, 2020 |
| Feb 18, 2020 | 39017761Z | ACTIVE | CLASS - 2 | REMOVE THREADS ON RELIEF VALVE DISCHARGE PIPING FOR EXPANSION TANKS AND BACKFLOW PREVENTER, PLUG OR CAP OPEN VALVES, ... | $625 | $0 | Feb 21, 2020 |
| Jan 28, 2020 | 39016419Z | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLAINT MANNER- I OBSERVED NO BALL DRIP INSTALLED BETWEEN THE FIRE DEPARTMENT ... | $625 | $0 | Feb 5, 2020 |
| Oct 17, 2019 | 35460635Z | ACTIVE | CLASS - 1 | UNLAWFUL ACTS UNABLE TO COMPLY WITH AN ORDER OF THE COMMISSIONERS.RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT... | $2,500 | $0 | Dec 31, 2019 |
| Aug 16, 2019 | 35445685L | ACTIVE | CLASS - 1 | AN UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF TEH COMMISSIONER FAILURE TO CORRECT AND CERTIFY SUMMONS #3537962N ... | $12,500 | $12,500 | Oct 22, 2019 |
| Jun 24, 2019 | 35423759H | ACTIVE | CLASS - 1 | UNLAWFUOL ACTS FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICTE NO APPLICATION WAS MADE TO CORREC... | $0 | $0 | Sep 10, 2019 |
| May 10, 2019 | 35423606R | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT... | $0 | $0 | Jul 16, 2019 |
| Mar 13, 2019 | 35359037M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER,RECORDS INDICATE APPLICATION NOT MADE TO CORRECT&CE... | $0 | $0 | May 21, 2019 |
| Jan 29, 2019 | 32097845Y | RESOLVE | CLASS - 2 | B254,15,32A,45A,50A,50B. WEIL MCLAIN BOILER MDL 1288: 50A-MOTORIZED LOUVER NOT OPERABLE; 50B-CIRCULATORS LEAKING WATE... | $0 | $0 | Apr 30, 2019 |
| Jan 29, 2019 | 32097846X | ACTIVE | CLASS - 2 | B254,15,32A,45A,50A,50B. WEIL MCLAIN BOILER MDL #1288: 50A-MOTORIZED LOUVER NOT OPERABLE; 50B-CIRCULATOR LEAKING WATE... | $0 | $0 | Apr 30, 2019 |
| Jan 24, 2019 | 35372715Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED ON 01/24/19 AT ABOVE ADDRESS HOT WATER PUMP LEAKING TH... | $0 | $0 | Apr 9, 2019 |
| Jan 8, 2019 | 35379763P | ACTIVE | CLASS - 2 | FAILURE TO PROVIDE (GFCI)GROUND FAULT CIRCUIT INTERRUPTER PROTECTION AS REQUIRED. OBSERVED RECEPTACLE OUTLET OF THE T... | $0 | $0 | Mar 26, 2019 |
| Jan 8, 2019 | 35379762N | ACTIVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS DEVICES MATERIALS APPLIANCES OR WIRING IN USE. OBSERVED O... | $0 | $0 | Mar 26, 2019 |
| Sep 13, 2018 | 35346153R | ACTIVE | CLASS - 1 | UNLAWFUL ACT FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT... | $0 | $0 | Nov 27, 2018 |
| Jul 13, 2018 | 35346375M | ACTIVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... | $0 | $0 | Oct 2, 2018 |
| Jul 13, 2018 | 35346376Y | ACTIVE | CLASS - 2 | FAILURE TO PROVIDE EFFECTIVE ELECTRICAL CONTINUITY FOR METAL RACEWAYS CABLE ASSEMBLIES/BOXES/CABINETS/FITTINGS.OBSERV... | $0 | $0 | Oct 2, 2018 |
| Jul 10, 2018 | 32097352X | RESOLVE | CLASS - 2 | 15,32A,45A,50A,50B,50C,50D,50E-AT TIME OF INSPECTION, THE FOLLOWING VIOLATIONS WERE OBSERVED: 15,32A,45A)5 HEADS LEAK... | $0 | $0 | Oct 9, 2018 |
