ECB violations
Rockaway Freeway, Queens • Block 15908 • Lot 0007
58 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 2, 2026 | 39183050X | ACTIVE | CLASS - 1 | FAILURE TO PROTECT CONDUCTOR(S) AGAINST OVERCURRENT PER EC. OBSERVED IN THE ELEVATOR MACHINE RM THAT THE OVERCURRENT ... | $4,800 | $4,800 | Oct 13, 2026 |
| Apr 2, 2026 | 39183049Z | ACTIVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... | $1,600 | $1,600 | Oct 13, 2026 |
| Apr 2, 2026 | 39183048R | ACTIVE | CLASS - 1 | FAILURE TO INSTALL GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH SECTION. OBSERVED IN THE MAIN ELECTRICAL RM NO IN... | $4,800 | $4,800 | Oct 13, 2026 |
| Apr 2, 2026 | 39183051H | RESOLVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED ON THE GROUND FLOOR THE INSTALLATION ONE HUNG ELECTRIC HEATER. ALSO ONE FE... | $2,500 | $2,500 | Oct 13, 2026 |
| Feb 5, 2026 | 39176239Y | ACTIVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER TO FILE A CERTIFICATE OF CORRECTION WITH THE DEPT OF BUILDINGS FOR SU... | $6,250 | $6,250 | Apr 14, 2026 |
| Dec 19, 2025 | 39171027J | RESOLVE | CLASS - 3 | HEAT TIMER BOILER CONTROL IS DEFECTIVEÝHEAT TIMER SERVICE TECH REQUIRED¨+APT#620 WEATHER STRIP@APT DOOR+@ROOF ACCESS ... | $500 | $0 | Apr 14, 2026 |
| Mar 26, 2025 | 39142831H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. OBSERVED NON FIRE RATED DOOR AT 1 FLOOR LEVEL NEAR STAFF LOUNG... | $2,500 | $2,500 | Jul 15, 2025 |
| Mar 26, 2024 | 39109897X | RESOLVE | CLASS - 1 | GAS LEAK FOUND ON 2 INCH GAS VALVE AS WELL AS 2 INCH GAS PIPING IN THE GAS METER ROOM LOCATED ON THE MAIN FLOOR. AS P... | $1,250 | $0 | Sep 24, 2024 |
| Oct 24, 2022 | 35657276P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.OBSERVED IN KITCHEN ON MAIN FLOOR GAS PIPING SHUT NOT LOCKED OR... | $312 | $0 | Mar 28, 2023 |
| Oct 24, 2022 | 39072582P | RESOLVE | CLASS - 2 | I OBSERVED AT THE REAR OF THE DRYERS ON THE FIRST FLOOR NEXT TO THE SPRINKLER CONTROL ROOM. CABLE ASSEMBLIES(BX) UNSU... | $0 | $0 | Jan 10, 2023 |
| Oct 24, 2022 | 39072572L | RESOLVE | CLASS - 2 | AT 6TH FL, SMOKE DOOR NEAR 616/628 RMS, AT 5TH FL . SMOKE DOOR NEAR 528 RM, AT 3RD FL SMOKE DOOR NEAR 306/314 RMS, AT... | $0 | $0 | Oct 17, 2023 |
| Oct 24, 2022 | 39072571J | RESOLVE | CLASS - 2 | AT GROUND LEVEL, MAIN ENTRANCE DOORS, LIBRARY RM, KITCHEN EXIT DOOR AND CORRIDOR SMOKE DOORS, ILLEGAL KITCHEN STOPS A... | $0 | $0 | Dec 13, 2022 |
| Oct 24, 2022 | 39072583R | RESOLVE | CLASS - 2 | I OBSERVED IN THE LOBBY ENTRANCE AND THE REAR CONFERENCE ROOM THE INSTALLATION OF FLEXIBLE CORDS IN A RACEWAY THIS IS... | $0 | $0 | Dec 13, 2022 |
| Oct 24, 2022 | 39072580L | RESOLVE | CLASS - 1 | I OBSERVED ON THE ROOF A CONDUIT EXITING THE LOWER WALL BROKEN WITH EXPOSED CONDUCTORS, ALSO NOTED THE JUNCTION BOXES... | $400 | $0 | Jun 27, 2023 |
| Oct 24, 2022 | 39072591R | RESOLVE | CLASS - 1 | ROPER GRIPPER DO NOT CLOSE AFTER OPENING UP THE GOVERNOR ELECTRICAL SWITCH. THIS FEATURE WORKS ON THE OTHER CONTROLLE... | $1,250 | $0 | Apr 18, 2023 |
| Oct 24, 2022 | 39072579Y | RESOLVE | CLASS - 2 | I OBSERVED IN THE ELEVATOR MACHINE A GFCI RECEPTACLE NOT OPERATING AS DESIGNED WHEN TESTED THE GFCI DID NOT TRIP AS R... | $1,200 | $0 | Dec 13, 2022 |
