| Issued | Violation | Status | Severity | Description | Penalty | Balance due | Hearing |
|---|---|---|---|---|---|---|---|
| Apr 12, 2018 | 35331925X | RESOLVE | CLASS - 1 | WORK WITHOUT A PERMIT.OBSERVED ON THE 4TH FLR A POWER VENTED HOT WATERHEATER INSTALLED WITH WATER GAS AND FLUE PIPING... | $0 | $0 | Jun 5, 2019 |
| Apr 12, 2018 | 35331032Z | RESOLVE | CLASS - 2 | EC410.64/USE OF LUMINAIRES AS A RACEWAY.OBSERVED IN THE STAIRWELL OF THE FRONT SECTION OF THE BUILDING THE USE OF THE... | $2,000 | $0 | Jul 23, 2018 |
| Apr 12, 2018 | 35331030P | RESOLVE | CLASS - 2 | FAILURE TO PROVIDE GROUND FAULT CIRCUIT INTERRUPTOR(GFCI)PROTECTION ASPER SECTION.OBSERVED IN THE 2FLR BATHROOM LOCAT... | $5,000 | $0 | Jul 23, 2018 |
| Apr 12, 2018 | 35331029H | RESOLVE | CLASS - 1 | FAILURE TO PROVIDE DISCONNECTING MEANS.OBSERVED ON 2ND FLR IN ROOM LABELED 206,ADJACENT TO THE BATHROOM A GAS FIRED H... | $4,000 | $0 | Jul 23, 2018 |
| Mar 31, 2018 | 35326332Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35289628N ISSUED ON 8/16/17 & TO FILE A C OF C PURSUANT... | $1,250 | $0 | Aug 6, 2018 |
| Mar 31, 2018 | 35326333X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35289910R ISSUED ON 8-16-17 & TO FILE A C OF C PURSUANT... | $1,250 | $0 | Aug 6, 2018 |
| Mar 27, 2018 | 35313019P | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED AT 2:30PM 8FT FLORESCENT FIXTURES INSTALLED IN HALLWAYS,CLASSROOMS FROM THE 4T... | $1,600 | $0 | Jul 9, 2018 |
| Mar 17, 2018 | 35324719J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35289909J ISSUED ON 8-16-17 & TO FILE A C OF C PURSUANT... | $1,250 | $0 | Oct 3, 2018 |
| Feb 22, 2018 | 35312853M | RESOLVE | CLASS - 1 | UNLAWFUL ACTS FAILURE TO COMPLY WAITH AN ORDER OF THE COMMISSIONER. RECORDS INDICATE NO APPLICATION WAS MADE TO CORRE... | $0 | $0 | Apr 16, 2018 |
| Feb 12, 2018 | 35283486J | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLAT ION #35289910R ISSUED ON 08/16/17 AND TO FILE A ... | $800 | $0 | Oct 3, 2018 |
| Feb 12, 2018 | 35283485H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLAT ION #35289628N ISSUED ON 08/16/17 AND TO FILE A ... | $800 | $0 | Oct 3, 2018 |
| Jan 21, 2018 | 35282173Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35289909J ISSUED ON 08/16/17 & TO FILE A C OF C PURSUAN... | $2,000 | $0 | Mar 19, 2018 |
| Dec 27, 2017 | 35282426N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35289910R ISSUED ON 8/16/17 & TO FILE A... | $2,000 | $0 | Feb 12, 2018 |
| Dec 27, 2017 | 35282427P | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION# 35289628N ISSUED ON 8/16/17 & TO FILE A... | $2,000 | $0 | Feb 12, 2018 |
| Dec 13, 2017 | 35274222L | RESOLVE | CLASS - 1 | UNLAWFUL ACT,FAILURE TO COMPLY WITH AN ORDER OF THE COMMISSIONER.RECORDS INDICATE NO APPLICATION FILED TO CERTIFY,COR... | $0 | $0 | Jan 29, 2018 |
| Dec 2, 2017 | 35282306Z | RESOLVE | CLASS - 2 | FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO#35289909J ISSUED ON 08/16/17 & TO FILE A C OF C PURSUAN... | $2,000 | $0 | Mar 19, 2018 |
| Nov 9, 2017 | 35279397X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35289628N ISSUED ON 08/16/17 & TO FIL... | $800 | $0 | Mar 7, 2018 |
