ECB violations
Ocean Promenade, Queens • Block 15926 • Lot 0001
162 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Feb 18, 2026 | 39177654X | RESOLVE | CLASS - 3 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. OBSERVED 2 CRACKS IN FLOOR TOWARD FRONT OF STORE MEASURING A... | $0 | $0 | Apr 28, 2026 |
| Apr 1, 2025 | 39143472J | RESOLVE | CLASS - 2 | #3 LARRAS HW BOILER ON ROOF IS NOT OPERATIONAL+COMBUSTION AIR PROVING SWITCH IS DEFECTIVE+MOTORIZED AIR LOUVER IS BRO... | $0 | $0 | Jun 10, 2025 |
| Apr 1, 2025 | 39143518X | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. NOTED AT APT.1602. OBSERVED CRACKS AND CHIPPED PAINT IN WALL... | $0 | $0 | Jun 10, 2025 |
| Apr 1, 2025 | 39143519H | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN A CODE COMPLIANT MANNER. NOTED AT APARTMENT 1409. OBSERVED BATHROOM VENT FILLED WITH ... | $0 | $0 | Jun 10, 2025 |
| Apr 1, 2025 | 39143477Z | RESOLVE | CLASS - 3 | #1 LAARS HW BOILER GRD FLOOR HAS THE #1 CIRCULATOR NOT OPERATIONAL+THE CONDENSATE NEUTRALIZER IS DEFECTIVE;CORRECT VI... | $0 | $0 | Jun 10, 2025 |
| Apr 1, 2025 | 39143493Z | RESOLVE | CLASS - 2 | #1 LAARS HW BOILER ON ROOF HAS POOR COMBUSTIONÝODOR+FUMES¨>REPAIR+COMBUSTION TEST REQUIRED;CORRECT VIOLATION+SUBMIT C... | $0 | $0 | Jun 10, 2025 |
| Apr 1, 2025 | 39143494K | RESOLVE | CLASS - 3 | #3 LAARS HW BOILER ON ROOF IS NOT OPERATIONAL+TRI GAUGE ON HW TANK#2 IS DEFECTIVE;CORRECT VIOLATION+SUBMIT CERTIFICAT... | $250 | $0 | Jun 10, 2025 |
| Jan 8, 2025 | 39134948L | RESOLVE | CLASS - 2 | DEVICE OUT OF SERVICE RESTORED DEVICE BACK TO SERVICE. LOBBY DOOR DAMAGE FALL HAZARD CONDITION NOT SITTING IN THE SAD... | $625 | $0 | May 6, 2025 |
| Sep 19, 2024 | 39532528Z | RESOLVE | CLASS - 2 | I OBSERVED PEDESTRIAN PROTECTION (SIDEWALK SHED) INSTALLED AT EXPOSURES 1,2&3 CONTRARY TO CODES: 3307.6.4.11-SHED BEA... | $2,400 | $0 | Nov 26, 2024 |
| May 28, 2024 | 39529030Y | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION OF FACADE RESTORATION JOB SITE OBSERVED 4 OUTRIGGER BEAMS SUSPENDED SCAFFOLD INSTALLED/I... | $0 | $0 | Nov 12, 2024 |
| May 28, 2024 | 39529029R | RESOLVE | CLASS - 2 | AT THE TIME OF MY INSPECTION I OBSERVED 4 OUTRIGGER BEAMS SUSPENDED SCAFFOLD INSTALLED AND IN USE -OBSERVED SUSPENDED... | $0 | $0 | Aug 6, 2024 |
| Apr 11, 2024 | 39111454J | RESOLVE | CLASS - 1 | AT TIME OF INSPECTION OBSERVED AT THE GARAGE SECTION OF CEILING CONCRETE ALONG WALL PULLING AWAY AND EXPOSED SPACE AP... | $1,250 | $0 | Jun 18, 2024 |
| Mar 14, 2024 | 35682453L | RESOLVE | CLASS - 1 | FAILURE TO EXTERIOR BUILDING FACADE AND APPURTENANCES.-NOTE: BROKEN GLASS PANE WITH JAGGED SHARDS REMAINING OBSERVED ... | $2,500 | $0 | May 28, 2024 |
| Dec 19, 2023 | 39101745K | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. NOTED THROUGHOUT GROUND LEVEL PARKING GARAGE, MULTIPLE STEEL S... | $1,250 | $0 | Feb 27, 2024 |
| Sep 20, 2023 | 39521899Y | RESOLVE | CLASS - 2 | AT THE TINE OF MY INSPECTION OF A 19 STORY BUILDING, I OBSERVED SIDEWALK SHED IN PLACE AT EXPOSURE #1&3 WITH A VALID ... | $2,400 | $0 | Apr 23, 2024 |
| Sep 20, 2023 | 39521900M | RESOLVE | CLASS - 2 | AT THE TINE OF MY INSPECTION OF A 19 STORY BUILDING, I OBSERVED SIDEWALK SHED IN PLACE AT EXPOSURE #1&3 WITH A VALID ... | $2,400 | $0 | Apr 23, 2024 |
