ECB violations

C Road, Manhattan • Block 01819 • Lot 0010

325 records

Environmental Control Board violations, which carry a hearing and a penalty.

Issued Violation Status Severity Description Penalty Balance due Hearing
Dec 14, 2022 39075969N RESOLVE CLASS - 2 OBSERVED: AT FIRST FLOOR, SELF-CLOSING FIREPROOF DOORS, 40% OF THE DOORS SHOW DEFECTS IN THE SELF-CLOSING SYSTEM, COR... $1,562 $0 Jan 10, 2023
Dec 14, 2022 39075846N ACTIVE CLASS - 2 OBSERVED ON THE MAIN FLOOR SPRINKLER HEAD IS OBSTRUCTED BY THE DROP CEILING. IF A FIRE WOULD HAPPEN SPRINKLER HEAD WI... $625 $0 Jan 11, 2023
Dec 14, 2022 39075801J RESOLVE CLASS - 2 AT FIRST FLOOR, MECHANICAL ROOM, SEVERAL OPENING DUE PIPES/CABLES PENETRATION WITHOUT FIRE STOPPING PROVIDED. PREVIOU... $3,125 $0 Jan 11, 2023
Dec 14, 2022 39075811N ACTIVE CLASS - 2 -AT FIRST FLOOR, MECHANICAL ROOM, SEVERAL OPENING DUE PIPES/ CABLES PENETRATION AND WALLS DAMAGES WITHOUT FIRE STOPPI... $3,125 $0 Jan 11, 2023
Dec 14, 2022 39075786K RESOLVE CLASS - 1 OBSERVED: AT FIRST FL, CAFETERIA, EXIT DOOR TO EXPOSURE # 3 ARE BEING OBSTRUCTED BY TABLES AND EXIT DOOR TO EXPOSURE ... $1,250 $0 Jan 11, 2023
Dec 14, 2022 39075967J RESOLVE CLASS - 2 OBSERVED: AT FIRST FLOOR, MECHANICAL ROOM, SEVERAL OPENING DUE PIPES AN CABLES PENETRATION WITHOUT FIRE STOPPING PROV... $3,125 $0 Jan 11, 2023
Dec 14, 2022 39075741R RESOLVE CLASS - 1 I OBSERVED IN THE KITCHEN THE IMPROPERLY TERMINATED RACEWAY FROM THE EQUIPMENT DISCONNECT TO THE WARMING OVEN WITH TH... $1,600 $0 Jan 11, 2023
Dec 14, 2022 39076056N RESOLVE CLASS - 2 OBSERVED: AT FIRST FLOOR,MAIN ENTRANCE DOOR (2), ROOF LEVEL STAIR B AND EXTERIOR EXIT DOOR EXPOSURE # 4 DO NOT CLOSE ... $1,562 $0 Jan 10, 2023
Dec 14, 2022 39075968L ACTIVE CLASS - 2 OBSERVED: AT FIRST FLOOR, ACOUSTICAL CEILING, SEVERAL MISSING/DAMAGE PANELS DUE ROOF WATER LEAKS. PREVIOSUS VIOLATION... $1,562 $0 Jan 10, 2023
Dec 14, 2022 39075745Y RESOLVE CLASS - 2 OBSERVED: AT FIRST FLOOR, MECHANICAL ROOM, ELECTRICAL RM, SEVERAL OPENING DUE PIPES AN CABLES PENETRATION WITHOUT FIR... $3,125 $0 Jan 11, 2023
Dec 14, 2022 39075636P RESOLVE CLASS - 2 BOILER NOT OPERATING. CORRECT VIOLATING CONDITIONS & SUBMIT A CERTIFICATE OF CORRECTION $625 $0 Jan 11, 2023
Dec 14, 2022 39075785Z ACTIVE CLASS - 2 OBSERVED: AT SECOND FLOOR, MECHANICAL ROOM, CONCRETE STRUCTURE WITH CONCRETE DETACHMENT, CRACKED AND OTHER CONSTRUCTI... $3,125 $0 Jan 10, 2023
