ECB violations
149 Road, Queens • Block 13381 • Lot 0001
78 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 3, 2026 | 39183146K | RESOLVE | CLASS - 1 | CLASS 1 DOOR ZONE RESTRICTOR INOPERATIVE. THIS IS A SAFETY FEATURE WHICH ENSURES PASSENGER SAFETY. REMEDY: TO RESTORE... | $1,250 | $0 | Aug 25, 2026 |
| Mar 4, 2025 | 39140359Y | RESOLVE | CLASS - 1 | I OBSERVED THE FEEDS FOR THE SCAFFOLD MOTORS PASSING THE DOORWAYS OF THE ELECTRICAL ROOM, ALSO PASSING UNPROTECTED TH... | $1,600 | $0 | Jul 1, 2025 |
| Mar 4, 2025 | 39140358M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN COMPLETE DRAWINGS AND INSPECTION LOGS ON SITE, NO APPROVED DRAWINGS FOR SUPPORTED, OR PIPE SCAFFO... | $2,500 | $0 | Oct 28, 2025 |
| Mar 4, 2025 | 39140360L | RESOLVE | CLASS - 1 | I OBSERVED THE SAFETY LINES NOT INSTALLED AS REQUIRED, I NOTED THEM INSTALLED BENEATH DEBRIS , PASSING THROUGH THE CO... | $10,000 | $0 | Jul 1, 2025 |
| Mar 4, 2025 | 39140338P | RESOLVE | CLASS - 1 | OBSERVED EXCESSIVE HOLE PENETRATIONS THROUGHOUT BUILDING. PRIMARY IN THE MECHANICAL ROOMS ON EACH FLOOR. POTENTIAL FI... | $2,500 | $0 | May 13, 2025 |
| Mar 4, 2025 | 39140361N | RESOLVE | CLASS - 1 | I OBSERVED THE FAILURE TO MAINTAIN THE NETTING ON THE PIPE LADDER SCAFFOLDING AT EXPOSURE #1 AS REQUIRED IN BC 3309.1... | $10,000 | $0 | Jul 1, 2025 |
| Mar 13, 2024 | 39108609H | RESOLVE | CLASS - 2 | OBSERVED QUICK DISCONNECT PIPING TO STATIONARY GAS EQUIPMENT LOCATED IN THE KITCHEN. AS PER 411.1.1 OF THE FGC COMMER... | $625 | $0 | Aug 20, 2024 |
| Mar 1, 2024 | 39107394P | RESOLVE | CLASS - 2 | FEDERAL BOILER MODEL# FST-200. FOUUND FRESH AIR FAN INTERLOCK IS BYPASSED AND BACK FLOW PREVENTER IS LEAKING. CORRECT... | $0 | $0 | May 7, 2024 |
| Nov 3, 2022 | 39073373N | RESOLVE | CLASS - 1 | AT CELLAR LEVEL, RECREATION/CLASS ROOMS (RM # 18,18, 19, 3 & 5) EXIT DOORS & EXIT PASSAGEWAY ARE BEING BLOCKED BY GAT... | $1,250 | $0 | Dec 20, 2022 |
| Nov 3, 2022 | 39073379Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE LAUNDRY ROOM TWO SWITCHES SUPPLYING POWER TO THE WASHING MACHINES WITH THE CONDUCTORS PASSING FROM ... | $800 | $0 | Jan 17, 2023 |
| Nov 3, 2022 | 39073372L | RESOLVE | CLASS - 2 | OBSERVED: AT EXPOSURE # 1&3, BBQ AREA CMU RETAINING WALLS, EXTERNAL ENCLOSURE CMU WALLS/ (FENCE), ALSO, AT CELLAR LEV... | $625 | $0 | Jan 17, 2023 |
| Nov 3, 2022 | 39073380L | RESOLVE | CLASS - 1 | I OBSERVED IN THE BASEMENT BOOSTER PUMP ROOM CONDUITS AND FLEXIBLE RACEWAYS BROKEN WITH EXPOSED ENERGIZED CONDUCTORS.... | $1,600 | $0 | Apr 4, 2023 |
| Nov 3, 2022 | 39073348L | RESOLVE | CLASS - 2 | BRAKE MAINTENANCE TAG EXPIRED ON 10/28/21. | $312 | $0 | Jan 17, 2023 |
| Nov 3, 2022 | 39073347J | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). BRAKE MAINTENANCE TAG EXPIRED ON 10/28/21. | $312 | $0 | Jan 17, 2023 |
| Nov 3, 2022 | 39073378M | RESOLVE | CLASS - 2 | I OBSERVED IN THE MAIN BUILDING THE INSTALLATION OF CONDUITS, SUB-FEEDER WIRING,CIRCUIT BREAKER PANELS, BRANCH CIRCUI... | $800 | $0 | Jan 17, 2023 |
| Nov 3, 2022 | 39073377K | RESOLVE | CLASS - 2 | I OBSERVED ON MULTIPLE FLOORS IN THE MAIN AND NEW BUILDINGS THE INSTALLATION OF NEW EMERGENCY LIGHTS WITH WIREMOLD RA... | $600 | $0 | Dec 20, 2022 |