| Nov 9, 2017 | 35279398H | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION #35289910R ISSUED ON 08/16/17 & TO FIL... | $800 | $0 | Mar 14, 2018 |
| Oct 11, 2017 | 35293697Z | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,DEVICES,MATERIALS,APPLIANCES OR WIRING IN USE.DEPARTMENT ... | $0 | $0 | Apr 4, 2018 |
| Oct 5, 2017 | 35279804Y | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35289910R ISSUED ON 08/16/17 & TO FILE A C... | $800 | $0 | Apr 18, 2018 |
| Oct 5, 2017 | 35279803M | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35289628N ISSUED ON 08/16/17 & TO FILE A C... | $800 | $0 | Apr 4, 2018 |
| Oct 5, 2017 | 35279805X | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIO # 35289909J ISSUED ON 08/16/17 & TO FILE A C... | $800 | $0 | Apr 4, 2018 |
| Aug 16, 2017 | 35289628N | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.OBSERVED ON 8/16/17 @ ABOVE ADDRESS EXCESSIVE AMOUNT OF STORAGE THR... | $1,000 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289910R | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTED:AT SUB-CELLAR,STORAGE RM NEXT TO ELECTRICAL METER RM,I-BEAMS ... | $1,000 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289913M | RESOLVE | CLASS - 2 | ALTERED/CHANGED BUILDING OCCUPIED WITHOUT A VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1-28-118.3.2 PERMIT #30183... | $500 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289688P | RESOLVE | CLASS - 1 | SERVICE IN EXCESS OF 1000KVA HASN'T BEEN SUBMITTED FOR APPROVAL. OBSERVED IN BSMT THE INSTALLATION OF 3 SERVICE SWITC... | $1,600 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289631Y | RESOLVE | CLASS - 1 | FGC401.1. GAS PIPING NOT LABELED. OBSERVED ON 8/16/17 @ ABOVE ADDRESS GAS PIPING THROUGHOUT BSMT ISN'T LABELED. PHOTO... | $1,600 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289630M | RESOLVE | CLASS - 1 | FGC403.8. UNPAINTED GAS PIPE NOT PROTECTED FROM CORROSIAN. OBSERVED ON8/16/17 @ ABOVE ADDRESS GAS PIPING TO HEATINGS ... | $1,600 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289627L | RESOLVE | CLASS - 1 | FGC408.2. FUTURE CONNECTIONS EXIST. OBSERVED ON 8/16/17 @ ABOVE ADDRESS FUTURE GAS CONNECTIONS EXIST DOWN STRAM OF AP... | $1,600 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289689R | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O A PERMIT. OBSERVED IN BSMT THE INSTALLATION MAIN ELECTRICAL SERVICE EQUIPMENT,SWITCHES,ELE. PANEL... | $1,600 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289693J | RESOLVE | CLASS - 1 | FAILURE TO PROPERLY BOND ELECTRICAL SYSTEMS.OBSEVED IN BSMT:A 400 AMP 3 PHASE SEVICE DISCONNECT SWITCH NOT PROPERLY B... | $1,500 | $0 | Mar 19, 2018 |
| Aug 16, 2017 | 35289909J | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY COFO OF DOB RECORDS.COFO#136987 INDICATES BLDG TO BE 5 STRY W/WAREHOUSE OCCUPYI... | $2,400 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289690Y | RESOLVE | CLASS - 1 | UNAPPROVED,UNSAFE,UNSUITABLE ELECTRICAL EQUIPMENT,APPARATUS,DEVICES,MATERIALS,APPLIANCES OR WIRING IN USE. OBSERVED I... | $1,000 | $0 | Feb 28, 2018 |
| Aug 16, 2017 | 35289629P | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED ON 8/16/17@ ABOVE ADDRESS NO FINAL SPRINKLER INSPECTION P... | $500 | $0 | Feb 28, 2018 |
