ECB violations
Chauncey Street, Brooklyn • Block 01691 • Lot 0012
80 records
Environmental Control Board violations, which carry a hearing and a penalty.
| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 24, 2026 | 39186027L | ACTIVE | CLASS - 2 | 1) THE DRIVE SHEAVE IS WORN (8.11.2.1.2) 2) THE FLOOR INDICATOR IN THE CAR DOES NOT WORK (8.11.2.1.1) 3) THE CAT-1 TA... | $625 | $0 | Jul 31, 2026 |
| Aug 28, 2025 | 39158702H | ACTIVE | CLASS - 2 | FOUND WEIL MCLAIN BOILER MODEL 994 WITH DEFECTS. BAROMETRIC DAMPER DEFECTIVE. DRAIN CLOGGED WITH STANDING WATER. EVID... | $1,250 | $0 | Jun 12, 2026 |
| Oct 24, 2023 | 39097787J | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. DIRTY CAB MIRROR. WATER IN PIT. WORN ROLLER GUIDE. SEAL HOI... | $625 | $0 | Jan 3, 2024 |
| Aug 30, 2023 | 39093768X | RESOLVE | CLASS - 2 | CLASS 2: HANDRAIL LOOSE REPAIR & SECURE TO BACK WALL. CAR DOOR MISALIGNED CAUSING RUBBING/SCRAPPING ADJUST TO REMOVE.... | $625 | $0 | Nov 8, 2023 |
| Jul 27, 2023 | 39091261H | RESOLVE | CLASS - 2 | AT TIME OF INSPECTION OBSERVED (2) WORKERS INSTALLING NEW ELECTRICAL SERVICE AT CELLAR LEVEL AND NEW ELECTRICAL ROUHG... | $0 | $0 | Oct 11, 2023 |
| May 4, 2023 | 39085523H | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. CLEAN MACHINE ROOM. INSUFFICIENT MAINTENANCE LOG. REMOVE NO... | $0 | $0 | Jul 12, 2023 |
| May 4, 2023 | 39085522X | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. CLEAN MACHINE ROOM. INSUFFICIENT MAINTENANCE LOG. REMOVE NO... | $0 | $0 | Jul 12, 2023 |
| May 4, 2023 | 39085521Y | RESOLVE | CLASS - 2 | REPLACE WORN GIBS WHERE NEEDED. SECURE GIBS WHERE NEEDED. CLEAN MACHINE ROOM. INSUFFICIENT MAINTENANCE LOG. REMOVE NO... | $0 | $0 | Jul 12, 2023 |
| May 4, 2023 | 39085520M | RESOLVE | CLASS - 2 | RESTORE DEVICE TO SERVICE. | $0 | $0 | Jul 12, 2023 |
| Feb 13, 2023 | 39079566R | RESOLVE | CLASS - 2 | IN CAR COMMUNICATION INOPERATIVE, REPAIR. | $312 | $0 | Jun 28, 2023 |
| Jun 30, 2022 | 39065031N | RESOLVE | CLASS - 2 | FOUND WEIL MCLAIN GAS FIRED BOILER MODEL-994 ACTIVE WITH DEFECTS. THERMAL SPILL SWITCH DEFECTIVE. CORRECT ALL VIOLATI... | $312 | $0 | Nov 2, 2022 |
| Mar 14, 2022 | 39057976M | RESOLVE | CLASS - 1 | OUT OF SERVICE. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT-OF-SERVICE. REMEDY: RESTORE TO SERVICE IMMEDIATELY AND... | $1,250 | $0 | Jul 20, 2022 |
| Jan 7, 2020 | 38272843Y | RESOLVE | CLASS - 1 | 42M05,71X10,60X10:42-M-05 NO DOOR LOCK MONITORING INSTALLED IN THIS CONTROLLER AS MANDATED BY 3.10.12 OF APPENDIX K3 ... | $1,250 | $0 | Dec 10, 2020 |
| Nov 9, 2018 | 32096994N | RESOLVE | CLASS - 1 | B154,51. WEIL MCLAIN BOILER MODEL #994 HAS VIOLATING CONDITIONS AND CRACKED SECTION ON THE REAR / RIGHT AREA OF BOILE... | $0 | $0 | Feb 4, 2019 |
| Apr 9, 2018 | 32096291R | RESOLVE | CLASS - 2 | 23,32A,34B,50,50A,50B. 50-POOR FLAME FROM BURNER; 50A-FRONT RIGHT FLUE DOOR IMPROPER CLOSING; 50B-FRONT FLAME SIGHT G... | $312 | $0 | Feb 25, 2019 |