Dec 14, 2022 39075812P RESOLVE CLASS - 2 AT FIRST FLOOR, SELF-CLOSING FIREPROOF DOORS, SEVERAL DOORS SHOW DEFECTS AS SELF-CLOSING SYSTEM, CORROSION AND OTHER ... $1,562 $0 Jan 11, 2023
Dec 14, 2022 39075803N RESOLVE CLASS - 2 AT FIRST FLOOR, SELF-CLOSING FIREPROOF DOORS, 80% OF THE DOORS SHOW DEFECTS ON SELF-CLOSING SYSTEM, CORROSION AND OTH... $1,562 $0 Jan 11, 2023
Dec 14, 2022 39075802L ACTIVE CLASS - 2 AT FIRST FLOOR, ACOUSTICAL CEILING, SEVERAL MISSING PANELS AND WATER PENETRATION FROM ROOF. ALSO, ROOF LEAKS IN 20% O... $1,562 $0 Jan 11, 2023
Dec 13, 2022 39075793Z RESOLVE CLASS - 2 OBSERVED IN THE MECHANICAL ROOM THE DRAIN IS CLOGGED WITH DEBRIS, AS PER THE NYC PLUMBING CODE102.3 MAINTENANCE. INST... $625 $0 Jan 11, 2023
Dec 13, 2022 39075817Y ACTIVE CLASS - 2 OBSERVED IN THE MECHANICAL ROOM LOCATED ON THE MAIN FLOOR ACTIVE WATER LEAK ON PIPING. AS PER NYC PLUMBING CODE 102.3... $625 $0 Jan 11, 2023
Dec 13, 2022 39075835H ACTIVE CLASS - 2 OBSERVED ACTIVE LEAK IN THE MECHANICAL ROOM AND EXCESSIVE DEBRIS IN THE MECHANICAL ROOM. AS PER 102.3 MAINTENANCE. IN... $625 $0 Jan 11, 2023
Dec 13, 2022 39075830Z RESOLVE CLASS - 2 OBSERVED IN THE MECHANICAL ROOM LOCATED ON MAIN FLOOR EXTREMELY CORRODED O, S& Y VALVE ALSO ACTIVE LEAK FOUND ON THE ... $625 $0 Jan 11, 2023
Dec 13, 2022 39075792R ACTIVE CLASS - 2 OBSERVED ON THE ROOF ACTIVE LEAK ON THE AC CHILLER, AS PER NYC PLUMBING CODE 102.3 MAINTENANCE. INSTALLATIONS, BOTH E... $625 $0 Jan 11, 2023
Oct 12, 2022 39071874M ACTIVE CLASS - 2 I OBSERVED IN THE BASEMENT SPRINKLER CONTROL ROOM THE INSTALLATION OF A RECEPTACLE OUTLET BOX IMPROPERLY TO A FLORESC... $1,200 $0 Oct 31, 2022
Oct 11, 2022 39071786M ACTIVE CLASS - 2 I OBSERVED A PUMP IN BOILER ROOM #4 LEAKING PROFUSELY. AS PER PC 602.3.5.PUMPS SHALL BE SEALED TO THE WELL CASING OR ... $625 $0 Oct 31, 2022
Oct 6, 2022 39071863R ACTIVE CLASS - 1 I OBSERVED IN THE GENERATOR AT THE SIDE OF THE BUILDING NO GROUNDING CONDUCTOR INSTALLED AS REQUIRED FOR ELECTRICAL S... $4,800 $0 Oct 31, 2022
Oct 6, 2022 39071733Z ACTIVE CLASS - 2 -AT FIRST FLOOR, CORRIDORS, BOILER ROOM # 4 AND SPRINKLER ROOM SEVERAL OPENING THROUGH FIREPROOF WALLS AND CEILINGS D... $3,125 $0 Oct 31, 2022