| Oct 24, 2022 | 39072590P | RESOLVE | CLASS - 2 | BRAKE MAINTENANCE TAG EXPIRED ON 4/22/20. IN CAR PHONE NOT WORKING. | $0 | $0 | Dec 13, 2022 |
| Oct 24, 2022 | 39072581N | RESOLVE | CLASS - 1 | I OBSERVED IN THE KITCHEN THE IMPROPER TERMINATION OF ENERGIZED ELECTRICAL WIRES EXTENDING FROM A FLOOR MOUNTED JUNCT... | $1,600 | $0 | Jun 27, 2023 |
| Oct 1, 2021 | 39048557N | RESOLVE | CLASS - 2 | COMBUSTION AIR FANS TO BE INTERLOCKED WITH BOILER & MISSING SWITCH AT 2ND DOOR FOR BOILER.CORRECT VIOLATION & SEND IN... | $0 | $0 | Nov 16, 2021 |
| Oct 1, 2021 | 39048558P | RESOLVE | CLASS - 2 | COMBUSTION AIR FAN TO BE INTERLOCKED WITH BOILER ,REMOTE SWITCH REQUIRED AT 2ND DOOR TO BOILER ROOM,CORRECT VIOLATION... | $0 | $0 | Nov 16, 2021 |
| Oct 1, 2021 | 39048559R | RESOLVE | CLASS - 2 | COMBUSTION AIR FAN TO BE INTERLOCKED WITH WATER HEATER,FAN BY WTR HTR CANNOT RUN CONTINOUS NEED REMOTE SWITCH AT 2ND ... | $0 | $0 | Nov 16, 2021 |
| Sep 24, 2021 | 39048142L | RESOLVE | CLASS - 2 | THREE IMPROPER GLASS FUSE ON THE CONTROLLER. WIRES HANGING OFF THE TERMINAL NOT CAP REPLACE WIRE ON THE TERMINAL. | $0 | $0 | Nov 9, 2021 |
| Sep 24, 2021 | 39048143N | RESOLVE | CLASS - 2 | ONE IMPROPER GLASS FUSE ON THE CONTROLLER. WIRES HANDING OFF THE TERMINAL NOT CAP REPLACE WIRE ON THE TERMINAL. | $0 | $0 | Nov 9, 2021 |
| Aug 19, 2021 | 39046257M | RESOLVE | CLASS - 2 | OBSERVED: FIRE PROOF SELF-CLOSING AT CORRIDOR FROM 6 FL TO 1 FLOOR , NOT SELF-CLOSING PROPERLY DUE OVERLAPPING DOOR L... | $0 | $0 | Oct 5, 2021 |
| Feb 8, 2021 | 39035972H | RESOLVE | CLASS - 1 | NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 OF THE 2014 NYCBC. THIS IS... | $0 | $0 | Apr 27, 2021 |
| Aug 15, 2018 | 32097374R | RESOLVE | CLASS - 2 | B254,50A,50B. PEERLESS FH 2394 BOILER: 50A-FRESH AIR FANS TO BE INTER LOCKED WITH BOILER; 50B-CAP OR PLUG OPEN PIPING... | $625 | $0 | Oct 2, 2018 |
| Aug 15, 2018 | 32097526R | RESOLVE | CLASS - 2 | B254,50A,50B. AO SMITH GM08SVWP BOILER: 50A-FRESH AIR FANS TO BE INTERLOCKED WITH BOILER; 50B-CAP OR PLUG OPEN PIPING... | $625 | $0 | Oct 2, 2018 |
| Aug 15, 2018 | 32097525P | RESOLVE | CLASS - 2 | B254,50A,50B. PEERLESS RH 1995 BOILER: 50A-FRESH AIR FANS TO BE INTERLOCKED WITH BOILER; 50B-CAP OR PLUG OPEN PIPING.... | $625 | $0 | Oct 2, 2018 |
| Apr 20, 2018 | 32096871N | RESOLVE | CLASS - 2 | 50A)MANUFACTURERS RATING TAG FOR MODULER BOILER MISSING. B)LIGHTS IN BOILER ROOM NOT WORKING. CORRECT ALL VIOLATING C... | $312 | $0 | Sep 4, 2018 |
| Apr 20, 2018 | 32096873R | RESOLVE | CLASS - 2 | CORRODED FLUE PIPE, DEFECTIVE RELIEF VALVE, MISSING MANUAL RESET AQUASTAT. CORRECT ALL VIOLATING CONDITIONS AND SUBMI... | $625 | $0 | Jul 17, 2018 |
| Apr 20, 2018 | 32096872P | RESOLVE | CLASS - 2 | 50A)MANUFACTURERS RATING TAG OR MODULAR BOILER MISSING. CORRECT ALL VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF ... | $312 | $0 | Sep 4, 2018 |
| Jan 25, 2018 | 35298034K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING WALLS OR APPURTENANCES.NOTED:OBSERVED AT ROOF LEVEL,PERIMETER FENCE IS IN DISREPAIR,AT V... | $0 | $0 | Mar 13, 2018 |