| Nov 3, 2022 | 39073375R | RESOLVE | CLASS - 2 | OBSERVED: - AT FIRST FL, LAUNDRY ROOM DOORS, AT CELLAR LEVEL, SMOKE DOOR NEAR ELEVATOR, EXIT DOOR BETWEEN BOILER AND ... | $312 | $0 | Dec 20, 2022 |
| Nov 3, 2022 | 39073364L | RESOLVE | CLASS - 3 | SPRINKLER PIPE ON THE 2ND FL IN THE STAIRCASE NOT SUPPORTED CORRECTLY. SPRINKLER BRANCH IS BEING SUPPORTED WITH BAND ... | $250 | $0 | Dec 20, 2022 |
| Nov 3, 2022 | 39073371J | RESOLVE | CLASS - 2 | OBSERVED: -AT CELLAR LEVEL, EXIT DOOR BETWEEN BOILER AND LAUNDRY ROOMS ILLEGAL HARDWARE ALSO, AT CELLAR LEVEL, RECREA... | $312 | $0 | Dec 20, 2022 |
| Nov 3, 2022 | 39073374P | RESOLVE | CLASS - 2 | OBSERVED - AT 6TH FL, BANK A &B, UTILITIES ROOMS (FROM 2ND FL TO 6TH FL), AT CELLAR LEVEL MB27 RM, EXIT DOOR COMPUTER... | $625 | $0 | Dec 20, 2022 |
| Mar 2, 2020 | 39018638H | RESOLVE | CLASS - 1 | DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH. | $1,250 | $0 | Dec 15, 2020 |
| Feb 7, 2020 | 39017097J | RESOLVE | CLASS - 2 | NOTED: OBSERVED AT ROOF, LOOSE/MISSING CORRUGATED METAL AROUND BULKHEAD., REPAIR AND/OR REPLACE | $0 | $0 | Mar 24, 2020 |
| Feb 7, 2020 | 39017099N | ACTIVE | CLASS - 2 | NOTED: BUILDING ALTERED AND OCCUPIED UNDER ALT-1 APPLICATION #401685798 WITHOUT OBTAINING A VALID CERTIFICATE OF OCCU... | $1,250 | $0 | Aug 25, 2020 |
| Feb 7, 2020 | 39017098L | RESOLVE | CLASS - 2 | NOTED: OBSERVED AT MAIN ENTRANCE AND EXIT DOOR, MAGNETIC LOCKING DEVICES BEING USE WITH A REMOTE RELEASE SWITCH APPRO... | $0 | $0 | Mar 24, 2020 |
| Feb 7, 2020 | 39017513J | RESOLVE | CLASS - 2 | NOTED: OBSERVED WATER PENETRATING INTO THE ELECTRICAL ROOM AT CELLAR FROM SOUTH EXTERIOR STAIRS., MAINTAIN EXTERIOR B... | $0 | $0 | Mar 31, 2020 |
| Feb 7, 2020 | 39017094Y | RESOLVE | CLASS - 1 | I OBSERVED IN THE MAIN ELECTRICAL ROOM LOCATED IN THE BASEMENT, THE MAIN COPPER DETAIL, DRILLED MULTIPLE TIMES TO ADD... | $1,600 | $0 | Aug 25, 2020 |
| Feb 7, 2020 | 39017096H | RESOLVE | CLASS - 2 | NOTED: OBSERVED WATER PENETRATING INTO THE ELECTRICAL ROOM AT CELLAR FROM SOUTH EXTERIOR STAIRS., MAINTAIN EXTERIOR B... | $0 | $0 | May 12, 2020 |
| Jul 31, 2019 | 39006890L | RESOLVE | CLASS - 1 | OBSERVED THE INSTALLATION OF CONDUCTORS FROM A 200 AMP DISCONNECT TO A CIRCUIT BREAKER ENCLOSURE LABELED "SECURITY" I... | $4,800 | $0 | Sep 17, 2019 |
| Jul 31, 2019 | 39006891N | RESOLVE | CLASS - 2 | NORTH BUILDING MAIN ELECTRICAL ROOM, LARGE HOLES WERE CUT IN CONCRETE CEILING FOR DRAIN PIPES FROM BATHROOM ABOVE, AR... | $625 | $0 | Sep 17, 2019 |
| Jul 31, 2019 | 39006892P | RESOLVE | CLASS - 1 | DURING MY SCHEDULED INSPECTION I OBSERVED THE VIOLATING CONDITIONS AS STATED IN ECB # 35386386Y ISSUED ON 02/07/2019 ... | $0 | $0 | Jan 17, 2020 |
| Jul 31, 2019 | 39006887K | RESOLVE | CLASS - 2 | OBSERVED IN THE NORTHSIDE BUILDING IN THE BASEMENT AND HALLS ON ALL FLOORS THE IMPROPER INSTALLATION OF EMERGENCY LIG... | $250 | $0 | Sep 17, 2019 |
| Jul 31, 2019 | 39006889Y | RESOLVE | CLASS - 2 | OBSERVED IN NORTHSIDE BUILDING BASEMENT ELECTRICAL METER ROOM THE INSTALLATION OF CONDUITS, BRANCH CIRCUIT WIRING, OV... | $400 | $0 | Sep 17, 2019 |
