ECB violations

701-711 Beach 9 Street, Queens • Block 15572 • Lot 0001

34 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Apr 8, 2025 37034829H ACTIVE CLASS - 2 FAILURE TO SUBMIT AN ACCEPTABLE REQUIRED CYCLE 9C REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WA... $2,500 $0 Jul 8, 2025
Apr 17, 2023 39083927P ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 Jun 27, 2023
Feb 8, 2023 39079374M ACTIVE CLASS - 1 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH DISABLED(CU). NO DLM INSTALLED ON THIS CONTROLLER AS MANDATED BY CODE ... $1,250 $0 Jul 18, 2023
Dec 22, 2022 39076514L ACTIVE CLASS - 2 SEAL ALL HOLES IN BOILER ROOM,MISSING VENT LIMINATOR FOR GAS REGULATOR,NEED LADDER AND PLATFORM BOILER OVER 8' (YEAR ... $312 $0 Mar 7, 2023
Oct 7, 2022 39071631H ACTIVE CLASS - 1 NO DOOR LOCK MONTORING INSTALLEDIN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX KE OF THE 2014 NYCBC. THIS IS A... $3,125 $0 Nov 22, 2022
Mar 7, 2022 39057588K ACTIVE CLASS - 1 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... $1,250 $0 Sep 13, 2022
Sep 12, 2019 38270811K RESOLVE CLASS - 2 2-X-10,5-E-1.8-V-1,100-X-10=2-X-10 PHONE INOPERABLE 5-E-1 SKIN ON DOOR GETTING STUCK WHEN DOOR OPENS 8-V-1 LOBBY FLOO... $0 $0 Nov 26, 2019
Sep 12, 2019 38270812M RESOLVE CLASS - 2 2-B-10,2-X-10,100-X-10,11-M-7,3-D-X=2-B-10 ALARM BELL 2-X-10 PHONE INOPERABLE 100-X-10 FAN INOPERABLE 11-M-7 FLOOR BU... $0 $0 Nov 26, 2019
Apr 19, 2017 38253038H RESOLVE CLASS - 2 2X10 REPAIR ALARM BELL AND COMMUNICATION. $500 $0 Feb 6, 2018
Feb 10, 2017 38254503Z RESOLVE CLASS - 2 02X10,41O02;70O02:(02X10)ALARM SYSTEM IS NOT OPERATIVE(41O02)CLEAN MACHINE ROOM(41O02)CLEAN MACHINE ROOM(70O02)CLEAN PIT $0 $0 Jun 13, 2017
May 11, 2016 38242600M RESOLVE CLASS - 2 01L10, 11T07, 02X10, 05J01,12Q03, 07M07, 45E01. 02/X/10- ALARM NOT WORKING. 05/J/01- CAR DOOR GAP. 45/E/01- GOVERNOR ... $0 $0 Jun 28, 2016
May 11, 2016 38242601Y RESOLVE CLASS - 2 59Y02, 52Y02, 07M07. 07/M/07- ZONE LOCK MISSING PRODUCT. $0 $0 Jun 28, 2016
Jan 11, 2016 38239154Y RESOLVE CLASS - 2 02L07,99U07. 02L07-ALARM BELL'S (STEP SW ALSO) $0 $0 Mar 1, 2016
Jan 11, 2016 38239153M RESOLVE CLASS - 2 39O02,56Y02,70O02,99U07 $0 $0 Mar 1, 2016
Aug 1, 2015 35132881L RESOLVE CLASS - 2 WORK DOES NOT CONFORM TO APPROVED CONSTRUCTION DOCUMENTS AND/OR APPROVED AMENDMENT.NOTE:OBSERVED SIDEWALK SHED ERECTE... $500 $0 Feb 9, 2016
Aug 1, 2015 35132882N RESOLVE CLASS - 2 SIGN.NOTE:OBSERVED SIDEWALK SHED ERECTED ALL AROUND THE BUILDING.SIDEWALK SHED INFORMATION PANEL NOT PROVIDED. REMEDY... $800 $0 Feb 11, 2016
Apr 10, 2015 35095537M RESOLVE CLASS - 2 FAILURE TO MAINTAIN FACADE AND APPURTENANCES.NOTED: AT REAR,THE CHIMNEY IS CRACKED BROKEN, AND WITH LOOSE MASONRY.SOM... $500 $0 Oct 20, 2015
