ECB violations
Lacjhs, Manhattan • Block 01157 • Lot 0025
129 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 1, 2014 | 35093766R | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. ON 5TH FLOOR, OUTSIDE RM 508 ARTWORK HANGING FROM MECHANICAL EQUIP... | $0 | $0 | Jun 5, 2014 |
| Apr 1, 2014 | 35093764N | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG WALL(S) OR APPURTENANCES. EXTERIOR CHAINLINK FENCE OUTSIDE CAFETERIA AT 2ND FLOOR ON NORTH &... | $0 | $0 | Jun 5, 2014 |
| Apr 1, 2014 | 35093761H | RESOLVE | CLASS - 2 | RE-ISSUE # 35019007K. EXIT DOORS NOT SELF CLOSING. BASEMENT LEVEL GYM EXIT DOOR H & I AND EXIT 8 AND DOOR BETWEEN GYM... | $0 | $0 | Jun 5, 2014 |
| Apr 1, 2014 | 35093767Z | RESOLVE | CLASS - 2 | USE OF PLEXIGLASS OR THERMOPLASTIC ON VARIOUS DOORS. INTERIOR CORRIDOR SMOKE DOORS HAVE,IN ADDITION TO WIRED GLASS,PL... | $0 | $0 | Jun 5, 2014 |
| Apr 1, 2014 | 35093765P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. WATER PENETRATION AT EXIT 1 INSIDE STAIRWELL NEXT TO LOADING BAY. ... | $0 | $0 | Jun 5, 2014 |
| Apr 1, 2014 | 35093762J | RESOLVE | CLASS - 2 | RE-ISSUE # 35019005R. FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3; 27-345. GAS M... | $0 | $0 | Jun 5, 2014 |
| Mar 14, 2014 | 35038815M | RESOLVE | CLASS - 2 | WORK WITHOUT PERMIT. OBSERVED AT 5:30PM (1) DELUCE PANEL CONTROL INSTALLED ON WALL BY STAGE. (G LEVEL OF BUILDING). R... | $0 | $0 | May 15, 2014 |
| May 29, 2013 | 35019004P | RESOLVE | CLASS - 2 | REISSUE: 34950275J - AT AUDITORIUM STAGE THE OVERHEAD WALL ABOVE CURTAIN HAS VENTICLE CRACKS. RMDY: NO ACCESS. REPAIR... | $0 | $0 | Jul 18, 2013 |
| May 29, 2013 | 35019007K | RESOLVE | CLASS - 2 | REISSUE: 34950278P - DOORS NOT SELF CLOSING. BASEMENT LEVEL GYM EXIT DOOR H AND I AND GYM DOOR BETWEEN GYMNS. RMDY: M... | $0 | $0 | Jul 18, 2013 |
| May 29, 2013 | 35019005R | RESOLVE | CLASS - 2 | REISSUE: 34871316L - 1. THE GAS METER ROOM IS LACKING FIRE STOPPING AROUND PIPE PENETRATIONS AT CELLAR LEVEL; 2.ROOM ... | $0 | $0 | Jul 18, 2013 |
| May 29, 2013 | 35019006Z | RESOLVE | CLASS - 2 | REISSUE: 34950276L - 4TH FL CORRIDOR ONE ANIMAL (INFLATED) HANGING MECHANICAL EQUIPMENT. RMDY: REMOVE ALL ITEMS FROM ... | $0 | $0 | Jul 18, 2013 |
| May 29, 2013 | 35019003N | RESOLVE | CLASS - 2 | 27-333. REISSUE: 34950277N - PLEX-VISION PANELS INSTALLED AT 4TH FLRAND (ALL) FLOORS SMOKE DOORS. RMDY: REMOVE PLEXI ... | $0 | $0 | Jul 18, 2013 |
| Mar 27, 2012 | 34950277N | RESOLVE | CLASS - 2 | 27-317(B) REISSUE: 34921732N. PLEXI-VISION PANELS INSTALLED AT 4TH FLOOR AND (ALL) FLOOR SMOKE DOORS. REMEDY: REMOVE ... | $0 | $0 | May 31, 2012 |
| Mar 27, 2012 | 34950275J | RESOLVE | CLASS - 2 | REISSUE: 34921734R. AT AUDITORIUM STAGE THE OVERHEAD WALL ABOVE CURTAIN HAS VERTICAL CRACKS. REMEDY: REPAIR MASONRY W... | $0 | $0 | May 31, 2012 |
| Mar 27, 2012 | 34950276L | RESOLVE | CLASS - 2 | REISSUE: 34921733P. CHAIRS MADE OF WOOD ARE HANGING FROM LIGHT FIXTURES AND CONDUITS AT 4TH FLOOR CORRIDOR. REMEDY: R... | $0 | $0 | May 31, 2012 |
| Mar 27, 2012 | 34950278P | RESOLVE | CLASS - 2 | REISSUE:34921729M. 4TH FLOOR SMOKE DOOR NEAR ROOM 452G NOT CLOSING. 3RD FLOOR SMOKE DOORS NEAR ROOM 326 NOT CLOSING.B... | $0 | $0 | May 31, 2012 |