| Jul 10, 2018 | 32097351Y | RESOLVE | CLASS - 2 | 15,45A,50A,50B,50C-AT TIME OF INSPECTION, THE FOLLOWING VIOLATIONS WERE OBSERVED: 15&45A)THREE HEADS LEAKING. 50A)MOT... | $0 | $0 | Oct 9, 2018 |
| Jan 23, 2018 | 35297847N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED A INSPECTOR'S TEST STATION, NO PRESSURE GAUGE INSTALL... | $0 | $0 | Apr 3, 2018 |
| Jan 23, 2018 | 35297848P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT THE FIRE DEPARTMENT CONNECTIONS AT DIFFERENT LOCAT... | $0 | $0 | Apr 3, 2018 |
| Jan 23, 2018 | 35297849R | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER; FAILURE TO COMPLY WITH LAW FOR DRAINAGE SYSTEM PER PC 702.1; 2... | $0 | $0 | Apr 3, 2018 |
| Jul 17, 2017 | 35286761Z | ACTIVE | CLASS - 2 | FAILURE TO PAINT DEDICATED SPRINKLER PIPING/VALUES IN ACCORDANCE WITH SECTION. OBSERVED IN BOILER ROOM UNPAINTED FIRE... | $0 | $0 | Oct 17, 2017 |
| Jul 17, 2017 | 35286760R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED AT ACCESS PANELS IN KITCHEN CEILINGS IN ROOMS 107 AND... | $0 | $0 | Oct 17, 2017 |
| Jul 17, 2017 | 35287062Y | ACTIVE | CLASS - 2 | FAILURE TO PROVIDE (GFCI) GROUND FAULT CIRCUIT INTERRUPTER PROTECTION AS REQUIRED. OBSERVED RECEPTACLE OUTLETS NOT OF... | $0 | $0 | Oct 16, 2017 |
| Jul 17, 2017 | 35287063X | ACTIVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT. OBSERVED NEW PANELS AND JUNCTION BOXES THROUGHOUT HALLS. ALSO NOTED EXISTING PANELS DIS... | $0 | $0 | Oct 16, 2017 |
| Jul 17, 2017 | 35287061M | ACTIVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT, MATERIALS APPARATUSDEVICE APPLIANCE OR WIRING IN USE. OBSERVED EXP... | $0 | $0 | Oct 16, 2017 |
| Jan 18, 2017 | 35225612X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION I OBSERVED IN THE CELLAR NO TEST TEE INSTALL... | $0 | $0 | Mar 21, 2017 |
| Jan 18, 2017 | 35225611Y | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. AT TIME OF INSPECTION I OBSERVED ON THE FIRST FLOOR OF THE BLDG TW... | $0 | $0 | Mar 21, 2017 |
| Oct 26, 2016 | 35216312J | ACTIVE | CLASS - 2 | FAIL TO MAINTAIN BLDG IN CODE COMPLIANT MANNER, REINSTALLATION/MAINTENANCE OF PLUMBING MATERIALS/EQUIPMENT PER PC102.... | $0 | $0 | Jan 24, 2017 |
| Oct 26, 2016 | 35216313L | RESOLVE | CLASS - 2 | FAILURE TO PAINT DEDICATED SPRINKLERS PIPING/VALVES IN ACCORDANCE W/ SECTION. @ TIME OF INSP, 1:10PM ON 10/26/16 @ TH... | $0 | $0 | Jan 24, 2017 |
| Oct 26, 2016 | 35216314N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. @ TIME OF INSP 1:10PM ON 10/26/16 @ THE ABOVE PLACE OF OCCURENECE ... | $0 | $0 | Jan 24, 2017 |
| Aug 4, 1993 | 38036026J | RESOLVE | Non-Hazardous | 73U 35L 57L 73 PROVIDE DEVICE TAGS AS PER CODE 208/10 35 COVERS ON LIGHT SWITCH AND OUTLET TWIN RECEPTACLES 57 PIT LI... | $1,000 | $0 | Sep 21, 1993 |