ECB violations
Lacjhs, Manhattan • Block 01157 • Lot 0025
129 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Oct 3, 2003 | 38141421Y | RESOLVE | Non-Hazardous | 01B11/ 85BB05/ 59B07/ 63M07/ 01B11=REPAIR ALARM BELL IN STOP SWITCH. 85BB05=PERFORM & FILE FOR 5 YEAR TESTS. 59=PROVI... | $0 | $0 | Nov 20, 2003 |
| Oct 3, 2003 | 38141422X | RESOLVE | Non-Hazardous | 85BB05/ 63M07/ 59B07/ 83X10/ 85=PERFORM & FILE FOR 5 YEAR TEST. 63=PROVIDE NYC DEVICE # ON MAIN LINE DISCONNECT, CONT... | $0 | $0 | Nov 20, 2003 |
| Oct 3, 2003 | 38141423H | RESOLVE | Non-Hazardous | 63M07/ 66Y10/ 63M07=PROVIDE NYC DEVICE #'S ON MAIN LINE DISCONNECT, CONTROLLER, & TANK. 66Y10=REPAIR OIL LEAK IN PIT. | $0 | $0 | Nov 20, 2003 |
| Feb 28, 2003 | 34381722P | RESOLVE | Non-Hazardous | FAILRUE TO MAINTAIN BUIDLNG. NOTED : DOOR CHECKS BROKEN / DEFECTIVE; AT HALLWAY SMOKE DOORS NEXT TO ROOMS 526, 589, 5... | $0 | $0 | Jul 3, 2003 |
| Feb 28, 2003 | 34381723R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED : FIRE / SMOKE STOP DOORS MISSING NEXT TO ROOM G 15G REMEDY : MAINTAIN BUILDING. I... | $0 | $0 | Jul 3, 2003 |
| Feb 28, 2003 | 34381826J | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING NOTED. WOOD FLOORING AT BASEMENT GYM/DANCE STUDIO (G9D) HAS WATER DAMAGE CAUDING AREAS T... | $0 | $0 | Jul 3, 2003 |
| Feb 28, 2003 | 34381724Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. NOTED : SHEETROCK COVERING AROUND PLUMBING AND SPRINKLERS PIPES AT WALL & CEILING OF GY... | $0 | $0 | Jul 3, 2003 |
| Feb 28, 2003 | 34381725K | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. NOTED : CORROGATED SOUND BARRIER CONCRETE WALL APPROX 8' X 11' WIDE ON THE 5TH FLOOR NE... | $0 | $0 | Jul 3, 2003 |
| Feb 28, 2003 | 34381720L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUILDING. NOTED : LOWER SECTIONS OF FULL LENGHT WIDOWS AROUND PASSAGEWAYS ON 3RD, 4TH & 5TH FLOOR... | $0 | $0 | Jul 3, 2003 |
| Feb 28, 2003 | 34381721N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BUIDLING. NOTED : ROOF LEAKS ABOVE STAIRWAY 6 ON 5TH FL REMEDY : MAINTAIN BUILDING. REPAIR ROOF | $0 | $0 | Jul 3, 2003 |
| Feb 21, 2002 | 34315714J | RESOLVE | Hazardous | FAILURE TO MAINTAIN BUILDING; DEFECTS NOTED; EXCESSIVE CRACKS SEPARATION, DETERIORATING, LOOSE PULIING AWAY OF STRUCT... | $0 | $0 | Apr 25, 2002 |
| Feb 21, 2002 | 34315713H | RESOLVE | Hazardous | FAILURE TO MAINTAIN BLDG. DEFECT NOTED; BROKEN SAGGING DETERIORATED CRACKED MISSING, "COLLAPSING" WOOD PLANK FLOORIN ... | $0 | $0 | Apr 25, 2002 |
| Feb 21, 2002 | 34315715L | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN BLDG; DEFECT NOTED; CORRODED, ROTTEN DETERIORATED . MAJOR ERROSION OF ENTIRE CURTIN WALL SYSTEM T... | $0 | $0 | Apr 25, 2002 |
| Feb 21, 2002 | 34315712X | RESOLVE | Hazardous | FAILURE TO MAINTAIN; DEFECT NOTED; CRACKED MAJOR SEPARATION PULLING AWAY. IN DANGER OF COLLAPSEING, CONCRETE WALL (AP... | $0 | $0 | Apr 25, 2002 |
