ECB violations
C Road, Manhattan • Block 01819 • Lot 0010
325 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Jun 29, 2026 | 39194121H | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. ROOF LEAKING THROUGHOUT BUILDING., REPAIR AND/REPLACE | $2,500 | $0 | Jul 9, 2026 |
| Jun 29, 2026 | 39194120X | ACTIVE | CLASS - 2 | EXIT DOOR NOT SELF-CLOSING THROUGHOUT BUILDING., REPAIR/REPLACE DOOR | $625 | $0 | Jul 9, 2026 |
| Jun 29, 2026 | 39194129M | ACTIVE | CLASS - 1 | ATOI DRYERS WERE INSTALLED AND OPERATING WITH OUT PROPER SPRINKLER COVERAGE. 903.2.11.13 AN AUTOMATIC SPRINKLER SYSTE... | $2,500 | $0 | Jul 9, 2026 |
| Jun 29, 2026 | 39194124N | ACTIVE | CLASS - 1 | FAILURE TO CLOSE UNUSED OPENINGS (KNOCKOUTS) IN OUTLET/PANEL BOX. OBSERVED IN MAIN BUILDING AND COTTAGE 1 AND 3 THE P... | $1,600 | $0 | Jul 9, 2026 |
| Jun 29, 2026 | 39194068H | ACTIVE | CLASS - 2 | FOUND CLEAVER BROOK MODEL# FLX-200 OIL FIRED BOILER, WITH EXPOSED WIRING, SAFETY RELIEF VALVE SIGNS OF LEAKAGE,BODY D... | $1,250 | $0 | Jul 9, 2026 |
| Jun 29, 2026 | 39194123L | ACTIVE | CLASS - 1 | FAILURE TO GROUND ELECTRICAL SYSTEMS. OBSERVED IN THE MAIN ELECTRICAL NO GROUND ELECTRODE ROD INSTALLED, ALSO THE MAI... | $4,800 | $0 | Jul 9, 2026 |
| Jun 29, 2026 | 39194125P | ACTIVE | CLASS - 1 | UNAPPROVED/UNSAFE/UNSUITABLE ELECTRICAL EQUIPMENT, APPARATUS, MATERIALS, DEVICES, APPLIANCES OR WIRING IN USE. OBSERV... | $1,600 | $0 | Jul 9, 2026 |
| Apr 20, 2026 | 39189617P | ACTIVE | CLASS - 2 | SPILLSWITCH NEEDED,NOBACKFLOW PREVENTER. BOILER RM 2 BLOW DOWN ON RELIEF VALVE NEEDED, SPILL SWITCH NEEDED,BOILER RM ... | $1,250 | $0 | Jul 9, 2026 |
| Apr 20, 2026 | 39185289R | ACTIVE | CLASS - 1 | ELECTRICAL WORK WITHOUT A PERMIT. OBSERVED IN THE LAUNDRY RM NEW ELECTRICAL PANEL AND CONDUITS INSTALLED FOR WASHER A... | $2,500 | $0 | May 20, 2026 |
| Dec 30, 2025 | 39171867M | ACTIVE | CLASS - 2 | I FOUND A CLEAVER BROOK FLX-200 WITH THE BACK FLOW LEAKING/CORRECT ALL VIOLATING CONDITION/SUBMIT CERTIFICATE OF CORR... | $1,250 | $0 | Feb 6, 2026 |
| Dec 30, 2025 | 39172024Z | ACTIVE | CLASS - 2 | OBSERVED THROUGHOUT THE BUILDING NONFUNCTIONING TOILETS AND SHOWERS, LACK FIRE STOPPING AT PIPE PENETRATIONS AND OBST... | $1,250 | $0 | Feb 6, 2026 |
| Nov 19, 2025 | 39167643L | ACTIVE | CLASS - 2 | OBSERVED THROUGHOUT THE BUILDING SPRINKLER HEADS OBSTRUCTED AND PVC WASTE LINES USED FOR BATHROOM SINKS AND EJECTOR P... | $1,250 | $0 | Dec 23, 2025 |
