ECB violations
20-30 Elk Drive, Queens • Block 15767 • Lot 0007
48 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 9, 2022 | 39059925L | RESOLVE | CLASS - 1 | THE ONLY ELEVATOR IN BUILDING(OR SECTION OF BUILDING) OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-... | $1,250 | $0 | Jun 21, 2022 |
| Apr 5, 2022 | 39059617J | RESOLVE | CLASS - 1 | WORK WITHOUT PERMIT. PART NUMBER LOBBY HOIST DOORS AND PART WAS INSTALLED WITHOUT PERMIT BEING OBTAINED AND APPLICATI... | $625 | $0 | Jul 12, 2022 |
| Mar 23, 2022 | 39058631L | RESOLVE | CLASS - 2 | 1ST FLOOR NOT OPERATIONAL , ONLY SERVES 2ND TO 7TH FLOORS , RESTORE TO SERVICE ALL FLOORS | $0 | $0 | May 10, 2022 |
| Feb 5, 2021 | 39035906J | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Mar 23, 2021 |
| Nov 2, 2019 | 38268736R | RESOLVE | CLASS - 2 | 67-L-10,2-L-10,8-O-2,70-O-2=67 I 10 REPAIR 2 WAY COMMINCATION 70 O 2 CLEAN PIT 8 O 2 CLEAN SELLS AND SLADDERS 2 L 10 ... | $0 | $0 | Jan 14, 2020 |
| Oct 15, 2018 | 37012931R | RESOLVE | CLASS - 2 | FAILURE TO SUBMIT A REQUIRED CYCLE 8B REPORT OF CRITICAL EXAMINATION DOCUMENTING CONDITION OF EXTERIOR WALLS & APPURT... | $1,250 | $0 | May 14, 2019 |
| Sep 13, 2018 | 35308476Y | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. NOTED: AT TIME OF INSPECTION OF A 6 STORY RESIDENTIAL BLDG OBSERVED SUSPENDED SCAFFOLDING SET UP A... | $0 | $0 | Oct 30, 2018 |
| May 29, 2018 | 38263434Z | RESOLVE | CLASS - 1 | CU-5A10,57BB11,59M7. 5A10-DOOR ZONE RESTRICTOR HAS BEEN TAMPERED WITHDISABLED AND RENDERED INOPERATIVE. THIS IS A SAF... | $1,250 | $0 | Jul 17, 2018 |
| Apr 2, 2018 | 35313032J | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY W/ AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT ... | $0 | $0 | May 22, 2018 |
| Jan 10, 2018 | 35274595Y | RESOLVE | CLASS - 1 | UNLAWFUL ACT.FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.RECORDS INDICATE NO APPLICATION WAS MADE TO CORRECT ... | $0 | $0 | May 18, 2018 |
| Nov 21, 2017 | 35301832J | RESOLVE | CLASS - 2 | WORK WITHOUT PERMIT. NOTED: RENOVATION OF APT. 1A, NO FILING IN DOB RECORDS. STOP ALL WORK SWO ISSUED. WORK APPROX. 2... | $800 | $0 | Feb 13, 2018 |
| Nov 21, 2017 | 35301831H | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE APPROVED/ACCEPTED PLANS AT JOBSITE. AT TIME OF INSPECTION. NOTED: APPROVED PLANS FOR APP #44044044... | $0 | $0 | Jan 9, 2018 |
| Oct 24, 2017 | 35285084X | RESOLVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT APPARATUS, MATERIALS DEVICES APPLIANCES OR WIRING IN USE. THE ENTIR... | $1,000 | $0 | Dec 12, 2017 |
| Aug 2, 2017 | 38255866M | RESOLVE | CLASS - 1 | 97X10 ONLY ELEVATOR IN BLDG OUT OF SERVICE CREATING A HAZARDOUS CONDITION AS PER 1RCNY 11-02. RESTORE TO SERVICE IMME... | $1,000 | $0 | Feb 20, 2018 |
| Apr 4, 2017 | 38254140Z | RESOLVE | CLASS - 2 | 10H11,16J10,56Y2,56Y13,68M7,71M7. 8V1-CAR FLOOR TO LANDING SILL NOT LEVEL ADJUST; 10H11-CAR DOOR GIBS WORN REPLACE; 1... | $0 | $0 | May 23, 2017 |
