ECB violations
Grassmere Playground, Queens • Block 15772 • Lot 0031
76 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Mar 31, 2026 | 35727385P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ILLUMINATION FOR EXITS, EXIT DISCHARGES AND PUBLIC CORRIDORS P... | $1,250 | $0 | Apr 20, 2026 |
| Mar 31, 2026 | 35727384N | ACTIVE | CLASS - 2 | REISSUE ECB #35692063P. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: SIMPLE DOORS NOT OPERATING PROPE... | $3,125 | $0 | Apr 20, 2026 |
| Mar 31, 2026 | 35727383L | ACTIVE | CLASS - 2 | REISSUE ECB #35692064R. EXIT DOOR NOT SELF-CLOSING. NOTED: EXIT DOORS #2, 3, 13 NOT OPERATING PROPERLY. REMEDY: REPAI... | $1,562 | $0 | Apr 20, 2026 |
| Mar 31, 2026 | 35727382J | ACTIVE | CLASS - 2 | REISSUE ECB #35692066K. FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANTMANNER. NOTED: AT EXIT #7 AND EXIT #9 AROUND DO... | $3,125 | $0 | Apr 20, 2026 |
| Nov 25, 2025 | 39168249H | ACTIVE | CLASS - 2 | IN CAR EMERGENCY STOP SWITCH DEFECTIVE . NEED ALOT OF FORCE TO ACTIVATE , REPARE / INSIDE COMM INSUFFECIENT , OPERATO... | $625 | $0 | Dec 23, 2025 |
| Mar 27, 2025 | 35692065Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING MANNER. NOTED AT EXIT 8 DOOR SADDLE IS MISSING TRIP HAZARD AND BASE OF FRAMES RUSTED. RE... | $1,250 | $0 | Apr 23, 2025 |
| Mar 27, 2025 | 35692066K | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT EXIT 9AROUND DOORWAY CRACKS AND SPALLING AT INTERIOR ... | $1,250 | $0 | Apr 23, 2025 |
| Mar 27, 2025 | 35692064R | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING. NOTED AT 3 FLOOR SMOKE STAIR B AND C, 2 FLOORS(5) B, C, 1F(5) C. D. AND EXITS 2, 3, 7, 8,... | $625 | $0 | Apr 23, 2025 |
| Mar 27, 2025 | 35692063P | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT 2 FLOOR CORRIDOR BY 202, 1FL. GYM ENTRANCE AND STAGE ... | $1,250 | $0 | Apr 23, 2025 |
| Mar 27, 2025 | 35692067M | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED AT CELLARLEVEL SNOWBLOWER INSIDE BOILER AREA. REMEDY: RE... | $1,250 | $0 | Apr 23, 2025 |
| Jul 3, 2024 | 39118399H | RESOLVE | CLASS - 1 | DLM NOT WORKING TAMPERED WITH DISABLED(CU). | $1,250 | $0 | Jul 27, 2024 |
| Apr 19, 2024 | 35678621J | RESOLVE | CLASS - 2 | REISSUE#35636330Y AT EXIT DOORS 5 & 6 FRAMES ARE DETERIORATED WITH HOLES & RUST.REM:REPAIR AND/REPLACE. | $625 | $0 | Jul 3, 2024 |
| Apr 6, 2023 | 35671758Z | RESOLVE | CLASS - 2 | REISSUE #35636330Y(4/13/22) FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:AT EXIT 5 & 6 EXIT DOORS JAMS & FRA... | $1,562 | $0 | Jul 11, 2023 |
| Apr 13, 2022 | 35636330Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NOTED THE DOOR JOINTS AT EXITS 5 AND 6 ARE DETERIORATING,HAVE H... | $625 | $0 | Jul 26, 2022 |
| Apr 13, 2022 | 35636328P | RESOLVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING.NOTED AT THE 3RD FLOOR SMOKE BY 302,2ND FLOOR SMOKE BY 202,EXTERIOR DOOR AT EXIT 12,SMOKE ... | $625 | $0 | Jul 26, 2022 |
| Apr 13, 2022 | 35636329R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:ILLUMINATION FOREXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $625 | $0 | Jul 26, 2022 |