| Jun 26, 2025 | 39152104K | ACTIVE | CLASS - 1 | FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. OBSERVED EMERGENCY EXIT GATE PAD LOCKED AND CHAINED. ALL EMERGENCY E... | $1,250 | $0 | Jun 30, 2025 |
| Apr 4, 2025 | 39143979Z | ACTIVE | CLASS - 1 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 C... | $2,500 | $0 | Apr 10, 2025 |
| Apr 4, 2025 | 39143980X | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. CLIENTS BED ON 3RD FLOOR OBSTRUCTING SPRINKLER CONTROL VALUE R... | $1,250 | $0 | Apr 10, 2025 |
| Apr 4, 2025 | 39143866M | ACTIVE | CLASS - 2 | FOUND A CLEAVERBROOK FLX-200 STEAM BOILER WITH A SLIGHT OIL LEAK/MECHANICAL LOUVER FOR AIR INTAKE NOT WORKING PROPELY... | $1,250 | $0 | Apr 10, 2025 |
| Apr 4, 2025 | 39143981H | ACTIVE | CLASS - 2 | FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. FLEX CORD INSTALLED AT THE BACK OF COMMERCIAL DRYER AT LAUNDRY... | $1,250 | $0 | Apr 10, 2025 |
| Apr 4, 2025 | 39143978R | ACTIVE | CLASS - 1 | UNSAFE STORAGE OF COMBUSTIBLE MATERIAL AND EQUIPMENT. OBSERVED UNSAFE STORAGE AT BASEMENT LEVEL. (PLUMBERS B TANK). P... | $2,500 | $0 | Apr 10, 2025 |
| Dec 2, 2024 | 39131712L | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN 588 OIL FIRED BOILER WITH EXPOSED WIRING,AND MISSING SIGHT GLASS. | $625 | $0 | Dec 5, 2024 |
| Dec 2, 2024 | 39131711J | ACTIVE | CLASS - 2 | FOUND BURNHAM V910,OIL FIRED BOILER, WITH EXPOSED WIRING, 2 PUMPS NOT OPERABLE, SIGHT GLASS ON FRONT OF BOILER MISSIN... | $625 | $0 | Dec 5, 2024 |
| Dec 2, 2024 | 39131713N | ACTIVE | CLASS - 2 | FOUND BURNHAM V910 OIL FIRED BOILER WITH SIGHT GLASS MISSING ON FRONT OF BOILER, RATING LABEL MISSING ON SAFETY RELIE... | $625 | $0 | Dec 5, 2024 |
| Jun 3, 2024 | 39116412Y | ACTIVE | CLASS - 1 | I OBSERVED IN THE GENERATOR LOCATED ON THE SIDE OF THE BUILDING THE FAILURE TO INSTALL GROUNDING AS REQUIRED FOR ELEC... | $4,800 | $0 | Jun 13, 2024 |
| Jun 3, 2024 | 39116413X | ACTIVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH COMMISSIONER'S ORDER AS STATED IN ECB# 39071863R ISSUED ON 10/06/2022 AND FILE ... | $2,500 | $0 | Jul 27, 2024 |
| Apr 5, 2024 | 39110884P | ACTIVE | CLASS - 2 | OBSERVED EXCESSIVE CARBON BUILD UP IN BOILER ROOM 4 AND ALSO BOILER ROOM 2. ALSO SLIGHT GLASS MISSING FROM THE BOILER... | $625 | $0 | Jun 3, 2024 |
| Apr 5, 2024 | 39110881J | ACTIVE | CLASS - 2 | OBSERVED EXCESSIVE CARBON BUILD UP IN BOILER ROOM 4 AND ALSO BOILER ROOM 2. ALSO SLIGHT GLASS MISSING FROM THE BOILER... | $625 | $0 | Jun 3, 2024 |