| Apr 12, 2015 | 35063015Z | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/THE COMMISSIONER'S ORDER CONTAINED IN NOTICE OF VIOLATION #35057875H ISSUED ON 10/16/14. NO PERMI... | $2,400 | $0 | Aug 3, 2015 |
| Jan 16, 2015 | 38234009P | RESOLVE | CLASS - 1 | 97R07 - ILLEGAL OPERAITON OF DEVICE 3P13407 OPERATING W/O CERTIFICATE OF COMPLIANCE OR EXPIRED CERTIFICATE OF COMPLIA... | $1,000 | $0 | May 11, 2015 |
| Jan 15, 2015 | 35119249L | RESOLVE | CLASS - 2 | OPERATION OF A PLACE OF ASSEMBLY W/O A CURRENT CERTIFICATE OF OPERATION.CURRENTLY BLDG USED AS A RELIGIOUS SCHOOL & 6... | $400 | $0 | Oct 26, 2015 |
| Jan 15, 2015 | 35119577K | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.NOTICE STOPPING PER BC 712.3;27-345,@ EVERY LEVEL CLASSROOMS,THERE ... | $250 | $0 | Oct 30, 2015 |
| Jan 15, 2015 | 35119576Z | RESOLVE | CLASS - 2 | FAILURE TO MAINTAIN TO BLDG IN CODE COMPLIANT MANNER.ILLUMINATION FOR EXITS,EXIT DISCHARGES AND PUBLIC CORRIDORS PER ... | $250 | $0 | May 4, 2015 |
| Jan 15, 2015 | 35119248J | RESOLVE | CLASS - 2 | ALTERED/CHANGED BLDG OCCUPIED W/O VALID CERTIFICATE OF OCCUPANCY AS PER 28-118.3.1 & 28-118.3.2.C OF O #136987 OF OCT... | $400 | $0 | May 4, 2015 |
| Oct 16, 2014 | 35041163N | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMM ORDER TO FILE A CERT OF CORRECTION WITH THE DOB FOR NOV #5097651P ISSUED ON 08/21/14 ... | $800 | $0 | Mar 30, 2015 |
| Oct 16, 2014 | 35041162L | RESOLVE | CLASS - 2 | FAILURE TO COMPLY WITH THE COMM ORDER TO FILE A CERT OF CORRECTION W/ THE DOB FOR NOV #35097374X ISSUED ON 8/21/14 PU... | $0 | $0 | Mar 30, 2015 |
| Oct 16, 2014 | 35057875H | RESOLVE | CLASS - 1 | FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER TO CONTAINED IN NOTICE OF VIOLATION # 35097650N ISSUED ON 08/21/14. AT ... | $2,400 | $0 | Mar 30, 2015 |
| Aug 21, 2014 | 35097374X | RESOLVE | CLASS - 1 | OCCUPANCY CONTRARY TO THAT ALLOWED BY THE C OF O. #136987 DATED 10/23/53 WHICH INDICATE CELLAR THROUGH 5TH FLOORS AS ... | $0 | $0 | Jan 14, 2015 |
| Aug 21, 2014 | 35066825Y | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. FOUND THAT ADDRESS ABOVE HAS INSTALLED A GAS FIRED DIRECT VENT UNIT IN BLDG NO PERMITS WERE ISSUED... | $1,600 | $0 | Jan 14, 2015 |
| Aug 21, 2014 | 35066449J | RESOLVE | CLASS - 2 | WORK W/O A PERMIT. FOUND THAT ADDRESS ABOVE HAS INSTALLED MULIPLE BATHROOMS THOUGHOUT THE BLDG PORHU OF THE DAY CARE ... | $0 | $0 | Jan 14, 2015 |
| Aug 21, 2014 | 35097650N | RESOLVE | CLASS - 1 | WORK W/O A PERMIT. FULL HEIGHT PARTITIONS ERECTED TO ENCLOSE/CREATE CLASSROOMS,KITCHENS,BATHROOMS W/INSTALLATION OF N... | $1,600 | $0 | Jan 12, 2015 |
| Aug 21, 2014 | 35039114Y | RESOLVE | CLASS - 2 | FAIL TO PROVIDE EFFECTIVE CONTINUITY FOR METAL RACEWAYS,ENCLOSURES,ARMORED CABLES. (1040 AR) OBSERVED IN 2ND FL CLASS... | $0 | $0 | Jan 14, 2015 |
| Aug 21, 2014 | 35097651P | RESOLVE | CLASS - 1 | FAILURE TO MAINTAIN BLSG IN CODE COMPLIANT MANNER,NOTED AT THE TIME OFINSPECTION DEFECTIVE & MISSING PANIC BARS @ EGR... | $1,000 | $0 | Jan 14, 2015 |
| Aug 21, 2014 | 35039113M | RESOLVE | CLASS - 1 | ELECTRICAL WORK W/O PERMIT. ELECTRICAL WIRING & INSTALLATION OF PANELS,FEEDERS,BRANCH CIRCUITS,RECPTICLE OUTLETS,SWIT... | $0 | $0 | Jan 14, 2015 |