ECB violations
804 Cross Bay Boulevard, Queens • Block 15460 • Lot 0008
6 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Sep 23, 2013 | 35021841P | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEM. WATER GROUND NOT PROVIDED FOR 200AMP SERVICE SWITCH. REMEDY: PROVIDE GROUNDING. | $4,800 | $0 | Jan 14, 2014 |
| Sep 23, 2013 | 35021840N | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. 200 AMP SERVICE SWITCH. REMEDY: PROVIDE PROPER BONDING. | $3,000 | $0 | Jan 14, 2014 |
| Sep 23, 2013 | 35021842R | RESOLVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE W/SECTION. NO GROUND ROD PROVIDED FOR SERVICE 200 AMP.... | $4,800 | $0 | Jan 14, 2014 |
| Sep 23, 2013 | 35021843Z | RESOLVE | CLASS - 3 | FAILURE TO CLOSE UNUSED OPENINGS KNOCKOUTS IN OUTLET/PANEL BOX. REMEDY: CLOSE UNUSED OPENINGS. | $300 | $0 | Jan 14, 2014 |
| Sep 23, 2013 | 35021844K | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE ARC-FAULT CIRCUIT INTERRUPTER (AFCI) PROTECTION IN DWELLING UNITS. REMEDY: PROVIDE AFCI PROTECTION. | $2,400 | $0 | Jan 14, 2014 |
| Sep 23, 2013 | 35021845M | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS MATERIALS DEVICES APPLIANCES OR WIRING IN USE. NEED 2 POL... | $800 | $0 | Jan 14, 2014 |