| Apr 9, 2018 | 32096292Z | RESOLVE | CLASS - 2 | 23,32A,50. 50-POOR FLAME FROM BURNER. | $312 | $0 | Feb 25, 2019 |
| Dec 5, 2017 | 38259900P | RESOLVE | CLASS - 1 | 66L10)EMERGENCY ROPE GRIPPER DEFECTIVE, REPAIR. WHEN MAIN LINE IS IN ROPE GRIPPER IS STILL LOCKS UP. | $1,000 | $0 | Jan 30, 2018 |
| Nov 6, 2017 | 38259223R | RESOLVE | CLASS - 2 | 7L10;1L10;70O2:CAR DOOR HAS TOO MUCH GAP WHEN DOOR OPEN/ON RETURN POST DEFECTIVE-REPAIR;PITLIGHTDEFECTIVE-REPAIR;PIT ... | $250 | $0 | Mar 5, 2018 |
| Jul 24, 2017 | 38257001M | RESOLVE | CLASS - 2 | 8V1,5J1,10H11,16J1,17H11,29J1,59BB7,56Y2,56Y13,77K10. 8V1-CAR FLOOR TO LANDING SILL NOT LEVEL ADJUST; 5J1-CAR DOOR MI... | $250 | $0 | Sep 11, 2017 |
| Apr 12, 2017 | 32088107H | RESOLVE | CLASS - 2 | B254,50A,50B,50C. FULTON V.T. BOILER 15HP,NB83141,HP STM OIL BUILT 1999.450A-LOWER HANDHOLE PORTS BULGED. REMOVE CEME... | $250 | $0 | Jun 5, 2017 |
| Mar 14, 2016 | 38241118J | RESOLVE | CLASS - 1 | 05X10,05J01,14M11,09K10,12B07,40B07,56Y02,59U15,67X10,71B07. 05X10-DOOR RESTRICTOR DISABLED; 05J01-EXCESSIVE GAPS(CAR... | $1,000 | $0 | Jul 25, 2016 |
| Mar 14, 2016 | 38241117H | RESOLVE | CLASS - 1 | 05X10.05X10-DOOR ZONE RESTRICTOR HAS BEEN DISABLED. | $1,000 | $0 | Jun 13, 2016 |
| Dec 2, 2015 | 38239491P | RESOLVE | CLASS - 2 | 67,X,10,05,X,10.67-X-10:PHONE IN ELEVATOR NOT WORKING;05-X-10:DOOR RESTRICTOR NOT WORKING. | $0 | $0 | Jan 25, 2016 |
| Dec 2, 2015 | 38239492R | RESOLVE | CLASS - 2 | 97,X,10.97-X-10:ELEVATOR IS OUT FOR REPAIR OF REPAIRS AND HOISTING DEVICE.RETURN ELEVATOR TO AND COMPLETE REPAIRS. | $0 | $0 | Jan 25, 2016 |
| Aug 18, 2015 | 38238154J | RESOLVE | CLASS - 2 | 97X07 RESTORE TO SERVICE. | $0 | $0 | Oct 5, 2015 |
| Aug 4, 2015 | 35044498Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN NOV #35116334M ISSUED ON 6/10/15 AND TO FILE A CERTIFICA... | $0 | $0 | May 31, 2016 |
| Jun 10, 2015 | 35116334M | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED: AS A RESULT OF FIRE AT THE 5TH AND 2ND FLRS, SMOKE DAMAGE TO... | $1,000 | $0 | Oct 26, 2015 |
| Apr 27, 2015 | 38235934R | RESOLVE | CLASS - 2 | 67X10,05X10,98M07,68B07,60X10,13I10. 67X10-REPAIR EMERGENCY PHONE;05X 10-REPAIR DOOR ZONE LOCK; 98M07-MISSING CAT5 TE... | $0 | $0 | Jun 15, 2015 |
| Feb 18, 2015 | 35119740L | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN,CORRIDOR WIDTH PER BC 1016.2,27-369.NOTED:@ 1ST FLUPK,APPROX 50% CORRIDOR OBSTRUCTION W/ TABLES,C... | $0 | $0 | Apr 27, 2015 |
| Aug 29, 2012 | 38222871X | RESOLVE | CLASS - 2 | 70O2,41I10,02L10,67L10: 70O02;CLEAN PIT. 41I10;MOTOR ROOM DOOR DAMAGED02L10;ALARM BUTTON NOT WORKING. 07L10;PHONE NOT... | $0 | $0 | Oct 15, 2012 |
| May 7, 2012 | 38221806P | RESOLVE | CLASS - 1 | 28-116.4.1: 16R07:OPERATING DEVICE WITHOUT A CERT OF COMPLIANCE. NO REPORT OF INSPECTION SUBMITTED TO DOB & NO WITNES... | $1,600 | $0 | Jun 25, 2012 |
| May 7, 2012 | 38221807R | RESOLVE | CLASS - 1 | 28-116.4.1: 44R07;OPERATING DEVICE WITHOUT A CERT OF COMPLIANCE. NO REPORT OF INSPECTION SUBMITTED TO DOB & NO WITNES... | $1,600 | $0 | Jun 25, 2012 |
