ECB violations
2390 Richmond Road, Staten Island • Block 03626 • Lot 0010
7 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 25, 2013 | 35021293N | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O PERMIT. ELECTRICAL WIRING OF SERVICE ENTRANCE, STAND PIPE, SERVICE SWITCH, FEEDERS, PANELS, FUSE ... | $0 | $0 | Oct 9, 2013 |
| Jun 25, 2013 | 35021294P | RESOLVE | CLASS - 1 | SEC. EC 240.53. VIOLATION OF THE ELECRICAL CODE TECHNICAL STANDARDS. BASEMENT, PLUG FUSES ARE NOT TAMPER-PROOF TYPE. ... | $0 | $0 | Oct 9, 2013 |
| Jun 25, 2013 | 35021295R | RESOLVE | CLASS - 1 | SEC. EC 250.50 VIOLATION OF THE ELECTRICAL CODE TECHNICAL STANDARDS. BASEMENT, ELECTRICAL SERVICE GROUND CONDUCTOR IS... | $0 | $0 | Oct 9, 2013 |
| Jun 25, 2013 | 35021296Z | RESOLVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. SERVICE GROUNDING CONDUCTOR NOT CONTINUOUS TO WATER MAIN. AT 11:05 OBSERVED AT ... | $0 | $0 | Oct 9, 2013 |
| Jun 25, 2013 | 35021297K | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY GROUP/LABEL DISCONNECT. BSMT, PANELS, BOXES, SERVICE SWITCH NOT IDENTIFIED OR LABELED WHAT THEY S... | $0 | $0 | Oct 9, 2013 |
| Jun 25, 2013 | 35021298M | RESOLVE | CLASS - 1 | FAILURE TO PROTECT CONDUCTORS AGAINST OVERCURRENT PER EC. BSMT BRANCH CIRCUITS OVER FUSED. 30 AMP ON #12 AWG WIRE PAN... | $0 | $0 | Oct 9, 2013 |
| Jun 25, 2013 | 35021299Y | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS. BSMT, ELECTRICAL SERVICE EQUIPMENT NOT BONDED TOGETHER. AT 11:05 AM OBSE... | $0 | $0 | Oct 9, 2013 |