| Apr 2, 2024 | 39110541N | ACTIVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR ACTIVE WATER LEAK AN VALVE IN THE BOILER ROOM. AS PER 102.3 OF THE PLUMBING CODE, REP... | $625 | $0 | Jun 3, 2024 |
| Apr 1, 2024 | 39110494J | RESOLVE | CLASS - 2 | LARGE HOLE CUTOUT OF CEIL EXPOSING WATER DAMAGED, (ROTTEN) JOIST, LOCATED AT EXPOSURE #3., REPAIR AND/OR REPLACE | $625 | $0 | Jun 5, 2024 |
| Apr 1, 2024 | 39110525N | ACTIVE | CLASS - 2 | OBSERVED IN THE BATHROOM ON THIRD FLOOR AND THROUGHOUT BUILDING SPRINKLER BRANCHES ( ONES WITH THE SPRINKLER HEAD) UN... | $625 | $0 | Jun 3, 2024 |
| Apr 1, 2024 | 39110480Z | RESOLVE | CLASS - 2 | OBSERVED IN THE BASEMENT/CELLAR ACTIVE WATER LEAK IN THE THE MECHANICAL ROOM. AS PER 102.3 OF THE PLUMBING CODE MAINT... | $625 | $0 | Jun 3, 2024 |
| Apr 1, 2024 | 39110496N | ACTIVE | CLASS - 2 | MULTIPLE CRACKS IN FACADE AND FOOR MECHANICAL WALLS WITH SIGNS OF FUTURE DETACHMENT., REPAIR AND/OR REPLACE | $625 | $0 | Jun 5, 2024 |
| Apr 1, 2024 | 39110486J | ACTIVE | CLASS - 2 | OBSERVED IN THE MECHANICAL ROOM LOCATED ON THE MAIN FLOOR ACTIVE LEAK ON PIPING. AS 102.3 OF THE PLUMBING CODE MAINTE... | $625 | $0 | Jun 5, 2024 |
| Apr 1, 2024 | 39110499Z | ACTIVE | CLASS - 2 | OBSERVED 2 LEAKS IN THE BOILER ROOM ALSO OBSERVED LEAK ON THE VALVE TO THE COOLING TOWER LOCATED ON ROOF. MAINTENANCE... | $625 | $0 | Jun 3, 2024 |
| Apr 1, 2024 | 39110502K | ACTIVE | CLASS - 2 | CRACKS IN CMU BLOCK WALLS OF BOILER MECHANICAL ROOM LOCATED ON GROUND FLOOR., REPAIR AND/OR REPLACE | $625 | $0 | Jun 3, 2024 |
| Mar 26, 2024 | 39109946N | ACTIVE | CLASS - 2 | FOUND BURNHAM MODEL# V910, WITH EXPOSED WIRING, OIL LEAK AT TRANSFER PUMP,SIGHT GLASS MISSING ON FRONT OF BOILER, CIO... | $625 | $0 | May 29, 2024 |
| Mar 26, 2024 | 39109948R | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN MODEL #588 WITH MISSING BACK FLOW PREVENTER. | $625 | $0 | May 29, 2024 |
| Mar 26, 2024 | 39109949Z | ACTIVE | CLASS - 2 | FOUND BURNHAM MODEL# V910 WITH SAFETY RELIEF VALVE LABEL NOT LEGIBLE, EXPOSED WIRING, | $625 | $0 | May 29, 2024 |
| Mar 26, 2024 | 39109947P | ACTIVE | CLASS - 2 | FOUND BURNHAM MODEL# V910, WITH EXPOSED WIRING AND MISSING BACK FLOW PREVENTER. | $625 | $0 | May 29, 2024 |
| Mar 25, 2024 | 39109728P | ACTIVE | CLASS - 2 | MISSING JACKET ON BOILER/ COMBUSTION RFESH AIR INTAKE MECHANICAL LOUVER NOT OPERATIONAL/CORRSCT ALL VIOLATING CONDITI... | $625 | $0 | May 29, 2024 |