| Jul 27, 2011 | 34921731L | RESOLVE | CLASS - 2 | CONDENSATE LEAK AT 5TH FL CORRIDORS ADJACENT TO ROOMS 536 & 522 CONCEALED CONDENSATE LEAK W/ DRIPPING WATER PRESENT A... | $0 | $0 | Sep 15, 2011 |
| Jul 27, 2011 | 34921730J | RESOLVE | CLASS - 2 | SPALLING CONCRETE CEILING AT 5FL CORRIDOR ADJACENT TO ROOM 536 THE CONCRETE WAFFLE CEILING IS SPALLING AT EXTERIOR WI... | $0 | $0 | Sep 15, 2011 |
| Jul 27, 2011 | 34921733P | RESOLVE | CLASS - 2 | HANGING CHAIR ART WORK AT 4TH FL SOUTH CORRIDOR 30 PAINTED WOOD CHAIRS HANG FROM LIGHT FIXTURES AND CONDUITS AT CEILI... | $0 | $0 | Sep 15, 2011 |
| Jul 27, 2011 | 34921734R | RESOLVE | CLASS - 2 | DEFECTIVE CMU BLOCK WALL AT AUDITORIUM STAGE THE OVER HEAD KNEE WALL ABOVE CURTAIN HAS VERTICAL CRACKS APPX 6' ON THE... | $0 | $0 | Sep 15, 2011 |
| Jul 27, 2011 | 34921732N | RESOLVE | CLASS - 2 | 27-371B PLEXI VISION PANELS AT 4FL ALL SMOKE DOORS W/ PLEXI VISION PANELS REM: REMOVE ALL PLEXI PANELS PROVIDE CODE C... | $0 | $0 | Sep 15, 2011 |
| Jul 27, 2011 | 34921728K | RESOLVE | CLASS - 2 | BROKEN DOOR CHECKS THE FIRE ROOF SELF CLOSING DOORS HAVE BROKEN DOOR CHECKS AT 2FL STAIRWAY E 1FL STAIRWAY F REM: REP... | $0 | $0 | Sep 15, 2011 |
| Jul 27, 2011 | 34921729M | RESOLVE | CLASS - 2 | RACKED DOORS THE FIRE PROOF CLOSING DOORS ARE RACKED TO FRAME AND JAM AT 5FL STAIRWAY C 1FL EXIT 4 SMOKE DOORS 3FL AD... | $0 | $0 | Sep 15, 2011 |
| Aug 12, 2010 | 34871317N | RESOLVE | CLASS - 2 | THE EXTERIOR ROOF HAS BECOME POROUS AND ALLOWING RAIN INTO THE BLDG CAUSING INTERIOR DAMAGES BY THE CORRIDOR HALLWAY ... | $0 | $0 | Sep 16, 2010 |
| Aug 12, 2010 | 34871315J | RESOLVE | CLASS - 2 | REISSUE:34779453X.THE GAS IS LACKING FRESH AIR VENTILATION @ THE CELLAR LEVEL.NOTED:THE NEGATIVE PRESSURE IN THE GAS ... | $0 | $0 | Sep 16, 2010 |
| Aug 12, 2010 | 34871316L | RESOLVE | CLASS - 2 | THE GAS METER ROOM IS LACKING FIRE STOPPING AROUND THE PIPE PENETRATION AT CELLAR LEVEL.REMEDY:PROVIDE FIRE STOPPING ... | $0 | $0 | Sep 16, 2010 |
| May 12, 2009 | 34779455J | RESOLVE | CLASS - 2 | REISSUE:34712009N SOUTHWEST PENTHOUSE MECHANICAL ROOM LEAK HAS DAMAGEDCEILING IN ROOM 538. REMEDY:STOP LEAK & REPAIR ... | $0 | $0 | Jul 9, 2009 |
| May 12, 2009 | 34779454H | RESOLVE | CLASS - 2 | REISSUE:34712008L.HORIZONTAL CRACKS IN CEMENT BLOCK WALL THRU-OUT GYM.REMEDY:REPAIR CRACKS IN WALL. | $0 | $0 | Jul 9, 2009 |
| May 12, 2009 | 34779451M | RESOLVE | CLASS - 2 | REISSUE:34712005X.CEILING FELL,FLOOR WATER DAMAGED NEAR ROOM 192,DUE TO DEFECTIVE VENT AT NORTH SIDE OF BLDG.WATER IS... | $0 | $0 | Jul 9, 2009 |
| May 12, 2009 | 34779450K | RESOLVE | CLASS - 2 | REISSUE:34712004Y. EXTERIOR LEAK FROM VENT ON NORTH SIDE WATER DAMAGE IN CORRIDOR NEAR ROOM 192.REMEDY:STOP WATER LEA... | $0 | $0 | Jul 9, 2009 |
| May 12, 2009 | 34779452Y | RESOLVE | CLASS - 2 | REISSUE:34712006H CEILING CONCRETE IS CRACKED IN GAS METER ROOM AT CELLAR LEVEL.REMEDY:REPAIR CRACKED CEILING. | $0 | $0 | Jul 9, 2009 |
| May 12, 2009 | 34779453X | RESOLVE | CLASS - 2 | REISSUE:34712007J.NO FRESH AIR VENT IN GAS METER ROOM AT CELLAR LEVEL.REMEDY:INSTALL FRESH AIR VENTILATION. | $0 | $0 | Jul 9, 2009 |
| Oct 8, 2008 | 34712010K | RESOLVE | CLASS - 2 | TEACHERS CAFETERIA 2ND ENTRANCE DOOR MISSING DOOR CHECK. REMEDY: REPAIR DOOR. | $0 | $0 | Jan 8, 2009 |