| Feb 7, 2019 | 35386385M | RESOLVE | CLASS - 2 | ELECTRICAL WORK W/O A PERMIT. OBSERVED IN ELEVATOR MOTOR ROOM THE INSTALLATION OF FAN UNIT FOR COOLING,W/ COMPRESSOR ... | $400 | $0 | May 7, 2019 |
| Feb 7, 2019 | 35386386Y | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE. OBSERVED I... | $1,000 | $0 | May 7, 2019 |
| Feb 7, 2019 | 35386387X | RESOLVE | CLASS - 2 | EC 400.8 UNPERMITTED USES OF FLEXIBLE CORDS. OBSERVED IN OSY CLOSETS ON THE 5TH FL SOUTHSIDE THE CONNECTION OF FLEXIB... | $400 | $0 | May 7, 2019 |
| Feb 7, 2019 | 35387708M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35346382K ISSUED ON 7/16/18 AND TO FILE ... | $625 | $0 | May 7, 2019 |
| Jan 8, 2019 | 38267326J | RESOLVE | CLASS - 1 | 59L10,78B14,80E10. 59L10-BRAKE MONITORING SWITCH DEFECTIVE MISSING PARTS. 78B14-GOVERNOR TENSION WEIGHT NEEDS TO BE S... | $1,250 | $0 | May 7, 2019 |
| Jan 8, 2019 | 38267325H | RESOLVE | CLASS - 1 | CU5A10,CU59L10,78B14. 5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH. THIS IS A SAFETY DEVICE TO ENSURE PASSENGE... | $1,250 | $0 | May 7, 2019 |
| Dec 17, 2018 | 35393084Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35331054H ISSUED ON 11/18/17 AND TO F... | $1,250 | $0 | Feb 26, 2019 |
| Oct 15, 2018 | 35389192J | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#353310534 ISSUED ON 11/18/18 & TO FILE A C OF C PURSUAN... | $0 | $0 | Dec 11, 2018 |
| Aug 22, 2018 | 35388130J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/ VIOLATION #35331053H ISSUED ON 11/18/18 AND TO F... | $1,250 | $0 | Oct 9, 2018 |
| Jul 16, 2018 | 35346380R | RESOLVE | CLASS - 2 | FAILURE TO INSTALL GROUND FAULT CIRCUIT INTERRUPTER (GFCI) PROTECTION AS REQUIRED. OBSERVED IN COMMERCIAL KITCHEN NO ... | $1,250 | $0 | Sep 25, 2018 |
| Jul 16, 2018 | 35346382K | RESOLVE | CLASS - 2 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,MATERIALS,DEVICES,APPLIANCES OR WIRING IN USE.OBSERVED IN... | $800 | $0 | Sep 25, 2018 |
| Jul 16, 2018 | 35387700H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35272267X ISSUED ON 07/17/2017 & TO FILE A CERT OF COR... | $1,250 | $0 | Dec 11, 2018 |
| Jul 16, 2018 | 35387701J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35272265M ISSUED ON 07/17/2017 & TO FILE A CERT OF COR... | $1,250 | $0 | Dec 11, 2018 |
| Jul 16, 2018 | 35346381Z | RESOLVE | CLASS - 2 | LUMINAIRES & LAMPHOLDERS NOT INSTALLED IN AN APPROVED MANNER.OBSERVED IN UTILITY CLOSETS & THROUGHOUT HALLS & STAIRWA... | $250 | $0 | Sep 25, 2018 |
| Jul 16, 2018 | 35387702L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35272268H ISSUED ON 07/17/2017 & TO FILE A CERT OF COR... | $0 | $0 | Dec 11, 2018 |
| Jul 16, 2018 | 35346383M | RESOLVE | CLASS - 2 | EC 408.4 FAILURE TO PROVIDE CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION OBSERVED THROUGHOUT KITCHEN,BOILER ROOMS, (2)... | $400 | $0 | Sep 25, 2018 |
| Apr 4, 2018 | 32096580N | RESOLVE | CLASS - 2 | 5:B254-5A)CORRECT VIOLATING CONDITION & SUBMIT A CERT OF CORRECTION. | $0 | $0 | Jul 3, 2018 |
| Nov 18, 2017 | 35331056N | RESOLVE | CLASS - 1 | FAILURE TO HAVE NEW OR ALTERED PLUMBING SYSTEM TESTED.OBSERVED ON UPPERNORTH FLOOR OF NORTH BUILDINGS.TWO PRESSURE GA... | $1,000 | $0 | Aug 21, 2018 |