| Feb 4, 2012 | 38214984M | RESOLVE | CLASS - 1 | 16I10 3I10 21I10 97#10 FIRE DAMAGE TO ELEVATOR DUE TO FIRE IN HALLWAY @ 6TH FL | $0 | $0 | Jun 11, 2012 |
| Mar 3, 2011 | 38210796R | RESOLVE | CLASS - 2 | 97X10/ 97-X-10 RESTORE TO SERVICE SO PROPER INSPECTION CAN BE DONE BY THIS DEPT | $250 | $0 | May 16, 2011 |
| Sep 14, 2010 | 38212834H | RESOLVE | CLASS - 1 | 61L11,43N11,40Y02,41I11,52B07,56Y10,56O02,58V10,60X10,42R09,100D06,75I10,67X10,13X11,24I10,78E10. CEASE USE. 61L- MAI... | $1,000 | $0 | Jan 24, 2011 |
| May 8, 2009 | 38201736K | RESOLVE | CLASS - 1 | 16I11,16AI11,16A11, 16-REPLACE ALL HOISTWAY ROTTED DOORS FLOORS. BASE MENT, LOBBEY (1ST, 2ND, 3RD, 4TH , 5TH, 6TH) 16... | $1,000 | $0 | Jun 21, 2010 |
| Jan 5, 2009 | 38199112M | RESOLVE | CLASS - 2 | 12B10.70O02.12B LIGHTS OUT IN CAR | $0 | $0 | Mar 2, 2009 |
| Jan 5, 2009 | 38199113Y | RESOLVE | CLASS - 2 | 16B10.70O02.14M07.12M07.24X10.16B GATE NOT OPENING ALL THE WAY GETTING STUCK | $0 | $0 | Mar 2, 2009 |
| Jan 5, 2009 | 38199115H | RESOLVE | CLASS - 2 | 70O02.05H11.05 CAR SADDLE WORN | $0 | $0 | Mar 2, 2009 |
| Jan 5, 2009 | 38199114X | RESOLVE | CLASS - 1 | 56Y13.05B01 56Y OIL LEAK LOUD NOISE FROM MACHINE 05B DOOR NOT OPENING ALL THE WAY CALL 212 566-5539 | $1,000 | $0 | Mar 2, 2009 |
| Sep 26, 2008 | 38188799Y | RESOLVE | CLASS - 3 | 60X07,09H10,70O02. 60X NO LIGHTS IN MOTOR ROOM | $200 | $0 | Oct 7, 2009 |
| Sep 26, 2008 | 38188798M | RESOLVE | CLASS - 2 | 56Y13,41I10,14M07,08I10,70O02 | $500 | $0 | Nov 17, 2008 |
| Sep 26, 2008 | 38188797K | RESOLVE | CLASS - 2 | 09H11,12B07,24X10,15M07,70O02,60X07,56Y13. 09H WORK CAR FLOOR | $500 | $0 | Oct 7, 2009 |
| Aug 29, 2008 | 38188723H | RESOLVE | CLASS - 1 | THIS DEVICE HAS BEEN CEASE USE DUE TO NOISE COMING FROM MACHINE AND HOISTWAY WHEN ELEVATOR RUNNING. | $1,000 | $0 | Oct 20, 2008 |
| Aug 29, 2008 | 38188724J | RESOLVE | CLASS - 3 | 60L07,59H11,67L11,17H11,71L10,70O02. 60 PROVIDE LIGHT IN MACHINE ROOM.59 RELINE MACHINE BRAKE. 67 PROVIDE OUTSIDE COM... | $100 | $0 | Oct 20, 2008 |
| Aug 29, 2008 | 38190875J | RESOLVE | CLASS - 3 | 60L07,42G11,17H11,67L07,70O02. 60 PROVIDE LIGHT IN MACHINE ROOM. 42 REPLACE IMPROPER FUSE. 17 REPLACE (ALL HOISTWAY D... | $100 | $0 | Oct 20, 2008 |
| May 1, 2008 | 38182300Z | RESOLVE | Non-Hazardous | 83X10 83 REPAIR & RESTORE ELEVATOR TO SERVICE SO THAT A FULL INSPECTION CAN BE MADE BY THIS DEPT | $2,500 | $0 | Jun 23, 2008 |
| Apr 7, 2008 | 38183825X | RESOLVE | Non-Hazardous | 02X10,14M07,38O02,51B07,03M07,66O02,40I10,42N10,39A07.02X-CAR PHONE,51B-PROPER ANTI SPINOUTS.03M-TOE GUARD.39A-REMOVE... | $0 | $0 | Jun 2, 2008 |
| Apr 7, 2008 | 38183249R | RESOLVE | Non-Hazardous | 02X10,14M07,51B07,66O02,39A07,42N10.02X-CAR PHONE.51B-PROPER ANTI SPINOUTS.39A-REMOVE WOOD FROM CONTROLLER & MOTOR ROOM. | $180 | $0 | Jun 2, 2008 |
| Apr 7, 2008 | 38183247N | RESOLVE | Non-Hazardous | 16E10,02X10,17H11,09I10,13I10,03M07,39A09.16E-5FL.02X-CAR PHONE.17H-5FL.03M-TOE GUARD.39A-REMOVE WOOD FRAME CONTROLLE... | $0 | $0 | Jun 2, 2008 |