| Jan 28, 2017 | 38252740N | RESOLVE | CLASS - 2 | 41W07,32H11,09I11,03#04,56Y13,58B07. 41W07-MACHINE ROOM DOOR NOT LOCKABLE. 32H11-WORN GUIDESHOES; 09I11-DAMAGED CAR F... | $2,500 | $0 | May 30, 2017 |
| Oct 6, 2016 | 35201696X | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT DEVICES APPARATUS APPLIANCES MATERIALS OR WIRING IN USE.FLEXIBLE CO... | $400 | $0 | Jan 10, 2017 |
| Oct 6, 2016 | 35201694M | RESOLVE | CLASS - 2 | UNAPPROVED UNSAFE UNSUITABLE ELECTRICAL EQUIPMENT DEVICES APPARATUS APPLIANCES MATERIALS OR WIRING IN USE.WIRING OVER... | $400 | $0 | Jan 10, 2017 |
| Oct 6, 2016 | 35201693K | RESOLVE | CLASS - 2 | ELECTRICAL WRK W/OUT A PERMIT.OBSERVED AT 8AM OUTSIDE LIGHTS,HIGH HAT FIXTURES,WALL SCONS FIXTURES,IN LOBBY,INCANDESC... | $0 | $0 | Jan 10, 2017 |
| Oct 6, 2016 | 35182347R | RESOLVE | CLASS - 2 | SEC. 504 MISC VIOLATIONS. AT TIME OF INSPECTION 11AM I OBSERVED DRYER EXHAUST INSTALLED CONTRARY TO CODE. REMEDY: COM... | $800 | $0 | Jan 10, 2017 |
| Oct 6, 2016 | 35124413K | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY.NOTED: AT CELLAR LEVEL OF BUILDING THERE IS A LAUN... | $0 | $0 | Jan 10, 2017 |
| Oct 6, 2016 | 35201695Y | RESOLVE | CLASS - 2 | SERVICE ROOM SPACE SHALL NOT BE USED AS STORAGE/RUBBISH.ELECTRICAL SERVICE ROOM STACK WITH BOXES,CONTAINERS,PLATIC BA... | $0 | $0 | Jan 10, 2017 |
| Oct 6, 2016 | 35182346P | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. AT TIME OF INSPECTION 11AM I OBSERVED A LAUNDRY ROOM W/MULTIPLE WASHERS & GAS FIRED DRYERS. COMPLE... | $0 | $0 | Feb 1, 2017 |
| Oct 6, 2016 | 35182348Z | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER RE: PROHIBITED MATERIALS. AT TIME OF INSPECTION 11AM I OBSERVED RES... | $1,000 | $0 | Jan 10, 2017 |
| Jan 19, 2016 | 35048337X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN NOV #35090740P ISSUED ON 3/21/14 & TO FILE A C OF C PURSUANT TO 28-... | $0 | $0 | Mar 29, 2016 |
| Dec 23, 2015 | 38239720J | RESOLVE | CLASS - 2 | 100M07,16F01,39Y02,16T07. 100M07-HANDRAILS MISSING IN CAR PROVIDE; 16F01-HOISTWAY DOOR 3RD FLR LOST MOTION SLAMMING A... | $0 | $0 | Feb 9, 2016 |
| Mar 3, 2015 | 38231562R | RESOLVE | CLASS - 2 | 02L10,15M07,16L01,29M07,39O02,41I10,56Y13,69B11,70O02,97O02. 02LM-REPAIR OUTSIDE COMMUNICATING; 15M07-PROVIDE CERTIFI... | $500 | $0 | Dec 1, 2015 |
| Feb 6, 2015 | 38231559X | RESOLVE | CLASS - 1 | 97X10-RESTORE ELEVATOR TO SERVICE SO A COMPLETE INSP CAN BE MADE BY THIS DEPT. | $5,000 | $0 | Mar 24, 2015 |
| Mar 21, 2014 | 35090740P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALL OR APPURTENANCES: TERRACES HAVE SPALLINGCONCRETE SEALANT ON UNDERSIDE OF CEILINGS IN VA... | $1,000 | $0 | Jul 22, 2014 |
| Mar 21, 2011 | 38215687K | RESOLVE | CLASS - 2 | 67X10 16D06. 67X10-IN CAR EMERGENCY PHONE INOPERATIVE. 16D06-INTERLOCK KEEPERS ON DOORS @ 1ST & 7TH FLOOR UNSECURED. | $0 | $0 | May 10, 2011 |
| Dec 20, 2010 | 34890953H | RESOLVE | CLASS - 2 | WORK W/O PERMIT.WORK NOTED:@ APT 4M ERECTED FULL HEIGHT PARTITIONS,SUBDIVIDED L-ROOM & CREATED ADDITIONAL ROOM.REM:OB... | $0 | $0 | Jul 12, 2011 |