| Mar 22, 2024 | 39109573J | ACTIVE | CLASS - 2 | FOUND CLEAVER BROOKS MODEL FLX-200 WITH A MINOR OIL LEAK AND EXPOSE WIRE/CORRECT ALL VIOLATING CONDITIONS/SUBMIT CERT... | $625 | $0 | May 29, 2024 |
| Dec 21, 2023 | 39102028M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39071862P ISSUED ON 10/... | $2,500 | $0 | Jan 2, 2024 |
| Dec 21, 2023 | 39102027K | ACTIVE | CLASS - 1 | UNLAWFUL ACTS: FAILURE TO COMPLY WITH THE COMMISSIONERS ORDER CONTAINED IN SUMMONS/VIOLATION# 39071863R ISSUED ON 10/... | $2,500 | $0 | Jan 2, 2024 |
| Dec 15, 2022 | 39076109H | ACTIVE | CLASS - 2 | NEW SPRINKLER HEADS INSTALLED ON THE MAIN LEVEL ALSO IN THE IN BASEMENT/ CELLAR WITHOUT SYSTEM BEING TESTED. AS PER P... | $1,250 | $0 | Jan 10, 2023 |
| Dec 15, 2022 | 39075744M | RESOLVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR, COMMON AREA, ELECTRICAL RM AND MECHANICAL RM, ACOUSTICAL CEILING, SEVERAL MISSING PANELS AN... | $1,562 | $0 | Jan 11, 2023 |
| Dec 14, 2022 | 39075801J | RESOLVE | CLASS - 2 | AT FIRST FLOOR, MECHANICAL ROOM, SEVERAL OPENING DUE PIPES/CABLES PENETRATION WITHOUT FIRE STOPPING PROVIDED. PREVIOU... | $3,125 | $0 | Jan 11, 2023 |
| Dec 14, 2022 | 39075802L | ACTIVE | CLASS - 2 | AT FIRST FLOOR, ACOUSTICAL CEILING, SEVERAL MISSING PANELS AND WATER PENETRATION FROM ROOF. ALSO, ROOF LEAKS IN 20% O... | $1,562 | $0 | Jan 11, 2023 |
| Dec 14, 2022 | 39075803N | RESOLVE | CLASS - 2 | AT FIRST FLOOR, SELF-CLOSING FIREPROOF DOORS, 80% OF THE DOORS SHOW DEFECTS ON SELF-CLOSING SYSTEM, CORROSION AND OTH... | $1,562 | $0 | Jan 11, 2023 |
| Dec 14, 2022 | 39075969N | RESOLVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR, SELF-CLOSING FIREPROOF DOORS, 40% OF THE DOORS SHOW DEFECTS IN THE SELF-CLOSING SYSTEM, COR... | $1,562 | $0 | Jan 10, 2023 |
| Dec 14, 2022 | 39075788Y | RESOLVE | CLASS - 2 | AT 1ST FL, CAFETERIA, EXIT DOOR TO EXP # 3, EXIT DOOR TO EXP # 1 IS BEING OBSTRUCTED BY SCAN MACHINE AND DOESN'T CLOS... | $1,562 | $0 | Jan 11, 2023 |
| Dec 14, 2022 | 39075811N | ACTIVE | CLASS - 2 | -AT FIRST FLOOR, MECHANICAL ROOM, SEVERAL OPENING DUE PIPES/ CABLES PENETRATION AND WALLS DAMAGES WITHOUT FIRE STOPPI... | $3,125 | $0 | Jan 11, 2023 |
| Dec 14, 2022 | 39075743K | RESOLVE | CLASS - 2 | OBSERVED: AT FIRST FLOOR, SELF-CLOSING FIREPROOF DOORS, AT FIRST FL, MAIN ENTRANCE DOOR, MECHANICAL RM, SPRINKLER RM,... | $1,562 | $0 | Jan 11, 2023 |