Oct 6, 2022 39071720J RESOLVE CLASS - 2 AT CELLAR LEVEL, FIRST/SECOND FLOORS CORRIDORS, SEVERAL OPENING THROUGH WALLS/CEILING DUE PIPES/CABLES PENETRATION WI... $3,125 $0 Oct 31, 2022
Oct 6, 2022 39071732R RESOLVE CLASS - 2 AT FIRST FLOOR, DORM #3 (2UND) EXIT DOORS, EXIT DOOR "L" DO NOT CLOSE PROPERLY WHEN INSPECTED. ALSO, SMOKE DOOR BETWE... $1,562 $0 Oct 31, 2022
Oct 6, 2022 39071615H ACTIVE CLASS - 2 AS PER ONE BURNHAM HEATING BOILER. MODEL NO. V910A. SERIAL NO. 65744382. BOILER NOT REGISTERED; REGISTER BOILER, CALL... $625 $0 Oct 31, 2022
Oct 6, 2022 39071616J ACTIVE CLASS - 2 ELECT. WIRES AT HTG. PUMP EXPOSED-UNEVEN FLUE SECTIONS USED TO CONSTRUCT FLUE PIPE-NO CLEANOUT AT CHIMNEY BASE-RATING... $625 $0 Oct 31, 2022
Oct 6, 2022 39071875Y RESOLVE CLASS - 1 I OBSERVED IN THE BASEMENT STEAM ROOM THE IMPROPER SPLICING OF FLEXIBLE CORDS FOR THE FANS AND POWER CORDS FOR PLUG S... $1,600 $0 Oct 31, 2022
Oct 6, 2022 39071721L RESOLVE CLASS - 2 AT CELLAR LEVEL, ELECTRICAL ROOM & STORAGE ROOMS, WATER PENETRATION THROUGH THE FOUNDATION WALL CREATING DAMAGE TO TH... $3,125 $0 Oct 31, 2022
Oct 6, 2022 39071722N RESOLVE CLASS - 2 AT FIRST/SECOND/THIRD FLOORS, CORRIDORS SMOKE DOORS 20% OF THE DOORS DO NOT CLOSE PROPERLY, ALSO, AT SOUTH WING, SECO... $1,562 $0 Oct 31, 2022
Oct 6, 2022 39071617L ACTIVE CLASS - 2 NO BACKFLOW VALVE FOR BLRS NO. 5 AND 6-NO NAME PLATE ON BLR. NO. 6-FLUE PIPE CONSTRUCTION NOT AS PER BLR. CODE-PRESS.... $625 $0 Oct 31, 2022
Oct 6, 2022 39071618N ACTIVE CLASS - 2 HEATING PUMP LEAKING-NO BACKFLOW VALVE-ELECT. EXPOSED AT PUMP CONNECTION-NO DISCH. PIPE ON PRV FOR HW COIL-OPEN ELECT... $625 $0 Oct 31, 2022
Oct 6, 2022 39071614X ACTIVE CLASS - 2 NAME PLATE FOR BOILER MISSING-NO CLEANOUT AT CHIMNEY BASE-FLUE SEALED W/TAPE AND RESTING ON TOP OF BOILER-SOOT IN BOI... $625 $0 Oct 31, 2022
Oct 6, 2022 39071723P RESOLVE CLASS - 2 AT FIRST FLOOR, CORRIDOR NEAR KITCHEN, CEILING/WALL DAMAGE,STAIRCASE A&C, BETWEEN THIRD AND SECOND FLOOR WALLS, DAMAG... $1,562 $0 Oct 31, 2022
Oct 6, 2022 39071861N RESOLVE CLASS - 2 I OBSERVED AT THE FRONT ENTRANCE ROOFTOP LEVEL THE INSTALLATION OF SEALTITE RACEWAYS FROM THE DISCONNECT SWITCHES TO ... $800 $0 Oct 31, 2022
Oct 6, 2022 39071864Z RESOLVE CLASS - 2 I OBSERVED IN THE PARKING LOTS AND AROUND THE PERIMETER ON THE BUILDING, VARIOUS DEFECTIVE LIGHTS., COMPLY WITH EC; M... $800 $0 Oct 31, 2022