| May 26, 2021 | 39042437L | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $1,250 | $0 | Jun 10, 2021 |
| Apr 22, 2019 | 35415061X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER:LACK OF EMERGENCY LIGHTING FOR EXITS,EXIT DISCHARGES AND PUBLIC... | $0 | $0 | Jul 16, 2019 |
| Apr 22, 2019 | 35415060Y | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED: AT 2ND FL. ONE SMOKE DOOR ADJACENT TO ROOM 208A JAM AND... | $0 | $0 | Jul 16, 2019 |
| Apr 9, 2019 | 39002030N | RESOLVE | CLASS - 2 | FOUND FEDERAL #03 BOILER WITH VIOLATING CONDITIONS. BOILER FEED WATER LINE LEAKING WATER. RESOLVE VIOLATING CONDITION... | $0 | $0 | Apr 11, 2019 |
| Apr 9, 2019 | 39002029X | RESOLVE | CLASS - 2 | FOUND FITZGIBBONS #02 BOILER WITH VIOLATING CONDITIONS. BOILER FEED WATER LINE LEAKING WATER. RESOLVE VIOLATING CONDI... | $0 | $0 | Apr 11, 2019 |
| Apr 9, 2019 | 39002028Y | RESOLVE | CLASS - 2 | FOUND FITZGIBBONS #01 BOILER WITH VIOLATING CONDITIONS. SAFETY VALVES LEAKING. RESOLVE VIOLATING CONDITIONS AND SUBMI... | $0 | $0 | Apr 11, 2019 |
| May 31, 2018 | 35329338Z | RESOLVE | CLASS - 2 | REISSUE: 35271322P FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER NOTED: THERE ARE 3 ACTIVE SECURITY ROLL DOWN GAT... | $0 | $0 | Sep 11, 2018 |
| May 31, 2018 | 35329339K | RESOLVE | CLASS - 2 | REISSUE: 35271323R FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES NOTED: AT 3RD FLOOR, ROOM 335 WINDOW WALL HAVE C... | $0 | $0 | Sep 11, 2018 |
| Jul 19, 2017 | 35271323R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S)OR APPURTENANCES.NOTED:AT 3RD FKIIRMRN 335 WINDOW WALL HAVE CRACKS.REM:MAKE NECESSARY... | $0 | $0 | Oct 3, 2017 |
| Oct 12, 2016 | 35214470X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. NOTED: WATER DAMAGE TO CEILIGN AND WALLS DUE TO WATER PENETRAT... | $0 | $0 | Jan 10, 2017 |
| Oct 12, 2016 | 35214471H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. NOTED: AT CELLAR LEVEL, ELE... | $0 | $0 | Jan 10, 2017 |
| Sep 29, 2015 | 35148015L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER.USE OF PROHIBITED HARDWARE PER BC 1008.1-8;27-371(J)NOTED:EXIT DOOR... | $0 | $0 | Jan 5, 2016 |
| Sep 29, 2015 | 35148014J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.NOTED:@ CELLAR LEVEL@ ELECTRICAL RM EXTENION CORDS,TOOLS,TABLES,CHA... | $0 | $0 | Jan 5, 2016 |
| Sep 29, 2015 | 35148016N | RESOLVE | CLASS - 2 | REISSUE #35101101J.FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER.NOTED:VERTICAL CRACKING OF PLASTER @ WINDOW POCK... | $0 | $0 | Jan 5, 2016 |
| Jul 25, 2014 | 35101101J | RESOLVE | CLASS - 2 | VERTICAL CRACKING OF PLASTER @ WINDOW POCKETS IN ROOMS 336,337,338.REM:MAINTAIN BLDG. | $0 | $0 | Sep 30, 2014 |
| Jul 25, 2014 | 35101100H | RESOLVE | CLASS - 2 | REISSUE 35012333Y.@ 1FL EXIT 8,VESTIBULE DOOR REMOVED FROM OPENING DUETO DEFECTIVE FL CHECK(CLOSER).DOOR WAS UNABLE T... | $0 | $0 | Sep 30, 2014 |
| Apr 16, 2013 | 35012333Y | RESOLVE | CLASS - 2 | REISSUE 34987623X DEFECTIVE DOORS AT 3 FL STAIR C 2 FL CORRIDOR DOORS 2 SETS, STAIR B AND EXIT 8 VESTIBULE DOOR (CENT... | $0 | $0 | Jun 18, 2013 |
| Apr 16, 2013 | 35012334X | RESOLVE | CLASS - 2 | CORRIDOR PARTIAL OBSTRUCTION AT 3 FL FRONT OF 335 EXCESSIVE BOXES STORED. RMDY: REMOVE OBSTRUCTION. | $0 | $0 | Jun 18, 2013 |