| Dec 20, 2010 | 34890956N | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.NOTED:@ 5FLR APT 5A PASSAGEWAY IS BLOCKED BY A DOOR(W/ KEY LOCKING DE... | $0 | $0 | Jul 12, 2011 |
| Dec 20, 2010 | 34890955L | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY.NOTED:@ 4 FLR APT 4M PASSAGEWAY IS BLOCKED BY A DOOR(W/ KEY LOCKING D... | $0 | $0 | Jul 12, 2011 |
| Dec 20, 2010 | 34890954J | RESOLVE | CLASS - 2 | WORK W/O PERMIT.WORK NOTED:@ APT5A ERECTED FULL HEIGHT PARTITIONS,SUBDIVIDED L-ROOM & CREATED ADDITIONAL ROOM.REM:OBT... | $0 | $0 | Jul 12, 2011 |
| Oct 27, 2010 | 38212488Y | RESOLVE | CLASS - 2 | 32H01,39O02,40O02,56Y13,70O02,77B11,05J01.(05J01)PROVIDE STRIKE BUMPERS FOR THE CAR DOOR.(39O02)OIL ON TOP OF CAR.(40... | $0 | $0 | Dec 21, 2010 |
| Sep 8, 2009 | 38205004N | RESOLVE | CLASS - 2 | 03O02.16L10.98BB5.99BB5.56Y13.16H1 DOOR CLOSER RICKSON ON 6 & 4 FL 29J01 DOOR TIMER TOO SLOW RECURRING CONDITION # 98... | $2,500 | $0 | Nov 10, 2009 |
| Mar 11, 2009 | 38199094H | RESOLVE | CLASS - 2 | 16L10.39O02.40O02.70O02.98BB05.100O02.100O02 CLEAN CAR DOOR SADDLE 16L10 DOOR CHECKS ON 2ND & 5TH FLS | $2,500 | $0 | May 5, 2009 |
| Nov 7, 2008 | 38190294L | RESOLVE | CLASS - 2 | 03M07.39O02.40O02.70O02.98BB05.03M07 REPLACE HANDRAIL 98BB05 FILE & PERFORM 5YR TEST | $500 | $0 | Dec 30, 2008 |
| Feb 14, 2006 | 38157530J | RESOLVE | Non-Hazardous | 83L10 83- REPAIR TO SERVICE. | $0 | $0 | Apr 4, 2006 |
| Nov 1, 2005 | 38156024M | RESOLVE | Non-Hazardous | 21J01/02L10/83L10 21-ADJUST 7TH FLOOR LOCK, 02- EMERGENCY PHONE, 83- CAR RELEVELS. | $0 | $0 | Dec 20, 2005 |
| Oct 12, 2005 | 38154586P | RESOLVE | Non-Hazardous | 83X10. (83)RESTORE TO SERVICE SO A FULL INSPECTION CAN BE MADE. | $0 | $0 | Nov 29, 2005 |
| Jul 2, 1996 | 38057053H | RESOLVE | Non-Hazardous | 75B,15A,18I,25Q,50Y,08J,74#.75-PERFORM 5YR TEST,TAG DEVICE AND FILE ELEV 3 FORM WITH THIS DEPT 74-REPAIR 7TH FLOOR SO... | $1,000 | $0 | Sep 10, 1996 |
| Jul 8, 1994 | 38043086R | RESOLVE | Non-Hazardous | 35P,570, | $0 | $0 | Sep 13, 1994 |
| May 3, 1994 | 38040939X | RESOLVE | Hazardous | 15L,28H,50Y,50O,03O,57O,37G, 15L- 7TH FLOOR (CEASE USE TILL RETURNED TO PROPER WORKING ORDER. 030- CLEAN OIL- TOP OF CAR | $500 | $0 | Jul 5, 1994 |
| Aug 30, 1993 | 38036049M | RESOLVE | Non-Hazardous | 74I,17I,28H,14M,57O,35P,03M,62O,15L. 74 CAR SADDLE. 17 CAR DOOR. 03 CAPCITY PLATE. 62 TOP OF CAR. 35 UNABLE TO GAIN A... | $100 | $0 | Nov 16, 1993 |
| Nov 17, 1992 | 38028372M | RESOLVE | Non-Hazardous | 57O,03O,35P,74I,17I 74 CAR SADDLE. 17 CAR DOOR. | $0 | $0 | May 31, 1994 |
| Mar 11, 1991 | 38008416R | RESOLVE | Non-Hazardous | 10X,28I,31Q,36W,57O,74O. (10) 7TH FLOOR. (28) TOP OF CAR. (31) PROP-ERLY ENCLOSE AT MAIN FLOOR. (36) PROVIDE LOCK. (7... | $150 | $0 | Jul 2, 1991 |
| Oct 26, 1987 | 34005253M | RESOLVE | Non-Hazardous | FAILURE TO FILE A REPORT OF COMPLIANCE WITH LOCAL LAW 16/84 CERTIFYING TO THE INSTALLATION OF REQUIRED FIRE PROTECTIO... | $150 | $0 | Oct 17, 1989 |