Oct 6, 2022 39071827J ACTIVE CLASS - 2 OBSERVED THROUGHOUT BUILDING SPRINKLER BRANCH LINES UNSUPPORTED. AS PER BC 903 OF 2014 AND 3403.6.8 SPRINKLER PIPING ... $625 $0 Oct 31, 2022
Oct 6, 2022 39071862P RESOLVE CLASS - 1 I OBSERVED IN THE DORM AREA AND IN THE LINEN STORAGE CLOSET THE UNAPPROVED USE OF FLEXIBLE CORDS, THE CORDS WERE SLIC... $1,600 $0 Oct 31, 2022
Aug 25, 2022 35581349Z ACTIVE CLASS - 1 STRUCTURE RENDERED NON-COMPLIANT. HOUSE OF WORSHIP SUSTAINED EXTENSIVEDAMAGE DUE TO FIRE CONSISTING OF CHARRED WOOD J... $1,250 $0 May 4, 2023
May 26, 2022 39063014M ACTIVE CLASS - 2 OBSERVED ON FIRST FLOOR ACTIVE WATER LEAK AT CEILING FROM HVAC SYSTEM THAT'S LOCATED ON THE FLOOR ABOVE., REPAIR AND/... $625 $0 Jun 7, 2022
May 26, 2022 39063000L RESOLVE CLASS - 2 AT FIRST FLOOR, EXIT DOORS, STAIRCASE A, B & - B107 DO NO CLOSE PROPERLY WHEN INSPECTED, REPAIR/REPLACE DOOR $625 $0 Jun 7, 2022
Apr 8, 2022 35651054M RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER NO FIRE STOPPING PER BC 712.3; 27-345 OBSERVED AT ROOF LEVEL ME... $1,250 $0 Jul 21, 2022
Apr 8, 2022 35651063Y RESOLVE CLASS - 2 EXIT DOOR NOT SELF CLOSING OBSERVED AT 1ST FLOOR SELF CLOSING FIREPROOF DOORS SEVERAL DOORS SHOW DEFECTS AS SELF CLOS... $625 $0 Jul 21, 2022
Apr 8, 2022 35651055Y RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER OBSERVED AT 2ND FLOOR ACOUSTICAL CEILING SEVERAL MISSING PANELS... $625 $0 Jul 21, 2022
Apr 8, 2022 35651053K RESOLVE CLASS - 2 EXIT DOOR NOT SELF CLOSING.OBSERVED SELF CLOSING FIREPROOF DOORS AT 2ND FLOOR CORRIDOR SMOKE DOOR NEXT TO EXIT "N" SM... $625 $0 Jul 21, 2022
Apr 8, 2022 35651068N ACTIVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER OBSERVED AT 1ST FLOOR ACOUSTICAL CEILING SEVERAL MISSING/DAMAGE... $625 $0 Jul 21, 2022
Apr 8, 2022 35650622R RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER OBSERVED 1ST FLOOR CORRIDOR NEAR KITCHEN DAMAGE TO CEILING & WA... $625 $0 Jul 21, 2022
Apr 8, 2022 35651050P RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING WALL(S) OR APPURTENANCES OBSERVED AT CELLAR LEVEL STORAGE ROOM FOUNDATION WALL WATER PEN... $1,250 $0 Jul 21, 2022
Apr 8, 2022 35650624K RESOLVE CLASS - 2 FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.NO FIRE STOPPING PER BC 712.3; 27-345.OBSERVED AT 2ND & 1ST FLO... $1,250 $0 Jul 21, 2022