| Jul 26, 2012 | 34987623X | RESOLVE | CLASS - 2 | DEFECTIVE DOORS NOTED AT 3FL STAIR C,& EXIT #8 VESTIBULE DOOR. REMEDY:REPAIR/REPLACE DOOR. | $0 | $0 | Sep 18, 2012 |
| Jun 28, 2011 | 34918114Z | RESOLVE | CLASS - 3 | VERTICAL CRACKS ON INTERIOR WALLS AROUND WINDOWS THROUGHOUT 3 FLOOR. REMEDY: PROVIDE ENGINEERS REPORT ON CAUSE & REMEDY. | $0 | $0 | Sep 13, 2011 |
| Jun 18, 2009 | 34792076X | RESOLVE | CLASS - 2 | SPALLING PLASTER CEILING ROOM 313 & ALONG RIGHT SIDE WINDOW 318 PLASTER CRACKED FLOOR TO CEILING IN CORNER. REMEDY:RE... | $0 | $0 | Sep 15, 2009 |
| Jun 18, 2009 | 34792079L | RESOLVE | CLASS - 2 | FIRE STOPPING REQUIRED IN ELECTRICAL ROOM AROUND SEVERAL WALL PENETRATIONS. REMEDY:FIRE STOP WALL. | $0 | $0 | Sep 15, 2009 |
| Jun 18, 2009 | 34792078J | RESOLVE | CLASS - 2 | 3 FLOOR CENTER CORRIDOR ( ) DOOR INOPERABLE, PARTIALLY SWINGS IN ONE DIRECTION. REMEDY:REPAIR/REPLACE DOOR AND/OR HAR... | $0 | $0 | Sep 15, 2009 |
| Jun 18, 2009 | 34792077H | RESOLVE | CLASS - 2 | REISSUE 34724171J. BULGING BRICK BENEATH WALL LIGHT AT REAR OF AUDITIORIUM STAGE W/CORNER VERTICAL CRACKS APP 20' HIG... | $0 | $0 | Sep 15, 2009 |
| Jun 18, 2009 | 34792075Y | RESOLVE | CLASS - 2 | WINDOW GRATE ALONG BRIAR PLACE, RUSTED & PITTED, WALL SUPPORT DETERIORATED. REMEDY: REPAIR - MAINTAIN GRATING. | $0 | $0 | Sep 15, 2009 |
| Nov 14, 2008 | 34724169K | RESOLVE | CLASS - 2 | WATER PENETRATION THRU CEILING INTO RM # 313 REMEDY:STOP WATER PENETRATION & MAKE ALL NECESSARY REPAIRS | $0 | $0 | Jan 6, 2009 |
| Nov 14, 2008 | 34724171J | RESOLVE | CLASS - 2 | BULGING BRICK WALL AT AUDITORIUM BACK STAGE REISSUE 34586071J PARTIAL REMEDY:REPAIR/REPLACE MASONARY | $0 | $0 | Jan 6, 2009 |
| Nov 14, 2008 | 34724173N | RESOLVE | CLASS - 2 | STWY 'C' IN BULKHEAD WALLS SPALLING AROUND WINDOW DUE TO WATER PENETRATION IN BRICK WALL REMEDY:STOP WATER PENETRATION | $0 | $0 | Jan 6, 2009 |
| Nov 14, 2008 | 34724172L | RESOLVE | CLASS - 2 | CRACKED COPING STONE AT TOP SIDE @ S/W CORNER ALSO BLOCK UNDERNEATH COPING @ WESTSIDE ABOVE RM # 313 HAS 12' X 4 ' SE... | $0 | $0 | Jan 6, 2009 |
| Nov 14, 2008 | 34724170H | RESOLVE | CLASS - 2 | WATER PENETRATION THRU EXTERIOR BRICK WALL INTO AUDITORIUM BACK STAGE WALL STAIR B & C BULKHEAD REMEDY:STOP WATER PEN... | $0 | $0 | Jan 6, 2009 |
| Jul 19, 2007 | 34586073N | RESOLVE | Hazardous | NO PANIC HARDWARE PROVIDED AT CAFETERIA (OCCUPANCY 440) EXIT DOOR FROM HALLWAY TO EXTERIOR EXIT.REMEDY:PROVIDE PANIC ... | $0 | $0 | Sep 11, 2007 |
| Jul 19, 2007 | 34586071J | RESOLVE | Hazardous | BULGING BRICK WALL AT AUDITORIUM BACK STAGE ALSO VERTICAL CRACKS IN GLAZED BLOCK IN GYM & 3RD FLOOR CORRIDOR WINDOW S... | $0 | $0 | Sep 11, 2007 |
| Jul 19, 2007 | 34586069K | RESOLVE | Hazardous | WATER PENETRATION THROUGH CEILING INTO ROOM #313.REMEDY:STOP WATER PENETRATION & MAKE ALL NECESSARY REPAIRS. | $0 | $0 | Sep 11, 2007 |
| Jul 19, 2007 | 34586072L | RESOLVE | Hazardous | CRACKED COPING STONE AT TOP SIDE @ S/W CORNER.ALSO BLOCK UNDERNEATH COPING @ WEST SIDE ABOVE RM #313 HAS 12"X 4" SECT... | $0 | $0 | Sep 11, 2007 |