| Nov 17, 2017 | 35280539K | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35272442Y ISSUED ON 07/17/17 & TO FILE A C OF C PURSUAN... | $800 | $0 | May 29, 2018 |
| Jul 17, 2017 | 35272269J | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTER.OBSERVED IN LAUNDRY ROOM EXISTING GFCI RECEPTACLE OUTLETS NOT PRO... | $400 | $0 | Dec 5, 2017 |
| Jul 17, 2017 | 35272442Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.(1)OBSERVED IN GAS METER ROOM GAS LEAKING FROM CRACKED 90 DEGREES E... | $1,000 | $0 | Dec 5, 2017 |
| Jan 27, 2017 | 35225617P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. AT THE TIME OF MY INSPECTION I OBSERVED IN THE FIRE SPRINKLER CONT... | $500 | $0 | Sep 5, 2017 |
| Aug 30, 2016 | 35207637N | RESOLVE | CLASS - 1 | SEC. 408.2 & 411.1 MISC VIOLATION. OBSERVED ON 8/30/16 @ 12:35PM IN GAS METER ROOM & COMM. LAUDRY ROOM GAS (FUTURE) C... | $1,600 | $0 | Feb 14, 2017 |
| Aug 30, 2016 | 35207638P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLAINT MANNER. OBSERVED ON EXTERIOR TO CONNECT BALL CHECK VALUE CAPPED OFF. REQ'D... | $1,000 | $0 | Feb 14, 2017 |
| Feb 23, 2016 | 35171277R | RESOLVE | CLASS - 2 | SEC. 27-345 FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NO FIRE STOPPING PER BC 712.3;27-345. NOTED: AT 1ST FL ELECTRIC ... | $250 | $0 | Jun 28, 2016 |
| Feb 18, 2016 | 38240857Z | RESOLVE | CLASS - 2 | 15H7,70O02,24I10,100U5,17H11,12Q3,10H11,19X10,35Q7,40O2,100O2,52O2. 100U5-PERFORM AND FILE ANNUAL BRAKE TEST; 12Q3-PR... | $0 | $0 | Aug 9, 2016 |
| Feb 18, 2016 | 38240858K | RESOLVE | CLASS - 2 | 70O2,100U5,17H11,12Q3,10H11,19X10,35Q7,42O01,40O2,100O2,52O2. 100U5-PERFORM AND FILE ANNUAL BRAKE TEST; 12Q3-PROVIDE ... | $0 | $0 | Aug 9, 2016 |
| Aug 12, 2013 | 35027955K | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG. NOTED: EXTERIOR FACADE AT VARIOUS AREAS CONCRETE SPALLING EXPOSING REINFORCEMENT STEEL, PCS... | $10,000 | $0 | Oct 1, 2013 |
| Jun 5, 2013 | 35013511M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG WALLS. NOTE: SPALLING & CRACKING CONCRETE AT VARIOUS AREAS OF FACADE CONCRETE (FLOOR RIBBONS... | $2,500 | $0 | Jul 23, 2013 |
| Apr 27, 2013 | 34994973L | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED AT TIME OFINSPECTION OBSERVED: 1) AT EXPOSURE #1,2,3 & 4 ... | $1,000 | $0 | Jul 9, 2013 |
| Apr 27, 2013 | 35019677J | RESOLVE | CLASS - 1 | OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT C OF O. NOTED: OBSERVEDAT TIME OF INSPECTION AT 1ST FL ON THE DINING R... | $1,600 | $0 | Jul 9, 2013 |
| Mar 25, 2008 | 38183429Y | RESOLVE | Non-Hazardous | 17H11.10H11.85U15 | $350 | $0 | May 20, 2008 |
| Mar 25, 2008 | 38183428M | RESOLVE | Non-Hazardous | 17H11.10H11.85V10.59Q03. | $350 | $0 | May 20, 2008 |
| Mar 29, 2000 | 38095630X | RESOLVE | Non-Hazardous | 51F11,46H12, (51)REPAIR WORM AND GEARS F(46)REPLACE HOIST CABLES. | $0 | $0 | May 15, 2000 |
| May 10, 1999 | 38086611X | RESOLVE | Non-Hazardous | 50Y11,73O2. | $0 | $0 | Jun 29, 1999 |
| May 10, 1999 | 38086610Y | RESOLVE | Non-Hazardous | 50Y11,73O2. | $0 | $0 | Jun 29, 1999 |