| Sep 19, 2023 | 39521872Y | RESOLVE | CLASS - 1 | AT THE TIME OF MY INSPECTION OF A 19 STORY BUILDING, I OBSERVED SIDEWALK SHED IN PLACE AT EXPOSURE #1&3 WITH LOOSE DE... | $0 | $0 | Apr 23, 2024 |
| Nov 15, 2022 | 35669334M | RESOLVE | CLASS - 1 | FAILURE TO TAKE&PROVIDE SAFETY MEASURES SUCH AS SIDEWALKSHED,FENCE,NETTING ETC TO SECURE PUBLIC SAFETY FOR DOCUMENTED... | $25,000 | $0 | Jun 13, 2023 |
| Sep 30, 2022 | 39071213P | RESOLVE | CLASS - 2 | MAIN TRACTION SHEAVE WORN HOIST CABLES SITTING EXTREMELY LOW IN THE SHEAVE. | $625 | $0 | Jul 18, 2023 |
| Aug 23, 2022 | 35664235Y | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING EXTERIOR WALLS/FACADE AND APPURTNENANCES.OBSERVED AT EXP3 DAMAGED MASONRY WITH EXPOSE RE... | $2,500 | $0 | Nov 29, 2022 |
| Aug 23, 2022 | 35664234M | RESOLVE | CLASS - 1 | UNLAWFUL ACT.FAILURE TO COMPLY WITH COMMISSIONER'S ORDER:RESPONDENT FAILED TO COMPLY WITH PREVIOUS ECB VIOLATION#3565... | $2,500 | $0 | Nov 29, 2022 |
| Jun 2, 2022 | 35651580M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS. FAILURE TO COMPLY W/ COMMISSIONER'S ORDER. NOTE:PREVIOUSLY WRITTEN ECB#35647137X DATED ON 4-12-22,REQU... | $2,500 | $0 | Nov 18, 2022 |
| Jun 2, 2022 | 35651579P | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE REQUIRED SAFETY MEASURES TO PROTECT PUBLIC SAFETY FROM DOCUMENTED UNSAFE FACADE. NOTE:FISP3 UNSAFE... | $25,000 | $0 | Nov 18, 2022 |
| Apr 12, 2022 | 35647137X | RESOLVE | CLASS - 1 | FAILURE TO TAKE REQUIRED MEASURES TO PROTECT PUBLIC FROM DOCUMENTED UNSAFE FACADE.AS NOTED BUILDING FILE A FISP 3 UNS... | $25,000 | $25,000 | Nov 18, 2022 |
| Mar 25, 2022 | 35647447L | RESOLVE | CLASS - 1 | FAILURE TO TAKE REQUIRED MEASURES TO PROTECT PUBLIC FROM DOCUMENTED UNSAFE FACADE.NOTE:RESPONDENT FAILED TO CORRECT P... | $25,000 | $25,000 | Mar 8, 2023 |
| Mar 25, 2022 | 35647448N | RESOLVE | CLASS - 1 | FAILURE TO TAKE REQUIRED MEASURES TO PROTECT PUBLIC FROM DOCUMENTED UNSAFE FACADE.NOTE:RESPONDENT FAILED TO CORRECT P... | $25,000 | $25,000 | Mar 8, 2023 |
| Feb 9, 2022 | 35640209Y | RESOLVE | CLASS - 1 | FAILURE TO TAKE REQUIRED MEASURES TO PROTECT PUBLIC FROM DOCUMENTED UNSAFE FACADE AS NOTED BLDG FILED FISP3 UNSAFE NO... | $10,000 | $0 | Sep 9, 2022 |
| Feb 9, 2022 | 35640207K | RESOLVE | CLASS - 1 | FAILURE TO TAKE REQUIRED MEASURES TO PROTECT PUBLIC FROM DOCUMENTED UNSAFE FACADE.AS NOTED BLDG FILED FISP3 UNSAFE NO... | $10,000 | $10,000 | Sep 9, 2022 |
| Feb 9, 2022 | 35640208M | RESOLVE | CLASS - 1 | FAILURE TO TAKE REQUIRED MEASURES TO PROTECT PUBLIC FROM DOCUMENTED UNSAFE FACADE.AS NOTED BLDG FILED FISP3 UNSAFE NO... | $10,000 | $0 | Sep 9, 2022 |
| Aug 31, 2021 | 35533821R | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35507952H ISSUED ON 7/16/2021 AND TO F... | $1,250 | $0 | Nov 30, 2021 |
| Jul 16, 2021 | 35507952H | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.AT TIME OF INSPECTION OBSERVED MULTIPLE WINDOW TYPE A/C UNITS INSTA... | $1,250 | $0 | Oct 5, 2021 |
| Apr 2, 2021 | 39038749Z | RESOLVE | CLASS - 2 | BEARING ASSEMBLY ON CIRCULATOR LEAKING CORRECT VIOLATING CONDITION AND SUBMIT A CERTIFICATE OF CORRECTION | $625 | $0 | Oct 26, 2021 |