Apr 10, 2015 35095536K RESOLVE CLASS - 1 FAILURE TO TAKE REQURIED ACTION TO SECURE PUBLIC SAFETY.UNSAFE FACADE.NOTED: AT THE SITE DURING THE FISP3: NOT OF UNS... $2,400 $0 Oct 20, 2015
Feb 14, 2014 38230332R RESOLVE CLASS - 2 02L10,39Y02,56Y13. 02L10-OUTSIDE COMMUNICATION NOT WORKING; 39Y02-EXCESS AMOUNT OF OIL ON CAR TOP; 56Y13-LEAK RUNNING... $500 $0 Jun 17, 2014
Jan 23, 2012 38220203L RESOLVE CLASS - 2 2L10,39Y2,72B7. 1) REPAIR OUTSIDE COMMUNICATION. 2) CLEAN OIL OFF TOP OF CAR. 3) PROVIDE PIT STOP SWITCH 16" ABOVE DO... $250 $0 Mar 13, 2012
Apr 14, 2010 38210250P RESOLVE CLASS - 2 67X10. 67X- IN CAR EMERGENCY PHONE INOPERATIVE. $200 $0 Nov 16, 2010
Jul 9, 2008 38189331N RESOLVE CLASS - 1 02X10, 100BB05, 71X10, 71Q07 02-X-10 ALARM BELL IN THE CAR DOESNT WRK ALSO EMERGENCY PHONE DOES NOT WRK PROPERLY-CEAS... $1,000 $0 Sep 2, 2008
Oct 13, 2006 38161939R RESOLVE Non-Hazardous 31-H-10/84-B-10/84-B-10-ELEVATOR GETS STUCK WHILE LEVELING TO THE FLR IN THE UP DIRECTION $350 $0 Nov 28, 2006
Aug 25, 2006 34550605K RESOLVE Non-Hazardous FAILURE TO SUBMIT A 5 ROUND TECHNICAL REPORT IN COMPLIANCE W/ CODE PROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALLS &... $1,750 $0 Oct 31, 2006
Jun 2, 2006 34550166H RESOLVE Non-Hazardous FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE W/CODE PROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALL... $1,750 $0 Jan 9, 2007
Mar 17, 2006 34549434R RESOLVE Non-Hazardous FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR ... $1,750 $0 Nov 28, 2006
Oct 28, 2005 34548661M RESOLVE Non-Hazardous FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE WITH CODE PROVISIONS: PERIODIC INSPECTION OF EXTERIOR ... $1,750 $0 Mar 6, 2007
Jan 14, 2005 34460955L RESOLVE Non-Hazardous FAILURE TO SUBMIT A FIFTH ROUND TECHNICAL REPORT IN COMPLIANCE W/ CODEPROVISIONS:PERIODIC INSPECTION OF EXTERIOR WALL... $1,750 $0 Jan 24, 2006
Jun 25, 2004 34459499Z RESOLVE Non-Hazardous FAILURE TO SUBMIT A FIFTH ROUND TECHINCAL REPORT:PERIODIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED ... $1,750 $0 Jun 28, 2005
Mar 26, 2004 34460192M RESOLVE Non-Hazardous FAILURE TO SUBMIT A FIFTHR ROUND TECHINCAL REPORT:PERIOIC INSPECTION OF EXTERIOR WALLS AND APPURTENANCES AS REQUIRED ... $700 $0 Jun 28, 2005
May 11, 1999 38086009N RESOLVE Non-Hazardous 2I11,57O2,35P7. $0 $0 Jun 29, 1999
May 11, 1999 38086008L RESOLVE Non-Hazardous 46F15,57O2,58O2,59O2,35P7,8V1. $0 $0 Jun 29, 1999
Mar 29, 1993 38032205R RESOLVE Non-Hazardous 03M,03Y,30Y,15T,35D,35Z,50Y,50Y,03-PROVIDE 2000LBS IN CAB CAPACITY PLATE 10-PROPERLY MARK 7FL BUTTON OF STATION PLATE... $0 $0 May 11, 1993
Mar 29, 1993 38032204P RESOLVE Non-Hazardous 50Y,50Y,35D,15T,03Y,30Y,35Z, 35-REPAIR WATER DAMAGE TO WALLS REMOVE LOOSE PLASTER ETC.FROM MOTOR ROOM WALLS & REPAIR ... $0 $0 May 11, 1993