| Oct 8, 2008 | 34712006H | RESOLVE | CLASS - 2 | CEILING CONCRETE IS CRACKED LOCATED IN THE GAS METER ROOM ON ON CELLAR LEVEL. REMEDY: REPAIR CEILING CRACK. | $0 | $0 | Jan 8, 2009 |
| Oct 8, 2008 | 34712008L | RESOLVE | CLASS - 2 | HORIZONTAL CRACK IN CEMENT BLOCK WALL THRU-OUT GYMNASIUM. REMEDY: REPAIR CRACK IN WALL. | $0 | $0 | Jan 8, 2009 |
| Oct 8, 2008 | 34712009N | RESOLVE | CLASS - 2 | SOUTHWEST PENTHOUSE MECHANICAL ROOM LEAK HAS DAMAGED CEILING IN CLASS ROOM. REMEDY: STOP LEAK IN ROOM 538. | $0 | $0 | Jan 8, 2009 |
| Oct 8, 2008 | 34712007J | RESOLVE | CLASS - 2 | NO FRESH AIR VENTILATION IN THE GAS METER ROOM INSTALLED ON CELLAR LEVEL. REMEDY: INSTALL FRESH AIR VENTILATION. | $0 | $0 | Jan 8, 2009 |
| Oct 8, 2008 | 34712004Y | RESOLVE | CLASS - 2 | EXTERIOR LEAK FROM VENT ON NORTH SIDE WATER IN CORRIDOR NEAR RM 192. REMEDY: STOP WATER LEAKING FROM EXTERIOR VENT. | $0 | $0 | Jan 8, 2009 |
| Oct 8, 2008 | 34712005X | RESOLVE | CLASS - 2 | INTERIOR CEILING FELL BECAUSE OF WATER LEAK FROM EXTERIOR VENT ERECTED ON NORTH SIDE OF BUILDING. WATER LEAKING IN CO... | $0 | $0 | Jan 8, 2009 |
| Sep 4, 2007 | 34592967N | RESOLVE | Hazardous | NO FRESH AIR VENTILATION IN THE GAS METER ROOM INSTALLED ON CELLAR LEVCEL.REMEDY:INSTALL FRESH AIR VENTILATION. | $0 | $0 | Nov 15, 2007 |
| Sep 4, 2007 | 34592968P | RESOLVE | Hazardous | CEILING CONCRETE IS CRACKED LOCATED IN THE GAS METER ROOM ON CELLAR LEVEL REMEDY:REPAIR CEILING CRACK. | $0 | $0 | Nov 15, 2007 |
| Apr 25, 2006 | 34519139R | RESOLVE | Hazardous | REISSUE VI#34315712X AND 34381725K. CORROGATED SOUND BARRIER CONCRETE WALL APPROX. 8X11'WIDE ON 5TH FL NEAR ROOM M548... | $0 | $0 | Jul 20, 2006 |
| Mar 24, 2004 | 34432722M | RESOLVE | Non-Hazardous | PANIC HARDWARE INOPERATIVE NOTED : AT CAFETERIA - PANIC HARDWARE ON NORTH DOOR DEFETIVE, DOES NOT WORK PROPERLY REMED... | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432721K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING DEFECT(S) NOTED : DEFECTIVE DOORS - CORRIDOR DRS. NEAR RM # 452G, BMT - EXIT DR. NE, EXI... | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432570M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING DEFECT NOTED : (1) BROKEN / DEFECTIVE / MISSING DOOR CLOSERS - 536, 534, 532, 528 FIRE D... | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432571Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING DEFECT NOTED: DOORS WITH BROKEN/MISSING SAFTY GLASS-FIRE DRS NEAR RMS. 512,552B, 4TH FLR... | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432574J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN EXTERIOR BUILDING DEFECT NOTED: SE CORNER, EAST AND SOUTH STONE STEPS ARE BROKEN AND DETERIORATIN... | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432573H | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. DEFECT NOTED: DAMAGED CEILING FROM LEAKAGE - MAIN GYM, STAIR #6 LEAKAGE AT CONCRETE CEI... | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432575L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED: NO VENTILATION IN GAS METER ROOM. REMEDY: MAINTAIN BUILDING/ PROVIDE VENTILATION. | $0 | $0 | Jun 17, 2004 |
| Mar 24, 2004 | 34432685M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED: AT 2ND, 3RD AND 4TH FLOORS, CRACKED AND/ OR MISSING PERIMETER WINDOW PANES, APPRO... | $0 | $0 | Jun 17, 2004 |