| Apr 23, 2019 | 38267785Z | RESOLVE | CLASS - 2 | 2B10, 52B14 2B10 PHONE CALLS PREVIOUS COMPANY 52B14 SHORTEN HOIST CABLES. | $625 | $0 | Dec 3, 2019 |
| Apr 23, 2019 | 38267786K | RESOLVE | CLASS - 2 | 2B10, 5D1, 45M7 2B10-PHONE CALLS PREVIOUS COMPANY 5D1-DOORS SPLIT WHWHEN CLOSING - ADJUST ROLLERS 45M7 GOVENOR SEAL M... | $0 | $0 | Jul 2, 2019 |
| Apr 15, 2019 | 39004715P | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. COMBUSTION AIR PROVING SWITCH IS BYPASSED. CORRECT VIOLATING CO... | $625 | $0 | Aug 13, 2019 |
| Apr 15, 2019 | 39002133X | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. COMBUSTION AIR PROVING SWITCH IS BYPASSED. CORRECT VIOLATING CO... | $625 | $0 | Nov 10, 2020 |
| Apr 15, 2019 | 39002132Y | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORREC... | $625 | $0 | Nov 10, 2020 |
| Apr 15, 2019 | 39002131M | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. COMBUSTION AIR PROVING SWITCH IS BYPASSED. CORRECT VIOLATING CO... | $625 | $0 | Nov 10, 2020 |
| Apr 15, 2019 | 39004716R | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. CORRECT VIOLATING CONDITIONS AND SUBMIT A CERTIFICATE OF CORREC... | $625 | $0 | Aug 13, 2019 |
| Apr 15, 2019 | 39002130K | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. COMBUSTION AIR PROVING SWITCH IS BYPASSED. CORRECT VIOLATING CO... | $625 | $0 | Nov 10, 2020 |
| Apr 15, 2019 | 39004717Z | RESOLVE | CLASS - 2 | LAARS NTH100 BOILER. MISSING RETAINING CLIPS ON FLUE. COMBUSTION AIR PROVING SWITCH IS BYPASSED. CORRECT VIOLATING CO... | $625 | $0 | Aug 13, 2019 |
| Jan 7, 2019 | 38267098R | RESOLVE | CLASS - 1 | 5A10 DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH THIS IS A SAFETY DEVICE TO ENSURE PASSENGERS SAFETY. REPAIR RESTR... | $1,000 | $0 | Mar 19, 2019 |
| Jan 7, 2019 | 38267099Z | RESOLVE | CLASS - 1 | CU05A10, 78B14. 5A10-DOOR ZONE RESTRICTOR NOT WORKING TAMPERED WITH THIS IS A SAFETY DEVICE TO ENSURE PASSENGERS SAFE... | $1,000 | $0 | Mar 19, 2019 |
| Jun 1, 2018 | 35329341J | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. LACK OF EMERGENCY LIGHTING FOR EXITS, EXIT DISCHARGES AND PUBLIC C... | $1,250 | $0 | Dec 11, 2018 |
| Jun 1, 2018 | 35329340H | RESOLVE | CLASS - 2 | UNLAWFUL DISPLAY OF ARTWORK IN CORRIDORS GREATER THAN 20% PER FDNY 2008 CODE; FC 803.3.2. NOTED: ARTWORK DISPLAYED IN... | $0 | $0 | Dec 11, 2018 |
| Feb 4, 2018 | 38261169H | RESOLVE | CLASS - 2 | 99BB15,59B7,68B7,25M7,80B7-99BB15)ONE YEAR TAG EXPIRED. 59B7)PROVIDE DATE ON BRAKE MAINTENANCE TAG. 68B7)BRAKE MAINTE... | $250 | $0 | Jun 26, 2018 |
| Jan 25, 2018 | 38260137Z | RESOLVE | CLASS - 2 | 52K2;59B10;78B14:HOIST CABLES SEVERELY RUSTED;BRAKE ELECTRICAL CONTACT MISSING ONE CONTACT AND NEEDS TO BE ADJUSTED;G... | $500 | $0 | Mar 13, 2018 |
| Dec 9, 2017 | 38258339Y | RESOLVE | CLASS - 2 | 97X10)REPAIR AND RESTORE TO SERVICE. | $0 | $0 | Feb 6, 2018 |
| Dec 7, 2017 | 38259904M | RESOLVE | CLASS - 1 | CEASE USE 5A10,70O2, 71L10, 99BB7 5A10CEASE USE ITEM DOOR HONE RESTRICTOR HAS BEEN TAMPERED WITH DISABLED AND RENDERE... | $1,000 | $0 | Apr 24, 2018 |
| Nov 1, 2017 | 38259278Y | RESOLVE | CLASS - 1 | 02X10)REPAIR ALARM BELL. CENTENNIAL ELEVATOR LIC #249001 SUBMITTED A CATEGORY I TEST REPORT FOR 4F6054 ON MAY 27,2017... | $4,800 | $0 | Jun 12, 2018 |