| Mar 13, 2001 | 34282357M | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN: DEFECTS ARE; SPALLING CONCRETE CEILINGS; LOCATIONS: CORRIDORS ADJACENT TO 536, 540, 546, EXIT #4... | $0 | $0 | Oct 11, 2001 |
| Mar 13, 2001 | 34282359X | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECTS ARE CRACKED CONCRETE CEILINGS (PAN FORMED). LOCATIONS; 370, 378 AT ENTRANCE, 376. REMEDY:... | $0 | $0 | Oct 11, 2001 |
| Mar 13, 2001 | 34282361P | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECTS ARE. CRACKED CONCRETE FLOORS. LOCATIONS; FAN ROOM S/WEST PENTHOUSE AT EC27S, N/WEST PENTH... | $0 | $0 | Oct 11, 2001 |
| Mar 13, 2001 | 34282362R | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECTS ARE DAMAGED FLOORING WITH HOLES AND BUCKING. LOCATION: CORRIDOR S/E 4 FL AT WINDOW, LARGE... | $0 | $0 | Oct 11, 2001 |
| Mar 13, 2001 | 34282363Z | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN DEFECTS ARE SPALLING CONCRETE CEILING OVER HAND (PAN FORMED SLAB) LOCATION: NORTH CAFETERIA EXIT ... | $0 | $0 | Oct 11, 2001 |
| Mar 13, 2001 | 34282360N | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN, DEFECTS ARE INTERIOR BUILDING ERROSION AND DAMAGE DUE TO WATER LEAKING INTO BUILDING. LOCATIONS,... | $0 | $0 | Oct 11, 2001 |
| Mar 13, 2001 | 34282358Y | RESOLVE | Non-Hazardous | FAILURE TO MAINTAIN; DEFECTS ARE CRACKED MASONRY WALLS. LOCATION: NORTH WEST PENTHOUSE ADJACENT TO PLEINUM CHAMBER, R... | $0 | $0 | Oct 11, 2001 |
| Feb 10, 2000 | 38094040L | RESOLVE | Non-Hazardous | 05J01,30P07,35R06,54T16,57P07. 05- CAR DOOR SLAMS. 30- PROVIDE. 35- SECURE SMOKE HOLE. 54- TAG DEVICE WITH CITY NUMBE... | $2,500 | $0 | Mar 30, 2000 |
| Feb 10, 2000 | 38094039Y | RESOLVE | Non-Hazardous | 22D06,30P07,35R06,44L11,53B07,74##,50T16. 22- SECURE. 30- PROVIDE SMOKE HOLE. 44-EXCESSIVE ARCHING ON GENERATOR. 53- ... | $2,500 | $0 | Mar 30, 2000 |
| Apr 9, 1999 | 38085591N | RESOLVE | Non-Hazardous | 35D7,28E11. -35 REPAIR & FASTEN SMOKE HOLE FRAMES & GRATE, -28 ELIMI- NATE RUBBING NOISE FROM ROLLER GUIDES | $0 | $0 | Jun 3, 1999 |
| Sep 29, 1997 | 38064293M | RESOLVE | Non-Hazardous | 07L50Y25Q73T47B75U 07-REAR SAFETY EDGE NO WORKING PROPERLY 50-SEAL LEAK IN MACHINE 25-COVER BOTH DOOR MOTORS 73-TAG E... | $0 | $0 | Feb 5, 1998 |
| Sep 29, 1997 | 38064294Y | RESOLVE | Non-Hazardous | 73T47B73X75B 73-TAG ENTIRE DEVICE 47-SHORTEN GOVERNOR CABLE 73-RETURN TO SERVICE FOR COMPLETE INSPECTION 75-5 YR TEST... | $0 | $0 | Feb 5, 1998 |
| Sep 29, 1997 | 38064295X | RESOLVE | Non-Hazardous | 73T73Q37Q43B 73-TAG ENTIRE DEVICE 43-COVER BOX ON PUMP UNIT 37-COVER CONTROLLER 43-3 YR. TEST AND TAG. | $1,000 | $0 | Feb 5, 1998 |
| Feb 19, 1992 | 38022902N | RESOLVE | Non-Hazardous | 46K;50Y;08V; | $1,000 | $0 | Apr 30, 1992 |
| Feb 19, 1992 | 38022901L | RESOLVE | Non-Hazardous | 43Y;74Y; 74. EXCESS IN PLUNGER. | $1,000 | $0 | Feb 5, 1993 |